ELK-MM220 HOOK-UP DIRECTIONS

The ELK-MM220 has been factory programmed with a sample application as labeled on
the unit, for other applications it must be reprogrammed before installation.
 The Program
Development Kit (ELK-MK400S) is required to re-program the ELK-MM220 if desired. The Develop-
ment Kit contains software and programming instructions needed to program the ELK-MM220. The
program is written using the Elk Magic Module Software and debugged by using the ELK-MM443
Magic Module that is included in the development kit. The program is then download into the ELK-
MM220 through a 5 conductor ribbon cable connected between the ELK-MM443 J1 connector and
the ELK-MM220 J5 connector. Note: If using the Clock/Calendar Module(ELK-MC100), temporarily
remove it to gain access to the ELK-MM443 J1 connector.

The ELK-MM220 has two digital inputs that switch from Low to High at approximately 2 Volts. Each
input is jumper selectable at J1 & J2 for an onboard 2K input resistor either pulled up to +12 Volts,
or pulled down to Ground. The ELK-MM220 has two form C relay outputs. Relay 2 is jumper
selectable using J3 to switch the output through a transistor (100mA max). Placing J3 to the OUT
position will disable Relay 2 and allow the Relay 2 COM terminal to be pulled to ground through a
transistor when activated. This setting handles up to 100mA of current and is intended for applica-
tions like flashing an LED. If more current or dry contacts are required then set J3 to IN and use the
Relay 2 contacts, the transistor will be disabled.

Test the ELK-MM220 after downloading the program to ensure that it functions as desired. The
ELK-MM220 can be reprogrammed multiple times.

*The ELK-MM220S version is required if using Savoy Automation Software.

GND

To Input Circuitry

+12 VDC

2K

Normally Closed

Opens from

Ground

Input HookupTypes for IN1 and IN2

INx

2

OUTPUT

ELK-MM220

PROGRAMMER

1

NO COM NC

NO COM NC

IN1 IN2 NEG

+12V NEG

RELAY 2

RELAY 1

J1

J2

INPUT 2
SELECT

J3

+12V

GND

INPUT 1
SELECT

RELAY 2

OUT IN

J5

D4

D3

MM220

will see a
Low to Hi

when

Switch
Opens

J1 or J2

NEG

GND

Input

Jumper
is set to

+12V

GND

To Input Circuitry

+12 VDC

2K

Normally Closed

Opening switch will

trip this input

INx

MM220

will see a
Hi to Low

when

switch

Opens

J1 or J2

NEG

GND

Input

Jumper
is set to

GND

+2 to 12 Volts DC

GND

To Input Circuitry

+12 VDC

2K

Normally Open

Closes to

Ground

INx

MM220

will see a
Hi to Low

when

Switch
Closes

J1 or J2

NEG

GND

Input

Jumper

is set to

+12V

GND

To Input Circuitry

+12 VDC

2K

Normally Open

Closing Switch to

2 to 12 Volts DC

will trip this input

INx

MM220

will see a
Low to Hi

when

Switch
Closes

J1 or J2

NEG

GND

Input

Jumper

is set to

GND

+2 to 12 Volts DC

+12 Volt DC Power Supply

ELK-624 Recommended

+

-

N.O.

N.C.

ALARM

SWITCHES

12 VOLT

SIREN

(ELK-45)

+

-

IN1 is a Momentary Key Switch, IN2 is a Normally Closed Burglar Loop, Relay 1 is the Alarm Output, Relay 2 is the Status LED

1K

J3 is shown with

Relay 2 out of ciruit,

the COM terminal will

be pulled to ground

when output 2 is

activated

(100ma Max)

LED

RELAYS

ACTIVE

LEDS

+

-

+

-

+12V position pulls up

IN1 or IN2 through a

2K resistor

GND position pulls

down IN1 or IN2

through a 2K resistor

+

Example Hookup: ELK-MM220 used as a Single Zone Security System

JUMPERS J1, J2 ,J3 are

located under cover

MOMENTARY

KEY SWITCH