PAR. DESCRIPTION
M.U.
RANGE
EZ-HT
EZ-MT
EZ-LT
dt
drainage time. Coil drainage time.
min
0 ... 250
5
5
dFd Allows exclusion of the evaporator fans to be selected or not during
defrosting.
n
(0) = No (it depends on
FCO
);
y
(1) = Yes (fans excluded). flag
n/y
y
y
FCO
Allows to select compressor fans lock OFF (switched off).
H42 FCO
COMPRESSOR ON
COMPRESSOR OFF
H42 = y
0
Thermostat controlled
OFF
1
Thermostat controlled
Thermostat controlled
2
Not used
Not used
3
Not used
Not used
H42 = n
0
ON
OFF
1
Not used
Not used
2
Not used
Not used
3
Not used
Not used
num
0 ... 3
1
1
Att
HAL
and
LAL
parameters mode, i.e. the absolute temperature value or
differential in relation to the setpoint.
0
= Absolute value;
1
= Relative value.
flag
0/1
0
0
0
AFd Alarms activation differential.
°C/°F 1.0 ... 50.0
2.0
2.0
2.0
HAL
Temperature value (intended either as distance from setpoint or as an
absolute value based on
Att
) which, if exceeded in an upward direction,
triggers the activation of the alarm signal.
°C/°F
LAL ... 320
50.0
50.0
50.0
LAL
Temperature value (intended as distance from setpoint or as an absolute
value based on
Att
) which, if exceeded in an upward direction, triggers the
activation of the alarm signal.
°C/°F -67.0 ... HAL
-50.0
-50.0
-50.0
PAO Alarm override time after device is switched on following a power outage. hours
0 ... 10
0
0
0
dAO Temperature alarm exclusion time after defrost.
min
0 ... 999
0
0
0
OAO Alarm signal delay (low and high temperature) after the deactivation of
the digital input (port closed).
hours
0 ... 10
0
0
0