EWTQ 905

7/8

PARAMETERS TABLE

Par.

Description

Range

Def.

Group “]SP” (parameters relative to the Set Point)
1

SP1

Set Point 

SPLL ÷ SPHL

0

2

SPLL

Low Set Point 

-1999 ÷ SPHL

-1999

3

SPHL

High Set Point 

SPLL ÷ 9999

9999

Group “]InP” (parameters relative to the measure input)
4

SEnS

Probe type

input C : 
J / CrAL / S / Ir.J / Ir.CA / Pt1 / 0.50 / 0.60 / 12.60

J

input E :
J / CrAL / S /Ir.J / Ir.CA / Ptc/ ntc / 0.50 / 0.60 / 12.60

Ptc

input I :
0.20 / 4.20

4.20

input V :
0.1 /0.5 / 1.5 / 0.10 / 2.10

0.10

5

SSC

Low scale limit in case of input with V / I signals 

-1999 ÷ FSC

0

6

FSC

High scale limit in case of input with V / I signals 

SSC ÷ 9999

0

7

dP 

Number of decimal figures

Pt1 / Ptc / ntc: 0 / 1
norm sig.: 0 ÷ 3

0

8

Unit

Temperature unit of measurement

°C / °F

°C

9

FiL

Input digital filter

0FF÷ 20.0 sec.

0.1

10

OFSt

Measuring Offset

-1999 ÷ 9999

0

11

rot 

Rotation of the measuring straight line

0.000 ÷ 2.000

1.000

12

OPE 

Output power in case of measuring error

-100 ÷ 100%

0

Group “]Out” (parameters relative to the outputs)
13

O1F

Functioning of output 1

1.rEG / 2.rEG ALno / ALnc ALni / OFF

1.rEG

14

O2F

Functioning of output 2

1.rEG / 2.rEG ALno / ALnc ALni / OFF

ALno

Group “]AL1” (parameters relative to alarm AL1)
15

OAL1

Output where alarm AL1 is addressed

Out1 / Out2 /OFF

Out2

16

AL1t

Alarm AL1 type

LoAb / HiAb LHAb / LodE HidE / LHdE

LoAb

17

AL1

Alarm AL1 threshold

AL1L÷ AL1H

0

18

AL1L

Low threshold band alarm AL1 or 
Minimum set alarm AL1 for high or low alarm 

-1999 ÷ AL1H

-1999

19

AL1H

High threshold band alarm AL1 or 
Maximum set alarm AL1 for high or low alarm 

AL1L ÷ 9999

9999

20

HAL1

Alarm AL1 hysteresis

OFF ÷ 9999

1

21

AL1d

Activation delay of alarm AL1

OFF ÷ 9999 sec.

OFF

22

AL1i

Alarm AL1 activation in case of measuring error

no / yES

no

Group “]rEG” (parameters relative to the control)
23

Cont

Control type

Pid / On.FA On.FS / nr

Pid

24

Func

Functioning mode output 1rEg

HEAt / CooL

HEAt

25

HSEt

Hysteresis of ON/OFF control

0 ÷ 9999

1

26

CPdt

Compressor Protection time for 2.rEG

OFF÷ 9999sec.

0

27

Auto 

Autotuning Fast enable

OFF / 1 / 2 / 3 / 4

1

28

SELF

Selftuning enable

no / yES

no

29

Pb

Proportional band

0 ÷ 9999

50

30

Int

Integral time

OFF ÷ 9999 sec.

200

31

dEr

Derivative time

OFF÷ 9999 sec.

50

32

FuOc

Fuzzy overshoot control

0.00 ÷ 2.00

0,5

33

tcr1

Cycle time of output 1rEg

0.1 ÷ 130.0 sec.

20,0

34

Prat

Power ratio  2rEg / 1rEg

0.01 ÷ 99.99

1.00

35

tcr2

Cycle time of  2rEg

0.1 ÷ 130.0 sec.

10.0

36

rS

Manual reset

-100.0÷100.0 %

0.0

37

SLor

Gradient of rise ramp

0.00 ÷ 99.99 / InFunit/min.

InF

Group “]PAn” (parameters relative to the user interface)
38

AdE

Shift value for the shift index functioning

OFF...9999

2

EWTQ 905 WIRING DIAGRAM

EWTQ 905

6

5

4

3

2

PtC/NtC

Pt100 / Ni100

TcJ / TcK

+

1 2 3

12

11

10

9

8

1 2 3

1 2

1

7

1 2 3 4

V

+

I

0...1V

0/2...10V

0/1...5V

4…20 mA

SUPPLY

OUT1

OUT2

TcJ / TcK

+

1 2

active

1 2 3 4

V

-

I

+10V

0...1V

0/2...10V

0/1...5V

4…20 mA passive

with ext gen.

TERMINALS

INPUTS
1 - 2

TCJ/TCK

1 +; 2 -

2 - 3 

Pt100/Ni100

1 - 2

TCJ/TCK

1 +; 2 -

1 - 2 - 3

PtC/NtC

1 - 2

0…1V; 0/1…5V; 0/2…10V 1 +;

1 - 2

0/4…20mA active

1 +;

1 - 4

4…20mA passive

4+ (+10Vdc)

OUTPUTS
7 - 8 

SUPPLY

9 - 10 

OUT2

9 COMMON; 10 N.O.

11 - 12

OUT1

11 COMMON; 12 N.O.

Содержание EWTQ 905

Страница 1: ...figuration para meters menu Once the desired item has been selected push key set to confirm Selecting OPEr and ConF gives the possibili ty of accessing other menus containing addi tional parameters an...

Страница 2: ...with normalised analogue input signals it is first nec essary to program the desired resolution on par dP 0 1 1 0 1 2 0 01 3 0 001 and then on par SSC the value that the instrument must visualise at t...

Страница 3: ...Point SP and on the hysteresis HSEt The control works in the following way it deac tivates the outputs when the process value reaches the Set Point and it activates the output 1rEG when the process va...

Страница 4: ...matically calculate the fol lowing parameters Pb Proportional Band tcr1 Cycle time of the output 1rEG Int Integral Time dEr Derivative Time FuOC Fuzzy Overshoot Control and for the Double Action PID c...

Страница 5: ...of SP EWTQ 905 5 8 LoAb off ON AL1 AL1 PV HiAb HAL1 time off ON AL1 PV time HAL1 off off ON OUT off off ON OUT AL1 SP1 Unit PV SP1 Value change SP1 time min SLor SLor LoAb ABSOLUTE LOW ALARM The alarm...

Страница 6: ...for temperature probes tc J K RTD Pt 100 IEC PTC KTY 81 121 990 W 25 C NTC 103AT 2 10KW 25 C or mV sig nals 0 50 mV 0 60 mV 12 60 mV or normal ized signals 0 4 20 mA 0 1 V 0 1 5 V 0 2 10 V Normalized...

Страница 7: ...AL1H High threshold band alarm AL1 or Maximum set alarm AL1 for high or low alarm AL1L 9999 9999 20 HAL1 Alarm AL1 hysteresis OFF 9999 1 21 AL1d Activation delay of alarm AL1 OFF 9999 sec OFF 22 AL1i...

Страница 8: ...rms if the relative parameters ALni have been programmed yES 44 5 98 48 OUT2 48 ST AT OUT1 9 5 SET EWTQ 905 F set MAX 9 mm PANEL GASKET BRACKET TYPE 1 BRACKET TYPE 2 MECHANICAL DIMENSIONS PANEL CUT OU...

Отзывы: