 Air Conditioner Service Manual 

                                                                                             

(5) Defrost 

Defrosting of the outdoor heat exchange is controlled by the microprocessor with detection by the indoor 
pipe temperature sensor. 
Defrost control type is according to the JC on the PCB whether is connected. 

 

When the JC is connect on the PCB 

When one of the conditions of A, Band C is satisfy, the defrosting operation stars. 

A.

    IPT--- indoor pipe temperature 

 

In the condition A, it must satisfy the conditions a), b)and c) then into defrosting operation. 
a)  IPT1 satisfy  IPT1=IPT

MAX

-△

IPT

14.4℉

 

b) 

t5

50minutes(the compressor cumulative operation time

50 minutes, t5 is permitted move 

and lower than t1 too). 

c) 

IPT

104

and keep 2 minutes. 

According to the condition A enter the defrosting operation, the first defrosting operation time is 
8

 

minutes; After defrosting operation one cycle, and then judge and regulate the defrosting operation 

time. 

                 

      B. 

After the compressor cumulative operation time exceeds 120 minutes and the temperature of the IPT 

is less th

a

95℉

 for 2 minutes. When the defrosting operation time on this condition exceeds 

8

 

minutes, it will terminate. 

                        C. 

After the compressor operat

es

 continuously for 20 minutes and the IPT is less than 

73.4

 or from 

the last time of defrosting operation is 50 minutes or more interval. When the defrosting operation 
time on this condition exceeds 10 minutes, it will termina

te

.   

 

When the JC isn’t connected on the PCB   

When the conditions of a) or b) is satisfy, the defrosting operation starts. 
a) Under the heating operation, the compressor cumulative operation time exceeds 50 minutes and the 
temperature of the outdoor pipe temperature sensor reads lower than 

14.4℉

 

b) Under the heating operation, the compressor cumulative operation time exceeds 50 minutes, if the 
indoor pipe temperature sensor reads lower than 

104

  continuously for 2

 

minutes. 

Note: If haven’t the outdoor pipe temperature sensor that use

s

 the condition b) to defrost, against 

use the condition a). 

 

Defrost terminating conditions   

When the condition c) or d) is satisfy, the defrosting operation will termina

te

c) The outdoor defrost sensor reads 

68

 or more. 

d) The defrosting time exceeds 10 minutes. 

 

 

 

℉)

 

6

Содержание TAC-09CHSA series

Страница 1: ...MANUAL No TE1307 Models TAC 09CHSA TAC 12CHSA TAC 18CHSA TAC 24CHSA 1 IMPORTANT NOTICE 2 OPERATION DETAILS 3 ELECTRICAL SCHEMATIC DIAGRAM 4 EXPLOSION VIEW 5 PARTS LIST WALL MOUNTED SPLIT TYPEAIR COND...

Страница 2: ...for the interpretation of this information nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification...

Страница 3: ...controller 6 2 5 3 7 1 1 1 Air Conditioner Service Manual Operation Details Remote Control The remote controller is not preset as Cooling Only Air Conditioner or Heat Pump by manufacturer Each time af...

Страница 4: ...tioner Service Manual REMOTE CONTROLLER The four types of remote controller is as follow GYKQ 05 GYKQ 10e optional GYKQ 11e optional GYKQ 12e optional Note The function of remote controller above is t...

Страница 5: ...ressor Outdoor fan OFF when the indoor pipe temperature is Outdoor fan ON when the indoor pipe temperature is 118 4 Compressor OFF when the indoor pipe temperature is Compressor ON when the indoor pip...

Страница 6: ...selected without setting temperature the system will set the temperature at automatically with the AUTO FAN speed 2 When selecting the HEATING mode operation the system will operate according to the...

Страница 7: ...the IPT is less than for 2 minutes When the defrosting operation time on this condition exceeds 8 minutes it will terminate C After the compressor operates continuously for 20 minutes and the IPT is l...

Страница 8: ...he set temperature will be raised by 1 1 hour later and by 2 hour later When selecting HEATING operation with SLEEP mode the set temperature will be dropped by 1 1 hour later and 2 hour later After th...

Страница 9: ...d position and then set to the desired angle The positioning is decided as follows When the ON OFF button is pressed When the vane control is change from AUTO to MANUAL When the SWING is finished When...

Страница 10: ...ed or a button on the remote controller is pressed and normal operation will start NOTE Do not press the EMERGEMCY Operation switch during normal operation 14 AUTO RESTART Function Option 1 When the i...

Страница 11: ...of remoter controller except the signal of shut off When the system checks the voltage is 220V and the delay control is finished it operates at normal again When the indoor fan motor is failure the co...

Страница 12: ...TCL Air Conditioner Service Manual Wiring diagram Model TAC 09CHSA Indoor unit Outdoor unit 11...

Страница 13: ...Air Conditioner Service Manual Wiring diagram Model TAC 12CHSA TAC 18CHSA Indoor unit Outdoor unit 12...

Страница 14: ...Air Conditioner Service Manual Wiring diagram Model TAC 24CHSA Indoor unit Outdoor unit 13...

Страница 15: ...Air Conditioner Service Manual Explosion view Model TAC 09CHSA TAC 12CHSA Indoor unit 15 6 11 12 8 10 9 7 5 4 3 2 18 17 16 22 21 19 20 24 23 25 26 27 1 14 13 14...

Страница 16: ...Air Conditioner Service Manual Explosion view Model TAC 18CHSA Indoor unit 24 14 13 25 22 20 19 21 23 17 16 15 18 2 3 1 5 6 4 7 9 10 12 11 8 15...

Страница 17: ...Air Conditioner Service Manual Explosion view Model TAC 24CHSA Indoor unit 13 14 26 25 27 22 23 19 18 17 16 21 20 24 2 1 3 5 7 6 4 15 9 10 12 11 8 16...

Страница 18: ...CB 1 11 Display PCB Box 1 12 Air Filter 2 13 Front Panel 1 Option 14 Display PCB Cover 1 15 Power Supply Cord 1 16 Vane 1 17 Drainage Hose 1 18 Cable Clamp 1 19 Main PCB 1 20 Electrical Box 1 21 Vane...

Страница 19: ...Display PCB Box 1 12 Left Air Filter 1 Right Air Filter 1 13 Front Panel 1 14 Display PCB cover 1 option 15 Vane 1 16 Drainage Hose 1 17 Vane Motor 1 18 Sensor Holder 1 19 Main PCB 1 20 Indoor Motor C...

Страница 20: ...Box 1 12 Left Air Filter 1 Right Air Filter 1 13 Front Panel 1 14 Display PCB Cover 1 15 Electrical Box Cover 1 16 Vane A 1 17 Vane B 1 18 Drainage Hose 1 19 Cable Clamp 1 20 Vane Motor 2 21 Sensor Ho...

Страница 21: ...Air Conditioner Service Manual Explosion view Model TAC 09CHSA TAC 12CHSA Outdoor unit 27 1 26 2 3 4 25 23 24 22 21 19 20 16 17 15 14 18 5 6 7 8 10 9 13 12 11 20...

Страница 22: ...Air Conditioner Service Manual Explosion view Model TAC 18CHSA Outdoor unit 27 1 26 2 3 4 25 23 24 22 21 19 20 16 17 15 14 18 5 6 7 8 10 9 13 12 11 21...

Страница 23: ...Air Conditioner Service Manual Explosion view Model TAC 24CHSA Outdoor unit 27 1 26 2 3 4 25 23 24 22 21 19 20 16 17 15 14 18 5 6 7 8 10 9 13 12 11 22...

Страница 24: ...1 4 way Valve 1 12 4 way Valve Assembly 1 Optional 13 Outdoor Base 1 14 Right Plate 1 15 Two way Valve 1 16 Valve Supporter 1 17 Three way Valve 1 18 Electrical Box Cover 1 19 Outdoor cable Clamp 1 20...

Страница 25: ...d It Accessories 1 12 Discharge Pipe 1 Optional 13 Suction Pipe 1 Optional 14 Outdoor Base 1 15 Two way Valve 1 16 Valve Supporter 1 17 Three way Valve 1 18 Right Plate 1 19 Electrical Box Cover 1 20...

Страница 26: ...Valve 1 12 4 way Valve Assembly 1 Optional 13 Outdoor base 1 14 Right Plate 1 15 Two way Valve 1 16 Valve Supporter 1 17 Three way Valve 1 18 Electrical Box Cover 1 19 Outdoor Cable Clamp 1 20 Outdoo...

Отзывы: