 Air Conditioner Service Manual 

                                                                                             

 

Press the Timer button(‘h’ flashes). 

 

Use the 

▲▼

 button to select the time at which the air conditioner must activate (between 0 and 10 

hours can be set at every half hour-between 10 and 24 hours can be set at every hour). 

 

Press the Timer button (‘h’ stops flashing) and the preset time appears in the display. 

 

Press the Timer button again to delete the selected data from the memory. 

Note : If no buttons are pressed during the programming of the timer function, thee remote control will 
switch off automatically after 10 seconds. 

(2)  To switch the air conditioner off at the desired time, follow the procedure specified below (the remote control 

and air conditioner are switched off): 

 

Press the timer button. 

 

Use the 

▲▼

 button to select the time at witch. 

13. EMERGENCY Operation 

When the EMERGENCY Operation switch is pressed once, COOLING mode is selected and if in 3 seconds the 
EMERGENCY Operation switch is pressed again, mode is selected. Then pressed once again, the unit is switch 
off. 
When the remote controller is missing, has failed or the batteries run down, press the EMERGENCY Operation 
switch on the front of the indoor unit. The unit will start. 
The first 30 minutes of operation will be the test run operation. The operation is for servicing. The indoor fan runs 
at high speed and the system is in continuous operation. The thermostat is ON and the timer is reset to normal. 
After 30 minutes of test run operation the system shifts to AUTO COOLING/HEATING mode, and the indoor fan 
runs in automatic speed. The operation continues unit the EMERGENCY operation switch is pressed or a button 
on the remote controller is pressed

 and 

normal operation will start. 

NOTE: Do not press the EMERGEMCY Operation switch during normal operation. 

14.  AUTO RESTART Function(Option)

 

1.When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan 
speed are memorized by the indoor electric control PCB. The AUTO RESTART function sets to work the 
moment power has restored after power failure. Then, the unit will restart automatically. 
2. How to set the AUTO RESTAR function. 

 

Press the emergency switch and power supply to the PCB following, 

hold

 10

 

seconds and the buzzer will 

beep three times. The AUTO-RESTAR is set. 

 

Do the operation again, the buzzer will beep four times and the AUTO-RESTAR function is cancelled. 

15. 

Failure Display and Handling

 

a) Failure 

Display 

When the controller 

has

 failure, the buzzer will 

sound

 long for three times, and displays the failure from the 

failure lamp. 

b) Failure 

Code 

If have the digital pipe that display

s

 the failure code for digital pipe, or display for the run lamp. 

Type of failure 

The lamp flash 

Display of digital pipe 

The failure of room temperature sensor 

Once/cycle 

E1 

The failure of indoor pipe temperature sensor 

Twice/cycle 

E2 

The failure of indoor fan motor 

6 times/cycle 

E6 

c) Failure 

Handling 

 

When the room temperature sensor or the indoor pipe temperature sensor 

has a

 failure, the system will be 

shut off, the compressor will be OFF, and the outdoor fan and the indoor fan will be OFF. The system 
doesn’t receive the signal of remoter controller except the signal of shut off it. When the failure 
disappear, the controller can operate in normal mode. before this, presses the “ON/OFF” to start the 
system, and it will operate in COOLING or HEATING for 30 minutes, and follows shut off. During 

9

Содержание TAC-09CHSA series

Страница 1: ...MANUAL No TE1307 Models TAC 09CHSA TAC 12CHSA TAC 18CHSA TAC 24CHSA 1 IMPORTANT NOTICE 2 OPERATION DETAILS 3 ELECTRICAL SCHEMATIC DIAGRAM 4 EXPLOSION VIEW 5 PARTS LIST WALL MOUNTED SPLIT TYPEAIR COND...

Страница 2: ...for the interpretation of this information nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification...

Страница 3: ...controller 6 2 5 3 7 1 1 1 Air Conditioner Service Manual Operation Details Remote Control The remote controller is not preset as Cooling Only Air Conditioner or Heat Pump by manufacturer Each time af...

Страница 4: ...tioner Service Manual REMOTE CONTROLLER The four types of remote controller is as follow GYKQ 05 GYKQ 10e optional GYKQ 11e optional GYKQ 12e optional Note The function of remote controller above is t...

Страница 5: ...ressor Outdoor fan OFF when the indoor pipe temperature is Outdoor fan ON when the indoor pipe temperature is 118 4 Compressor OFF when the indoor pipe temperature is Compressor ON when the indoor pip...

Страница 6: ...selected without setting temperature the system will set the temperature at automatically with the AUTO FAN speed 2 When selecting the HEATING mode operation the system will operate according to the...

Страница 7: ...the IPT is less than for 2 minutes When the defrosting operation time on this condition exceeds 8 minutes it will terminate C After the compressor operates continuously for 20 minutes and the IPT is l...

Страница 8: ...he set temperature will be raised by 1 1 hour later and by 2 hour later When selecting HEATING operation with SLEEP mode the set temperature will be dropped by 1 1 hour later and 2 hour later After th...

Страница 9: ...d position and then set to the desired angle The positioning is decided as follows When the ON OFF button is pressed When the vane control is change from AUTO to MANUAL When the SWING is finished When...

Страница 10: ...ed or a button on the remote controller is pressed and normal operation will start NOTE Do not press the EMERGEMCY Operation switch during normal operation 14 AUTO RESTART Function Option 1 When the i...

Страница 11: ...of remoter controller except the signal of shut off When the system checks the voltage is 220V and the delay control is finished it operates at normal again When the indoor fan motor is failure the co...

Страница 12: ...TCL Air Conditioner Service Manual Wiring diagram Model TAC 09CHSA Indoor unit Outdoor unit 11...

Страница 13: ...Air Conditioner Service Manual Wiring diagram Model TAC 12CHSA TAC 18CHSA Indoor unit Outdoor unit 12...

Страница 14: ...Air Conditioner Service Manual Wiring diagram Model TAC 24CHSA Indoor unit Outdoor unit 13...

Страница 15: ...Air Conditioner Service Manual Explosion view Model TAC 09CHSA TAC 12CHSA Indoor unit 15 6 11 12 8 10 9 7 5 4 3 2 18 17 16 22 21 19 20 24 23 25 26 27 1 14 13 14...

Страница 16: ...Air Conditioner Service Manual Explosion view Model TAC 18CHSA Indoor unit 24 14 13 25 22 20 19 21 23 17 16 15 18 2 3 1 5 6 4 7 9 10 12 11 8 15...

Страница 17: ...Air Conditioner Service Manual Explosion view Model TAC 24CHSA Indoor unit 13 14 26 25 27 22 23 19 18 17 16 21 20 24 2 1 3 5 7 6 4 15 9 10 12 11 8 16...

Страница 18: ...CB 1 11 Display PCB Box 1 12 Air Filter 2 13 Front Panel 1 Option 14 Display PCB Cover 1 15 Power Supply Cord 1 16 Vane 1 17 Drainage Hose 1 18 Cable Clamp 1 19 Main PCB 1 20 Electrical Box 1 21 Vane...

Страница 19: ...Display PCB Box 1 12 Left Air Filter 1 Right Air Filter 1 13 Front Panel 1 14 Display PCB cover 1 option 15 Vane 1 16 Drainage Hose 1 17 Vane Motor 1 18 Sensor Holder 1 19 Main PCB 1 20 Indoor Motor C...

Страница 20: ...Box 1 12 Left Air Filter 1 Right Air Filter 1 13 Front Panel 1 14 Display PCB Cover 1 15 Electrical Box Cover 1 16 Vane A 1 17 Vane B 1 18 Drainage Hose 1 19 Cable Clamp 1 20 Vane Motor 2 21 Sensor Ho...

Страница 21: ...Air Conditioner Service Manual Explosion view Model TAC 09CHSA TAC 12CHSA Outdoor unit 27 1 26 2 3 4 25 23 24 22 21 19 20 16 17 15 14 18 5 6 7 8 10 9 13 12 11 20...

Страница 22: ...Air Conditioner Service Manual Explosion view Model TAC 18CHSA Outdoor unit 27 1 26 2 3 4 25 23 24 22 21 19 20 16 17 15 14 18 5 6 7 8 10 9 13 12 11 21...

Страница 23: ...Air Conditioner Service Manual Explosion view Model TAC 24CHSA Outdoor unit 27 1 26 2 3 4 25 23 24 22 21 19 20 16 17 15 14 18 5 6 7 8 10 9 13 12 11 22...

Страница 24: ...1 4 way Valve 1 12 4 way Valve Assembly 1 Optional 13 Outdoor Base 1 14 Right Plate 1 15 Two way Valve 1 16 Valve Supporter 1 17 Three way Valve 1 18 Electrical Box Cover 1 19 Outdoor cable Clamp 1 20...

Страница 25: ...d It Accessories 1 12 Discharge Pipe 1 Optional 13 Suction Pipe 1 Optional 14 Outdoor Base 1 15 Two way Valve 1 16 Valve Supporter 1 17 Three way Valve 1 18 Right Plate 1 19 Electrical Box Cover 1 20...

Страница 26: ...Valve 1 12 4 way Valve Assembly 1 Optional 13 Outdoor base 1 14 Right Plate 1 15 Two way Valve 1 16 Valve Supporter 1 17 Three way Valve 1 18 Electrical Box Cover 1 19 Outdoor Cable Clamp 1 20 Outdoo...

Отзывы: