30
RCD / x1/2, x1, x2, x5 (Trip-time)
1x
RCD
10mA
0
----
mS
180
----
mS
AC
General
Uc: --------- V
Ri: ---------
Ω
0
1
230
OK
TN-net
229
Figure 6.6.8 RCD / x1/2,x1,x2,x5 screen.
I. Set the rotary switch to RCD.
II. Press F1 button to change to x1/2, x1, x2, x5.
III. Connect the test leads as shown in Figure 6.6.1.
IV. If there is no problem with the test lead connection, “OK” is displayed as shown in Figure 6.6.8
V. When “OK” is displayed, press the Test button to perform measurement.
VI. The
symbol being measured is displayed.
VII. The voltage phase 0 ° is measured first and the Trip time is displayed.
VIII. When the 0 ° measurement is completed, turn on the RCD switch and measure 180 °.
IX. When all measurements are completed, the RCD 0 ° and 180 ° Trip time will be displayed on the
screen.
1x
RCD
10mA
0
68
mS
180
43
mS
AC
General
Uc: 10.5 V
Ri: 1000 Ω
0
OK
TN-net
1
230
229
Figure 6.6.9 RCD / x1/2,x1,x2,x5 Measurement completed.
Содержание EuroMaster AutoEv
Страница 1: ...Ver 1 3 ELIT EuroMaster AutoEv Brukermanual User manual page 55 ...
Страница 54: ...Euromaster AutoEV 53 ELIT AS Hellenvegen 9 2022 GJERDRUM ...
Страница 55: ...EuroMaster AutoEV User s manual Ver 1 0 3 ...