EuroMaster AutoEV
23
I. Set the rotary switch to Loop / Z-line.
II. Press the F2 button to change from No Trip to Hi Amp.
III. Connect the test leads as shown in Figure 6.5.4.
IV. IV. If there is no problem with the test lead connection, the terminal status is displayed as shown in
Figure 6.5.5 “OK” is displayed in the right window.
X X X
: This display indicates that there is no L, PE, or N connection.
L↔N
: This is an indication that the L and N lines have been switched.
L↔PE
: This is an indication that the L and PE lines have been switched.
N X
: This indicates that there is no N-line connection.
PE X
:
This indicates that there is no PE-line connection.
V. When “OK” is displayed, press the Test button to perform measurement.
VI. The
symbol is displayed during measurement.
VII. When the measurement is completed, the L-PE impedance measurement value and PFC (If) value
are displayed on the screen.
L-PE
LOOP
Hi Amp
0.65
Ω
If
353
A
R:
0.65 Ω
XL: 0.05 Ω
0
OK
TN-net
0
230
230
Figure 6.5.6 Loop / Hi Amp Measurement completed.
Do not measure where RCD is installed. RCD is tripped.
Z-Line / L-N
N(Blue)
L
N
PE
L (Brown)
Figure 6.5.7 Z-Line / L-N Connection.
Содержание EuroMaster AutoEv
Страница 1: ...Ver 1 3 ELIT EuroMaster AutoEv Brukermanual User manual page 55 ...
Страница 54: ...Euromaster AutoEV 53 ELIT AS Hellenvegen 9 2022 GJERDRUM ...
Страница 55: ...EuroMaster AutoEV User s manual Ver 1 0 3 ...
Страница 59: ...EuroMaster AutoEV 4 2 Product composition EuroMaster AutoEV Instrument ...
Страница 91: ...EuroMaster AutoEV 36 Figure 6 8 5 Earth Resistor 3Pole connection ...