Motor overtemperature Alarm
DESCRIPTION
This alarm appears when:
•
Motor temperature exceeds
Maximum motor temperature
value if set
Temperature probe type
is
KTY83/122
or
KTY84/130
.
•
Motor temperature sensor isn’t connected if
Thermostat
is selected as
Temperature probe type
.
UNIDRIVE BEHAVIOUR
UNIDRIVE stops motor rotation with emergency slope (disabling
power relay and three-phase bridge) and unlocks motor brake.
POSSIBLE TROUBLESHOOTING ISSUE
If motor hasn’t any PTC, set
none
as
Temperature
probe type
option (See Section 3.4.6. Otherwise, restore motor temperature
conditions, then reset alarms.
Safety Alarm
DESCRIPTION
This alarm is active when the SAFETY Input (P
IN
12) isn’t supplied.
UNIDRIVE BEHAVIOUR
UNIDRIVE stops motor rotation with emergency slope (disabling
power relay and three-phase bridge) and unlocks motor brake.
POSSIBLE TROUBLESHOOTING ISSUE
Check the connection of SAFETY input and
restart your UNIDRIVE.
Stalled rotor Alarm
DESCRIPTION
This alarm appears when the motor is blocked and at the same time
the phase current is high about for approximately for a second. For instance,
the vehicle’s wheels are blocked by an obstacle.
UNIDRIVE BEHAVIOUR
Drive won’t enable power relay and three-phase bridge.
POSSIBLE TROUBLESHOOTING ISSUE
Find the cause of the block and then remove
it.
74
Chapter A
Troubleshooting: Alarm Messages