20
3.
INSTALLATION
3.1.
GENERAL NOTES
3.1.1.
POWER CABLING
Take off the rear pannel
•
Connect a supply cable 3P+T of adequate size to support the current of the model.
•
Connect the load cable of correct size to support the maximum current (load 3-phase range 300/150).
•
In case connect the sense cable, 3-phase.
•
At the end, close the rear panel.
•
Remove the internal short circuit OUTPUT NEUTRAL
–
PE, this short circuits must be made externally on
the star of the output neutral (see schematics)
•
The signal part and the power part have not to cabled together.
•
The master/slave commands are all 230V, you have to use shielded cable if you cable together with
signal one for example the RS232 connections.
INGRESSO
INPUT
1
2
3
4
L1 L2 L3 PE
AUX MASTER
SENSE
OUT 3-FASE
AUX SLAVE
AUX MASTER
SENSE
OUT 3-PHASE
AUX SLAVE
1.
1
1.
2
1.
3
1.
4
1.
5
1.
6
1.
7
1.
8
12 13 14 15
16 17 18 19 20
2.
1
2.
2
2.
3
2.
4
2.
5
2.
6
L1 L2 L3 N
L1 L2 L3 N PE
Содержание 99116963
Страница 21: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 21 3 1 2 SIGNAL CABLING ...
Страница 25: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 25 3 5 4 Wiring diagram three phase of 2 wire configuration ...
Страница 26: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 26 3 5 5 Wiring diagram three phase of 4 wire configuration ...
Страница 38: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 1 HPS P 200K MANUALE UTENTE Click here to see the English version ...
Страница 58: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 21 3 1 3 CABLAGGIO DEI SEGNALI ...
Страница 62: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 25 3 5 4 Schema di cablaggio trifase configurazione 2 fili ...
Страница 63: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 26 3 5 5 Schema di cablaggio trifase configurazione 4 fili ...