11
INSTALLER INFORMATION
control access box, so an appropriate position for
the access box need to be determined.
This appliance has adjustable legs, these must
me set to stabalise the fire before flue position is
finalised.
Do not make any adjustments to the appliance,
except the leg length.
The appliance and Flue system should be fitted
with a minimum clearance of 500mm from any
combustible objects or materials, this includes
any combustible materials used for the fireplace
construction.
As this is a room sealed appliance and the
appliance stands on appropriate legs, a hearth
is not required for this appliance.
The Fireplace should be ventilated with openings
giving a total free vent area of 400 cm².
A gap of 50mm should be left all round the
appliance.
If a shelf is to be fitted above the fireplace opening,
a gap of 150mm minimum should be left between
the opening and the shelf.
The brackets supplied may be used fore securing
the appliance to a rear wall.
Timber Frame Construction
Whilst it is possible to install room-sealed
appliances in timber frame properties, great care
needs to be taken to ensure that the flue assembly
does not interfere with the weather proofing
qualities of any outer wall which it may penetrate.
Before attempting this work, further details need
to be referenced, (e.g. “Gas Installations in Timber
Frame Buildings” from the CORGI installer series
in the UK).
Carport or Building Extension
Where a flue terminal is sited within a carport or
building extension, it should have at least two
completely open and unobstructed sides. The
distance between the lowest part of the roof and
the top of the terminal should be at least 600mm.
Note: A covered passageway should not be
treated as a carport.
Flues should not be sited in
a covered passageway between properties.
Basements, Lightwells and Retaining walls
Flue terminals should not be sited within the
confines of a basement area, light well or external
space formed by a retaining wall, unless steps are
taken to ensure the products of combustion can
disperse safely at all times. It may be possible
to install this Balanced Flue system in such a
location provided that it is not sited lower than 1m
from the top level of that area to allow combustion
products to disperse safely.
Flue terminals should be sited to ensure
total clearance of the combustion products in
accordance with the inclosed information.
When the products of combustion are discharged,
they should not cause a nuisance to adjoining or
adjacent properties and they should be positioned
so that damage cannot occur to other parts of the
building. If the outer wall surface is constructed
of combustible material, a non-combustible plate
should be fitted behind the terminal projecting
25mm beyond the external edges of the terminal.
Содержание Modore 100 H
Страница 15: ...15 INSTALLER INFORMATION 15 INFORMATIE VOOR DE INSTALLATEUR...
Страница 16: ...16 INSTALLER INFORMATION 16 INFORMATIE VOOR DE INSTALLATEUR...
Страница 17: ...17 INSTALLER INFORMATION 17 INFORMATIE VOOR DE INSTALLATEUR...
Страница 18: ...18 INSTALLER INFORMATION 18 INFORMATIE VOOR DE INSTALLATEUR...
Страница 42: ...42...
Страница 43: ...43...
Страница 44: ...Element4 B V Paxtonstraat 23 8013 RP Zwolle The Netherlands September 2014...