9- Valve installation 

Verify the line pressure is lower of the maximum working 
pressure admitted to the valve.  
Check correspondence of flow direction with arrow 
printed on valve body.  
Check correct alignment of connecting pipes. 

Remove the end caps and make sure no foreign 
body is entered into the valve during handling. 

Install in an area that is protected from rain and 
water splashes or drops. 

Threaded models: 

1.  Put sealing agent onto the pipe thread (avoid 

excessive quantities of fittings glue which could 
enter in the valve and damage the seal seat). 

2.  Screw the pipes using proper tools only. Do not use 

unit as lever because damage to the valve stem 
could result. 

Flanged models: 

1.  Position the gasket and insert the bolts. 

2.  Screw the nuts tightening them crosswise and using 

proper tools only. 

Avoid overtightening and mount tension free. 

Following chart shows the maximum values of bending 
moment (F

max

), torque (T

max

) and screws driving torque 

(C

max

), according to EN161. 

 

Connections 

F

max

 

(Nm) t<10 s 

T

max

 

(Nm) 

C

max

 

(Nm) 

Rp3/8 70 

35 - 

Rp1/2 105 

50 - 

Rp3/4 225 

85 - 

Rp1 340 

125 

Rp1¼ 475 

160 - 

Rp1½ DN40 

610 

200 

50 

Rp2    DN50 

1100 

250 

50 

DN65 1600 -  50 
DN80 2400 -  50 
DN100 5000  -  80 
DN125 6000  -  160 
DN150 7600  -  160 
DN200 7600  -  160 

 

 

 

 

 

 

 

 

 

 

Fig. 4 
 
Valve may be mounted with coil in horizontal or vertical 
position.  Coil may be oriented 360 degrees in any 
direction.  

 

10- Electrical connections 

(IEC 730-1)

 

Check correspondence between valve voltage rating and 
line power supply, before making any electrical 
connections. 

1.  Switch off power supply and remove protection 

cover. 

2.  Connect power cables to connector plug terminal 

board.  

3.  Screw back the plug cover, taking care to use all 

gaskets properly, because this could condition the 
valve life duration. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 5 

 

WARNING 

 

To prevent product damage and dangerous 

situations, read the Installation and Service 
Instructions carefully. 

 

Turn off all power before servicing any part of 

the system. 

 

Perform leak and functional tests after mounting.  

A gas leak detection spray may be used also. 

 

Coil and DIN plug must be replaced with identical 

spare parts only. 

 

If the coil is turned, make sure the cap is 

properly tightened and the coil is locked. 

 

Use all gaskets properly (void warranty). 

 

All wiring must be in compliance with local and 

national codes. 

 

Make sure all works are performed by qualified 

technicians only.

 

 
 
 
 
 
 

 

F

max

 

T

max

 

C

max

 

Содержание EVRM-NA Series

Страница 1: ...Printed in Italy EE167 0105 EVRM NA Safety solenoid valves for gas Manual reset Normally open DN10 DN200 EVRM NA6 EVRM NA9 Certified Quality System www elektrogas com ...

Страница 2: ...vent dirty contamination of the seal seat except brass models Maximum operating pressure 500 mbar Suitable for air and non aggressive gases EN 437 1 2 and 3 families Coil insulation is class H 180 C Terminals with DIN 43650 plug and PG connector Valves are 100 tested by computerized testing machineries and are fully warranted For valve identification see the following charts WARNING This control m...

Страница 3: ...min max adjustable pressure switches leakage tester or other gas equipments Flanged models are provided with gauges in the outlet chamber too Brass models are available without gauges only On request valves are supplied with a G1 8 connection on the bottom to installed a closed position indicator micro switch from 3 4 to 8 An adapting rod is provided too 5 Coil features Coil and DIN plug are provi...

Страница 4: ...MNA7D DN 80 EVRMNA8A EVRMNA8B EVRMNA8C EVRMNA8D DN 100 EVRMNA9A EVRMNA9B EVRMNA9C EVRMNA9D DN 125 EVRMNA93A EVRMNA93B EVRMNA93C EVRMNA93D DN 150 EVRMNA95A EVRMN95B EVRMNA95C EVRMNA95D DN 200 EVRMNA98A EVRMN98B EVRMNA98C EVRMNA98D Fig 3 Connections Overall dimensions mm Model Threaded Flanged Max Pressure mbar Power Consump 230VAC W A B C D Int h Weight Kg EVRMNA0 O Rp 3 8 500 16 30 58 115 130 0 4 ...

Страница 5: ...tural gas Town gas Air V m h 1 3 4 OT 3 8 OT 1 2 OT 1 OT 1 2 3 8 3 4 1 2 1 DN 200 Liquid gas 8 Loss of pressure Formula of conversion from air to other gases 15 C 1013 mbar dry Gas type Specific gravity Kg m K Air 1 25 1 00 Natural Gas 0 80 1 25 Town Gas 0 57 1 48 Liquid Gas 2 08 0 77 ...

Страница 6: ... 225 85 Rp1 340 125 Rp1 475 160 Rp1 DN40 610 200 50 Rp2 DN50 1100 250 50 DN65 1600 50 DN80 2400 50 DN100 5000 80 DN125 6000 160 DN150 7600 160 DN200 7600 160 Fig 4 Valve may be mounted with coil in horizontal or vertical position Coil may be oriented 360 degrees in any direction 10 Electrical connections IEC 730 1 Check correspondence between valve voltage rating and line power supply before makin...

Страница 7: ... Do not use tools because a lip damage could result 10 Remove the filter and blow it with compressed air 11 Reassemble the valve following the inverse sequence Flanged models 1 Close ball valve upstream the system 2 Unscrew the knob 3 Using an Allen key remove the screws on the upper flange in cross way The gas in the valve will come out during this step 4 Check the main O ring and the rod O ring ...

Отзывы: