background image

46

EN

Date: 06-05-2014

Instruction Manual 

PS 8000 E 3U Series

7.7  Remote sense operation

Remote sense operation is used to compensate voltage drops 

of the conductors between the power supply and the load. 

Because the compensation is limited to a certain level, it is 

recommended to match the cross section of the conductors to 

the output current and thus minimise the voltage drop.
The sense input is located on the rear, at terminal 

Sense

where the sense conductors are connected to the load with 

correct polarity. The power supply will detect the external sense 

automatically and compensate the output voltage by the actual 

voltage at the load instead of the output. The output voltage 

will be raised by the value of the voltage drop between power 

supply and load.

Maximum compensation: see technical specifications, will vary 

from model to model. 

Also see figure 9 below.

7.8  Mains undervoltage or overvoltage

The units require two or three phases of a three-phase supply 

with 400V phase conductor voltage and tolerate max. +15%. 

This results in an input voltage range of 340...460V AC. Within 

this range, the units can be operated without any restrictions 

regarding power. Input voltages below 340V AC are considered 

as supply undervoltage and will store the last condition, as well 

as switch the power output off. Same happens at overvoltage 

above 460V AC.

New since firmware 6.01

:

 Over- or undervoltage in the AC 

input, as well as errors in the input section of the device are 

indicated as „power fail“ alarm on the device. This is done in the 

display with „PF“, via pin 6 „OT/PF“ of the analogue interface 

or via the internal alarm buffer, which can be read out with one 

of the optional, digital interface cards.

Attention!

Permanent input undervoltage or overvoltage must be 

avoided!

Operating the device 

Figure 9. Wiring remote sense

7.9  Connecting different types of loads

Different types of loads, such as ohmic loads (lamp, resistor), 

electronic loads or inductive loads (motor) behave differently 

and can retroact to the power supply. For example, motors 

can induce a countervoltage which may cause the overvoltage 

protection of the power supply to shut off the output. 
Electronic loads have regulator circuits for voltage, current and 

power that can counteract to the ones of the power supply and 

may result in increased output ripple or other, unwanted side 

effects. Ohmic loads are almost 100% neutral. It is recommen-

ded to consider the load situation when planning applications.

Содержание PS 8000 E 3U Series

Страница 1: ...PS 8000 E 3U Laboratory Power Supply Series Operating Guide...

Страница 2: ...3 CN PS 8000 E 3U 06 05 2014 Elektro Automatik 60VDC...

Страница 3: ...are 15 5 9 15 6 16 6 1 16 6 2 16 6 2 1 Preset Voltage 16 6 2 2 Preset UVL OVP 17 6 2 3 Preset Power 17 6 2 4 Preset Current 17 6 2 5 Memory Select M1 M5 17 6 2 6 Memory Start Memory Save 3s 18 6 2 7 L...

Страница 4: ...232 IEEE GPIB Ethernet LAN Profibus 0 5V 0 10V 0 100 3 3kW 5kW 6 6kW 10kW 15kW 150kW OT OVP CC CV CP 5 Share Bus CAN Vector 6 01 Vector CAN Windows LabView VIs 2 2 1 202 x 32 2 9 2 4 0 00V 99 99V 0 0V...

Страница 5: ...00mV 10mV 2 5V 2 5V 6V 10V 2 5V 0 44V 0 88V 0 220V 0 550V 0 44V INom 170A 170A 70A 30A 340A 0 INom 0 INom 0 INom 0 INom 0 INom 10 UIN 0 05 0 05 0 05 0 05 0 05 0 100 UOUT 0 15 0 15 0 15 0 15 0 15 BWL 2...

Страница 6: ...V 0 88V 0 176V 0 220V 0 440V INom 510A 340A 170A 140A 70A 0 INom 0 INom 0 INom 0 INom 0 INom 10 UIN 0 05 0 05 0 05 0 05 0 05 0 100 UOUT 0 15 0 15 0 15 0 15 0 15 BWL 20MHz 900mApp 120mArms 600mApp 80mA...

Страница 7: ...2 0 2 100mV 1V 10mV 10mV 100mV 10V 20V 2 5V 2 5V 6V 0 550V 0 1100V 0 88V 0 88V 0 220V INom 60A 30A 250A 510A 210A 0 INom 0 INom 0 INom 0 INom 0 INom 10 UIN 0 05 0 05 0 05 0 05 0 05 0 100 UOUT 0 15 0 1...

Страница 8: ...100mV 100mV 100mV 1V 7 5V 10V 18V 30V 0 264V 0 550V 0 660V 0 1650V INom 170A 90A 70A 30A 0 INom 0 INom 0 INom 0 INom 10 UIN 0 05 0 05 0 05 0 05 0 100 UOUT 0 15 0 15 0 15 0 15 BWL 20MHz 333mApp 27mArm...

Страница 9: ...10 2006 Elektro Automatik GmbH Co KG Irrt mer und nderungen vorbehalten CN 06 05 2014 PS 8000 E 3U 3 3 1 A D B E 80V C F 2 1...

Страница 10: ...11 CN PS 8000 E 3U 06 05 2014 3 4...

Страница 11: ...12 2006 Elektro Automatik GmbH Co KG Irrt mer und nderungen vorbehalten CN 06 05 2014 PS 8000 E 3U 5...

Страница 12: ...1 5 2 3 3kw 5kW 6 6kW 10kW 15kW PE L1 L2 L3 Imax Imax Imax 3 3kW 2 5mm 11A 2 5mm 11A 5kW 2 5mm 16A 2 5mm 16A 6 6kW 2 5mm 19A 2 5mm 11A 2 5mm 11A 10kW 4mm 28A 4mm 16A 4mm 16A 15kW 4mm 28A 4mm 28A 4mm...

Страница 13: ...4 PS 8000 E 3U 6 6kW 10kW L1 R L1 L1 max 44A L2 max 56A L3 max 60A 6 6kW 10kW 5 4 6 F16A 500V 6 3x32mm 5 5 1 5m 30A 6mm 70A 16mm 90A 25mm 140A 50mm 170A 70mm 210A 95mm 340A 2x70mm 510A 2x120mm 70mm 2...

Страница 14: ...15 CN PS 8000 E 3U 06 05 2014 400V 6mm 5 6 300V 5 7 Sense 2 2 3 1 7 7 5 8 Share Share 11 1 5 9 9...

Страница 15: ...KG Irrt mer und nderungen vorbehalten CN 06 05 2014 PS 8000 E 3U 8 6 6 1 8 OVP UVL CV on OT OVP CC on CP on Fine PF 6 0 1 V UVL OVP 2 CC CV 3 I P 4 5 I P 6 7 V UVL OVP 6 2 6 2 1 Preset Voltage Voltag...

Страница 16: ...L UVL Voltage UVL OVP 0 USet UVL OVP 0 110 UNom 5s OVP LOCK 6 2 8 UVL OVP 6 2 3 Preset Power Current Power 0 100 PNom 5s LOCK 6 2 8 6 2 4 Preset Current Current Power 0 100 INom 5s LOCK 6 2 8 6 2 5 Me...

Страница 17: ...On c 3s GPIB LOCK 6 2 8 6 2 7 Local LOCAL LOCAL LOCAL Local LOCAL Remote LOCK 6 2 8 LOCAL LOCAL LOCAL 6 2 8 Lock Unlock LOCK LOCK LOCK 6 02 LOCK 6 2 9 Output On Output Off Output On Output Off LED CC...

Страница 18: ...0 1V 210 250A 2A 0 1A 600V 5V 0 1V 340A 2A 0 1A 1000V 10V 1V 510A 5A 0 1A 1500V 10V 1V 3 3 5kW 50W 1W 6 6 10kW 100W 10W 15kW 100W 10W Note 2 3 2 10 3 9 7 7 1 8 AutoPwrOn on U I P OVP UVL off U I 0 P...

Страница 19: ...atik GmbH Co KG Irrt mer und nderungen vorbehalten CN 06 05 2014 PS 8000 E 3U 7 6 CV CV CC CC 0 PNom isen 1 2 P U I CP CC CC CV CP 7 7 Sense 9 7 8 400V 15 340V 460V 340V AC 460V AC 6 01 AC power fail...

Страница 20: ...000 0x7FC 0 2044 IDs Vector DBC CAN ID ID BAID ID IDs ID Sys Vector ID Sys Broad ID 0x7FF 0x000 0x7FF 0 2047 IDs Vector DBC CAN ID ID BCID ID ID ID ID Sys Vector ID Sys RID 0 0 31 RID CAN IF C1 CAN Bu...

Страница 21: ...CAN IF G1 GPIB IEEE IF E1 IF E1B Ethernet LAN USB IF PB1 Profibus USB LabView IF 8 OVP UVL GPIB 100 hex 0x6400 110 hex 0x6E00 OVP GPIB 10 10 1 15 OT OVP CC CV AI AI AI OVP AI 3 AI 0 5V 0 10V 0 100 8...

Страница 22: ...23 CN PS 8000 E 3U 06 05 2014 10 2 PLC 10 1 REM SB DGND PLC VREF VSEL CSEL VREF 3mA 10kOhm VREF 100...

Страница 23: ...High 4V LOW ULow 1V Vcc 5V 1mA UCE 0 3V Imax 10mA Umax 0 30V DGND 7 N C 8 PSEL AI 0 10V 0 5V PNom 0 100 0 5 Ri 100K 9 VMON AO 0 10V 0 5V UNom 0 100 Imax 2mA 0 2 AGND 10 CMON AO 0 10V 0 5V INom 0 100 1...

Страница 24: ...are 5 8 Share 12 Sense PS 8000 E 3U 11 2 PE 300V AGND DGND 200V PDC 1200 70 3U 600V 400V 500V 12 12 1 a USB RS232 CAN GPIB IEEE SCPI LAN SCPI Profibus a High Speed Ramping b 12 2 Windows IF U1 USB IF...

Страница 25: ...26 2006 Elektro Automatik GmbH Co KG Irrt mer und nderungen vorbehalten CN 06 05 2014 PS 8000 E 3U 12 13...

Страница 26: ...itched off Keep in mind Only operate the device at a mains voltage as stipulated on the type plate Never insert mechanical parts especially from metal through the air ventilation slots Avoid any use o...

Страница 27: ...Pushbutton Preset UVL OVP 42 6 2 3 Pushbutton Preset Power 42 6 2 4 Pushbutton Preset Current 42 6 2 5 Pushbutton Memory Select M1 M5 43 6 2 6 Pushbutton Memory Start Memory Save 3s 43 6 2 7 Pushbutt...

Страница 28: ...ccurate measurement and indication of actual values The main functions at a glance Set voltage current and power each with 0 100 Adjustable overvoltage threshold 0 110 UNom Optional pluggable digital...

Страница 29: ...rms 300mApp 40mArms 44mApp 11mArms 14mApp 8mArms 600mApp 80mArms Accuracy 0 2 0 2 0 2 0 2 0 2 Resolution of display 100mA 100mA 10mA 10mA 100mA Transient recovery time 10 90 load 2ms 2ms 2ms 2ms 2ms O...

Страница 30: ...mArms 33mApp 9mArms Accuracy 0 2 0 2 0 2 0 2 0 2 Resolution of display 100mA 100mA 10mA 100mA 10mA Transient recovery time 10 90 load 2ms 2ms 2ms 2ms 2ms Output Power Nominal power PNom 10000W 10000W...

Страница 31: ...App 16mArms 22mApp 11mArms 900mApp 120mArms 900mApp 120mArms 167mApp 33mArms Accuracy 0 2 0 2 0 2 0 2 0 2 Resolution of display 10mA 10mA 100mA 100mA 100mA Transient recovery time 10 90 load 2ms 2ms 2...

Страница 32: ...hreshold adjustable 0 264V 0 550V 0 660V 0 1650V Output Current Nominal current INom 170A 90A 70A 30A Adjustable range 0 INom 0 INom 0 INom 0 INom Stability at mains fluctuation 10 U IN 0 05 0 05 0 05...

Страница 33: ...06 05 2014 Instruction Manual PS 8000 E 3U Series About the device 3 Device description 3 1 Views A Mains switch D Share bus and remote sense terminals B Control panel E DC output figure shows output...

Страница 34: ...36 EN Date 06 05 2014 Instruction Manual PS 8000 E 3U Series About the device Figure 3 Figure 4...

Страница 35: ...37 2006 Elektro Automatik GmbH Co KG Irrt mer und nderungen vorbehalten EN Date 06 05 2014 Instruction Manual PS 8000 E 3U Series About the device Figure 5...

Страница 36: ...ower stage is remai ning operable because another power stage has switched off due to overheating the power supply will continue to provide power to the output Refer to section 2 2 Device specificatio...

Страница 37: ...5 5 DC output terminal The power output is located on the rear of the device The output is not fused In order to avoid damage to the load application always take care for the nominal values of the lo...

Страница 38: ...e output voltage so that the desired voltage is provided to the load For maximum regulation see section 2 2 Device specifications information Remote sense compensation The connection for remote sense...

Страница 39: ...t display area Actual current or set value I P 4 Control buttons Setting the device condition etc 5 Rotary knob right Set value adjustment of I and P as well as settings in the device setup 6 Preset b...

Страница 40: ...ht display area will then show like this In preset mode the right rotary knob Current Power is used to adjust the power set value from 0 100 PNom The adjusted value is instantly transferred to the out...

Страница 41: ...tput remains off the memory mode exits after saving The memory sets can also be defined by remote control and corresponding commands using a digital interface except GPIB They re stored immediately Th...

Страница 42: ...ue the button Preset Power has to be pushed Note The OVP value can be lower than the voltage set value and will cause an OV alarm as soon as the output is switched on and the actual voltage reaches th...

Страница 43: ...me time and are not yet acknowledged 7 5 Overtemperature alarms As soon as an overtemperature OT alarm occurs by internal overheating the output is switched off and the status text OT is indicated Sim...

Страница 44: ...out any restrictions regarding power Input voltages below 340VAC are considered as supply undervoltage and will store the last condition as well as switch the power output off Same happens at overvolt...

Страница 45: ...ee below at parameter ID Sys Parameter Broad ID Default 0x7FF Settings 0x000 0x7FF 0 2047 Meaning Adjusts the broadcast ID BCID for the CAN ID sy stem with three IDs Vector compatible dbc files This e...

Страница 46: ...utput on off The analogue interface short AI allows to remotely control current voltage and power of the power supply but always in combination It means that it s not possible to adjust voltage via th...

Страница 47: ...ing the output off is done by connecting the pin to ground DGND via a low resistive contact like a switch open collector transistor or relay Note A digital output of for example a PLC may not be able...

Страница 48: ...proof against DGND 7 N C Not connected 8 PSEL AI Set value power 0 10V or 0 5V correspond to 0 100 of PNom Accuracy 0 5 Impedance Ri 100K 9 VMON AO Actual value voltage 0 10V or 0 5V correspond to 0...

Страница 49: ...f the analogue interfaces of the units in series connection must not be wired to each other Remote sense must not be wired It is recommended to build a series connection only with unit of same model E...

Страница 50: ...52 EN Date 06 05 2014 Instruction Manual PS 8000 E 3U Series Figure 12 Parallel connection with Share Bus Figure 13 Series connection Miscellaneous...

Отзывы: