DIGITAL TEMPERATURE MONITOR – MASTERTEMP
9
Rev
1.1
MENU CONFI
The menu CONFI is used to configure the following parameters:
Sensor readout
LCD display
RS485 output
Analog output
SD card LOG
Date and time
Password change
Language
To access the menu CONFI, with the display in presentation mode, press SET. On the lower area, the display will
show the menus. Use the key ► to navigate until the menu CONFI and press the key SET.
The menu CONFI has a password and will show a 4 digits number, “password reminder”, and below:
0000
. Use
the keys ▲ or ▼ to type the correct digit. To confirm and go to next digit, press the key ►. If necessary go back to
previous digit, press the key ◄. After typing the 4 digits, confirm pressing the key
SET
and the configuration menu
will be released, displaying the submenus. Case the password is wrong, it will be shown the message
WRONG
PASSWORD
and go back to
0000
.
After input the password, the
MasterTemp
TM
will ask it again only when going back to the presentation mode. In
case of continuing on the configuration in other menus, the password will not be requested again.
Originally, the Mastertemp password is 0000. In case of lost or forgetting, get in touch with Electron do Brasil and inform the
Password Reminder.
Navigate by menus, submenus and paratemeters with keys ▲▼◄►. Select the submenu or parameter and press SET,
change the variable with keys ▲▼ and press SET to confirm the changing. If exiting the parameter or submenu without
confirming, the parameters return to previous values.
Submenu
Parameters
Variable
Description
Sensor
Readout
Type Readout
BKP / Ind
Read mode menu for PT100 sensors.
BKP - Makes the reading from both oil temperature points and indicates the
average.
It enables the option to turn off the oil sensor (Sensor 2).
If it occurs failure in one of PT100 sensors will continue the thermal
image calculation by the active sensor and display on the monitor
display "OFF" in the failured sensor and will actuate the fault relay.
If it occurs failure in the oil sensor (Sensor 2), the Sensor1 assumes the
parameters set for oil sensor (Sensor 2).
Note: only use this option if there are 2 sensors in operation. Otherwise,
use the option Ind (independent) and use Sensor 2 input to read the oil
temperature.
Ind - The sensor 1 does the reading on the environment temperature or
Commutator and sensor 2 reads the oil temperature.
It disables the option to turn off the sensor 2 (Oil Sensor).
If it occurs sensor failure 1 will continue the thermal image calculation
based on the sensor 2 and indicate OFF the sensor 1 and will operate the
failure relay.
If the sensor 2 fails the thermal image calculation is interrupted, will
actuate the failure and forced ventilation relays. It will indicate OFF on
the sensor 2.
Enables the MDTE menu option on the auxiliary relay 2.
Note: when Ind is selected, the Sensor 2 is automatically turned on.
Содержание MASTERTEMP
Страница 1: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 1 Instructions Manual Manual de Instruções ...
Страница 7: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 4 APPLICATION EXAMPLE ...
Страница 8: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 5 CATALOG CODE DIMENSION ...
Страница 9: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 6 WIRING DIAGRAM MASTERTEMP ...
Страница 45: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 42 EXEMPLO DE APLICAÇÃO ...
Страница 46: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 43 CÓDIGO DE CATÁLOGO DIMENSÕES ...
Страница 47: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 44 DIAGRAMAS DE LIGAÇÃO MASTERTEMP ...