The distance between the unit and
heat sources is at least 1.5 m.
Use an circuit breaker. The air switch
must have functions for magnetic
tripping.
and heat tripping to prevent short
circuit and overload. The suitable
capacity is specified in the following
table.
Cooling Capacity (BTU)
Circuit Breaker
9,000
16A
12,000-18,000
20A
24,000
25A
NOTE
Make sure that the live wire, the
neutral wire and the ground wire in
the mains socket are properly
connected.
Inadequate or incorrect electrical
connections can cause electric shock
or fire.
Grounding requirements
The unit is a type I electrical
appliance. Make sure that the unit is
properly grounded.
The yellow-green wire is the ground
wire that cannot be used for other
purposes. Improper grounding can
cause electric shock.
The ground resistance must comply
with local regulations.
The mains supply must have reliable
ground terminal. Do not connect the
ground wire to water pipes, gas pipes,
contamination pipes or other possible
unsafe places.
Fuses must comply with the
prescribed model and rating printed
on the fuse cover or circuit board.