28
electrolux
breaker) with a minimum gap of 3 mm
between the contacts must be installed
between the appliance and mains cable.
The switch must not interrupt the earth
wire at any point. The yellow-green earth
wire should be 2-3 cm longer than all
other cables.
The connection cable must in any case
be laid out so that at no point does it
reach 50°C (over room temperature).
After the connection has been carried
out, the heating elements must be tested
by being operated for about 3 minutes.
Terminal block
The oven is fitted with an easily accessible
terminal block which is designed to
operate with a single-phase power
supply of 230 V.
Letter L
-
Live terminal
Letter N
-
Neutral terminal
or E
-
Earth terminal
For Europe use
Min. size Cable/
Cable / flex type
Fuse
flex
2.5 mm
2
H07 RN-F, H05 RN-F, 15 A
H05 RR-F, H05 VV-F,
H05 V2V2-F (T90),
H05 BB-F