background image

 

ELEKTROGAS – MANUALE TECNICO 

 7-10 

 

 
Automatic mode 

In  the  automatic  mode  the  angular position corresponds to the  input analogue  signal  provided 
by  a  setpoint  device.  Factory  setting  allows  full  range  of  operation  (0-90°)  but,  as  above 
described, MIN and MAX position can be set within this range in manual mode.  

An output analogue signal proportional to angular position is also provided. 

Both input and output signals can be chosen between 0-10V, 0(4)-20mA setting the proper DIP 
switch configuration (see "DIP Chart"). 
 
Behaviour without input signal (4-20mA) 
In  the  event  of  cable  break  or  any  other  situation  that  a  missing  of  input  signal  can  happen, 
servomotor has to move in a defined mode. It's possible to set three different behaviour modes 
by the DIP switch: open position, closed position and stop (see "DIP Chart"). 
 
2-point control 
The  servomotor  can  work  as  2-point  device  by  means  of  an  external  relay,  setting  the  proper 
DIP switch configuration (see "DIP Chart"). Main power supply must be also provided. 
 
 

                                Fig.7 

 
 
If an input signal  V  is applied to relay terminals, the actuator opens. If no input signal is applied 
to relay terminals, the actuator closes. 
 
Hysteresis and Filtration 
The  input  analogue  signal  is  processed  internally  with  a  resolution  of  12  bit  (corresponding  to 
0.025%). This allows, with a 4-20mA input signal for example, to detect a change of 0.005 mA 
(hysteresis). 
If the input signal fluctuations are too greatly (e.g. due to noise), use of high resolution causes 
constant corrections of the position. In this case the hysteresis may be increased up to 0.5 mA 
(resolution is reduced down to 2.5%). 

The analogue input is sampled every 1 ms (sampling rate) and a mean value is generated over 
0.1  s.  This  filtering  can  be  prolonged  by  the  terminal  T1  up  to  1  s,  but  this  also  prolongs  the 
response time to a change at the analogue input.  
 
Running time setting 
Factory setting for running time is 30 s. However, it can be modified in the same unit by means 
of terminal T1, changing the parameter 

RUN_TIME

 as follows: 

 

RUN_TIME 

Time to run  0-90° 

7 s 

15 s 

30 s   (default

60 s 

 
Moreover the parameter 

RUN_MODE

 must be set as follows: 

 

RUN_MODE 

 

Running time according to 

RUN_TIME

 parameter (default

Running time may be adjust freely (manual mode) 

 

 
 
 
 

Remote Control Unit 

Содержание MB

Страница 1: ...elektrogas com MB MZ Servomotors for butterfly valves VF VFH EE157 1209 ...

Страница 2: ...r gearbox Status LEDs and position indicator of the motor visible externally Provided with four cams with double adjusting screw adjustment tool included in the housing Two switches for manual adjustment of the position Two switches to memorize minimum and maximum position MZ Analogue input and output signals for electronic positioning MZ Very high positioning precision The same unit is suitable f...

Страница 3: ... graduated scale and locking screw to setup high fire rate of the burner In case of combustion process with excess of air or gas VF butterfly valve can be used coupled to a Lambda sensor for ratio correction In case of combustion process with pre heated air VFH butterfly valve can be used MZ servomotor WARNING Location and mode of installation must be in compliance with local rules in force VF MZ ...

Страница 4: ...50 60Hz 110VAC 50 60Hz 24V AC DC Voltage tolerance 15 10 Power consumption 5 W Enclosure IP65 EN 60529 Cable gland 2x ISO 20 EN 50262 Torque Holding torque 5 Nm Operating time 0 90 From 7s up to 60s adjustable Outputs MB Potentiometer 2 5 KΩ Ω Ω Ω Analogue inputs MZ Signal type Overload max Load impedance 0 10V 11Vdc 100KΩ Ω Ω Ω 0 20mA 22mA 250Ω Ω Ω Ω 4 20mA 22mA 250Ω Ω Ω Ω Analogue outputs MZ Sig...

Страница 5: ...potentiometer in order to suppress interferences in the input signal MZ servomotor is provided with buttons for manual adjustment of the position and for memorization of minimum maximum limits Some LEDs visible even externally show the current status of the unit e g manual operation memorization errors etc The most of settings can be made with a DIP switch on board e g selection of analogue signal...

Страница 6: ... for more than 3 seconds shorter pressing are not considered When the position is memorized LED2 lights up and the button may be released MAX position can not be lower than MIN position memorized and vice versa In this case the position won t be memorized and an alarm will go up see Alarms Chart until a new proper position is memorized Running time setting continuous With a proper software configu...

Страница 7: ...s applied to relay terminals the actuator opens If no input signal is applied to relay terminals the actuator closes Hysteresis and Filtration The input analogue signal is processed internally with a resolution of 12 bit corresponding to 0 025 This allows with a 4 20mA input signal for example to detect a change of 0 005 mA hysteresis If the input signal fluctuations are too greatly e g due to noi...

Страница 8: ... 8 9 10 ON OFF 0 10V 1 2 3 4 5 6 7 8 9 10 ON OFF 4 20mA 0 20mA programmable by means of T1 Behaviour without input signal 4 20mA 1 2 3 4 5 6 7 8 9 10 ON OFF Open position 1 2 3 4 5 6 7 8 9 10 ON OFF Closed position 1 2 3 4 5 6 7 8 9 10 ON OFF Stop Sense of rotation 1 2 3 4 5 6 7 8 9 10 ON OFF Right 1 2 3 4 5 6 7 8 9 10 ON OFF Inverted 2 point control 1 2 3 4 5 6 7 8 9 10 ON OFF 2 point control act...

Страница 9: ...m type Description Cause 1 1 Flashing Permanent light Warning Input signal is missing 4 20mA Cable break 2 2 Flashings Permanent light Warning Invalid position Operator has attempted to memorize an invalid position e g MIN MAX 3 3 Flashings Permanent light Warning Invalid running time Operator has attempted to memorize an invalid running time out of 7 60 s range 4 4 Flashings Permanent light Warni...

Страница 10: ...dard Optional Programmable T1 Not available Specification is omitted if does not match any requirement Manufacturer reserves the right to update or make technical changes without prior notice Standards and approvals The actuators meet current European approval requirements regarding electrical safety Electromagnetic Compatibility 2004 108 CE Low Voltage Directive 2006 95 CE Quality Management Syst...

Отзывы: