ELEKTROGAS – MANUALE TECNICO
6-10
Fig.6
Manual mode
For a simplified commissioning, the actuator can be operated manually. The manual mode is
useful to determine the operating positions for the process, such as the High/Low fire positions.
To enter in the manual mode press the switch S1 downwards (LED1 lights up). Now it's possible
to move the valve toward the MAX. position (counter clockwise rotation seen from the top), by
pressing the push button B2, and to move the valve toward the MIN. position (clockwise rotation
seen from the top), by pressing the push button B1 (factory setting provides the cams C1 and
C2 at 0° and 90°). The initial rotating speed is 0. 25 RPM, this lets operator perform an accurate
adjustment of position. If the button is pressed for more than 3 seconds the rotating speed shifts
to 1 RPM.
Setting of the MIN and MAX positions
In manual mode it's possible to memorize current position as MIN (MAX) by pressing button B4
(B3) for more than 3 seconds (shorter pressing are not considered). When the position is
memorized, LED2 lights up and the button may be released.
MAX position can not be lower than MIN position memorized (and vice versa). In this case the
position won't be memorized and an alarm will go up (see "Alarms Chart") until a new proper
position is memorized.
Running time setting (continuous)
With a proper software configuration made by terminal T1, running time can be chosen also on
field. By means of terminal T1, changing the parameter
RUN_MODE
from 1 to 5 as follows:
RUN_MODE
1
Running time according to
RUN_TIME
parameter (default)
5
Running time may be adjust freely (manual mode)
Press both B3 and B4 buttons at the same time, for the time required (LED3 lights up). Running
time must be included between 7 s and 60 s, otherwise its value won't be memorized and an
alarm will go up (see "Alarms Chart") until a new proper time is memorized. A proper running
time is operative in automatic mode only.
Opening (B2)
Automatic/
Manual (S1)
Closing (B1)
S
e
tp
o
in
t
O
u
tp
u
t
0
N
2
3
0
-1
1
0
V
C
O
M
M
IN
M
A
X
2
4
V
N
D
ir
e
c
t
m
o
to
r
d
ri
v
in
g
T
e
rm
in
a
l
(T
1
)
H
y
s
te
re
s
is
M
IN
(
B
4
)
M
A
X
(
B
3
)
LED1
L
E
D
3
L
E
D
2