background image

                        

V.1.2

4

    

 

  

 

March

 1

5

, 201

8

Содержание Shark 200

Страница 1: ...V 1 24 March 15 2018 ...

Страница 2: ...This page intentionally left blank ...

Страница 3: ...eans electronic or mechanical including photocopying record ing or information storage or retrieval systems or any future forms of duplication for any purpose other than the purchaser s use without the expressed written permission of Electro Industries GaugeTech 2018 Electro Industries GaugeTech Shark is a registered trademark of Electro Industries GaugeTech The distinctive shapes styles and overa...

Страница 4: ...01 ii Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 5: ...te of shipment During the warranty period we will at our option either repair or replace any product that proves to be defective To exercise this warranty fax or call our customer support department You will receive prompt assistance and return instructions Send the instrument transporta tion prepaid to EIG at 1800 Shames Drive Westbury NY 11590 Repairs will be made and the instrument will be retu...

Страница 6: ...ted in this publication has been carefully checked for reliability however no responsibility is assumed for inaccuracies The information contained in this document is subject to change without notice This symbol indicates that the operator must refer must to an important WARNING or CAUTION in the operating instructions Please see 4 1 Considerations When Installing Meters on page 4 1 for important ...

Страница 7: ...el pour AVERTISSEMENT ou MISE EN GARDE l information pour éviter toute blessure ou tout endommagement du produit About Electro Industries GaugeTech EIG Founded in 1975 by engineer and inventor Dr Samuel Kagan Electro Industries GaugeTech changed the face of power monitoring forever with its first breakthrough innovation an affordable easy to use AC power meter More than forty years since its found...

Страница 8: ...01 vi Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 9: ...nputs 2 5 2 1 2 Ordering Information 2 5 2 1 3 V Switch Key Technology 2 8 2 1 4 Measured Values 2 10 2 1 5 Utility Peak Demand 2 11 2 2 Specifications 2 12 2 3 Compliance 2 17 2 4 Accuracy 2 19 3 Mechanical Installation 3 1 3 1 Introduction 3 1 3 2 ANSI Installation Steps 3 3 3 3 DIN Installation Steps 3 4 3 4 Transducer Installation 3 6 4 Electrical Installation 4 1 4 1 Considerations When Insta...

Страница 10: ...figuring Connection Setting 6 13 6 2 5 5 Configuring Communication Port Setting 6 13 6 2 6 Using Operating Mode 6 15 6 3 Understanding the of Load Bar 6 16 6 4 Performing Watt Hour Accuracy Testing Verification 6 17 7 Using the I O Option Cards 7 1 7 1 Overview 7 1 7 2 Installing Option Cards 7 1 7 3 Configuring Option Cards 7 3 7 4 1mA Output Card 1mAOS 7 3 7 4 1 Specifications 7 3 7 4 2 Default ...

Страница 11: ...eature 8 24 9 Data Logging 9 1 9 1 Overview 9 1 9 2 Available Logs 9 1 A Shark 200 Meter Navigation Maps A 1 A 1 Introduction A 1 A 2 Navigation Maps Sheets 1 to 4 A 1 B Modbus Map and Retrieving Logs B 1 B 1 Introduction B 1 B 2 Modbus Register Map Sections B 1 B 3 Data Formats B 1 B 4 Floating Point Values B 2 B 5 Retrieving Logs Using the Shark 200 Meter s Modbus Map B 3 B 5 1 Data Formats B 4 ...

Страница 12: ...50 Network E 7 E 1 4 EIG s Implementation of the IEC 61850 Server E 9 E 1 4 1 Shark 200 Server Configuration E 11 E 1 5 Reference Materials E 12 E 1 6 Free Tools for IEC 61850 Start up E 12 E 1 7 Commercial Tools for an IEC 61850 Implementation E 13 E 2 Using the Shark 200 meter s IEC 61850 Protocol Ethernet Network Card E 13 E 2 1 Overview E 13 E 2 2 Installing the IEC 61850 Protocol Ethernet Net...

Страница 13: ...ection or a delta connection Each connection has several different manifestations in actual use When attempting to determine the type of connection in use it is a good practice to follow the circuit back to the transformer that is serving the circuit It is often not possible to conclusively determine the correct circuit connection simply by counting the wires in the service or checking voltages Ch...

Страница 14: ...itions the currents are also separated by 120o However unbalanced loads and other conditions can cause the currents to depart from the ideal 120o separation Three phase voltages and currents are usually represented with a phasor diagram A phasor diagram for the typical connected voltages and currents is shown in Figure 1 2 Figure 1 2 Phasor Diagram Showing Three phase Voltages and Currents N Phase...

Страница 15: ...t of the wye In many industrial applications the facility will be fed with a four wire wye service but only three wires will be run to individual loads The load is then often referred to as a delta connected load but the service to the facility is still a wye service it contains four wires if you trace the circuit back to its source usually a transformer In this type of connection the phase to gro...

Страница 16: ... 1 3 Three phase Delta Winding Relationship In this example of a delta service three wires will transmit the power to the load In a true delta service the phase to ground voltage will usually not be balanced because the ground is not at the center of the delta Figure 1 4 shows the phasor relationships between voltage and current on a three phase delta circuit In many delta services one corner of t...

Страница 17: ...rounded delta used for lighting loads In this connection the center point of one winding is grounded On a 120 240 volt four wire grounded delta service the phase to ground voltage would be 120 volts on two phases and 208 volts on the third phase Figure 1 5 shows the phasor diagram for the voltages in a three phase four wire delta system Figure 1 5 Phasor Diagram Showing Three phase Four Wire Delta...

Страница 18: ... total three phase value In older ana log meters this measurement was accomplished using up to three separate elements Each element combined the single phase voltage and current to produce a torque on the meter disk All three elements were arranged around the disk so that the disk was subjected to the combined torque of the three elements As a result the disk would turn at a higher speed and regis...

Страница 19: ...antage of simultaneous sampling is the reduction of error introduced due to the difference in time when the samples were taken Figure 1 6 Three Phase Wye Load Illustrating Kirchhoff s Law and Blondel s Theorem Blondel s Theorem is a derivation that results from Kirchhoff s Law Kirchhoff s Law states that the sum of the currents into a node is zero Another way of stating the same thing is that the ...

Страница 20: ...ways based on some time increment it is the integration of power over a defined time increment Energy is an important value because almost all electric bills are based in part on the amount of energy used Typically electrical energy is measured in units of kilowatt hours kWh A kilowatt hour represents a constant load of one thousand watts one kilowatt for one hour Stated another way if the power d...

Страница 21: ...cified that the load is constant over that minute we can convert the power reading to an equivalent consumed energy reading by multiplying the power reading times 1 60 converting the time base from minutes to hours Figure 1 7 Power Use over Time 0 10 20 30 40 50 60 70 80 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Time minutes s t t a w o l i k ...

Страница 22: ...ustrated in Figure 1 7 and adjust the energy reading to an hourly value that constitutes the demand In the example the accumulated energy is 14 92 kWh But this measurement was made over a 15 minute interval To convert the reading to a demand value it must be normalized to a 60 minute interval If the pattern were repeated for an additional three 15 minute intervals the total energy would be four ti...

Страница 23: ...nd 70 kWh However during two intervals the energy rises sharply and peaks at 100 kWh in interval number 7 This peak of usage will result in setting a high demand reading For each interval shown the demand value would be four times the indicated energy reading So interval 1 would have an associated demand of 240 kWh hr Interval 7 will have a demand value of 400 kWh hr In the data shown this is the ...

Страница 24: ...the voltage and the value of corresponding current that is directly in phase with the volt age However in actual practice the total current is almost never in phase with the voltage Since the current is not in phase with the voltage it is necessary to consider both the inphase component and the component that is at quadrature angularly rotated 90o or perpendicular to the voltage Figure 1 9 shows a...

Страница 25: ...n be defined in two different ways The more common method of calculating power factor is the ratio of the real power to the apparent power This relationship is expressed in the following formula Total PF real power apparent power watts VA This formula calculates a power factor quantity known as Total Power Factor It is called Total PF because it is based on the ratios of the power delivered The de...

Страница 26: ...oncentrations of non linear loads Devices such as computer power supplies variable speed drives and fluorescent light ballasts make current demands that do not match the sinusoidal waveform of AC electricity As a result the current waveform feeding these loads is periodic but not sinusoidal Figure 1 10 shows a normal sinusoidal current waveform This example has no distortion Figure 1 10 Nondistort...

Страница 27: ...mental 60 Hz frequency This modeling is performed by mathematically disassembling the distorted waveform into a collection of higher frequency waveforms These higher frequency waveforms are referred to as harmonics Figure 1 12 shows the content of the harmonic frequencies that make up the distortion portion of the waveform in Figure 1 11 Figure 1 12 Waveforms of the Harmonics 1000 500 0 500 1000 t...

Страница 28: ... non linear loads are introducing significant quantities of higher order harmonics Since much voltage monitoring and almost all current monitoring is performed using instrument transformers the higher order harmonics are often not visible Instrument transformers are designed to pass 60 Hz quantities with high accuracy These devices when designed for accuracy at low frequency do not pass high frequ...

Страница 29: ...g that is used to record multiple cycles of all voltage and current waveforms in response to a transient condition 1 5 Power Quality Power quality can mean several different things The terms power quality and power quality problem have been applied to all types of conditions A simple defini tion of power quality problem is any voltage current or frequency deviation that results in mis operation or...

Страница 30: ...fining the cause and possible solutions to the problem Cause Disturbance Type Source Impulse transient Transient voltage disturbance sub cycle duration Lightning Electrostatic discharge Load switching Capacitor switching Oscillatory transient with decay Transient voltage sub cycle duration Line cable switching Capacitor switching Load switching Sag swell RMS voltage multiple cycle duration Remote ...

Страница 31: ...ark 200 meter offers extensive memory for logging and recording The unit provides you with up to seven logs three historical logs a log of limit alarms a log of I O changes a waveform log and a sequence of events log See NOTE on Flash memory on page 2 6 The purposes of these features include historical load profiling voltage analysis and recording power factor distribution The Shark 200 meter s re...

Страница 32: ...and MeterManager EXT Software User Manual for instructions The INP100S card also supports data push of up to 15 meter readings to cloud ser vices using the JSON structure such as Lucid BuildingOS Data Push For instruc tions on setting up the meter to perform data push see 8 4 2 4 Data Push on page 8 20 The Shark 200 meter is designed with advanced measurement capabilities allowing it to achieve hi...

Страница 33: ...y see Chapter 8 in the Communicator EXTTM 4 0 and MeterManager EXT Software User Manual for instructions on using this feature V Switch Key technology field upgradeable without removing installed meter Percentage of Load bar for analog meter reading 0 001 Frequency measurement for Generating stations Interval energy logging Line frequency time synchronization Easy to use faceplate programming IrDA...

Страница 34: ...tor EXTTM 4 0 and MeterManager EXT Software User Manual from the Shark Series Product CD or by clicking Help Contents from the Communicator EXTTM Main screen In addition to the Shark 200 meter trans ducer configuration a Shark 200T trans ducer configuration is available The Shark 200T transducer is a digital transducer only unit providing RS485 communication via Modbus RTU Modbus ASCII or DNP 3 0 ...

Страница 35: ...nt must be specified and ordered with the meter The current inputs are only to be connected to external current transformers The Shark 200 meter s current inputs use a unique dual input method Method 1 CT Pass Through The CT wire passes directly through the meter without any physical termination on the meter This is preferable for utility users when sharing relay class CTs Method 2 Current Gills T...

Страница 36: ...d control functions V5 Above with 3 MegaBytes data logging memory and 64 samples per cycle waveform recorder V6 Above with 4 MegaBytes data logging memory and 512 samples per cycle waveform recorder See 2 1 3 V SwitchTM Key Technology on page 2 8 for more information and instructions on obtaining a V SwitchTM key 5 Power Supply D2 Option Universal 90 to 265 V AC 50 60 Hz or 100 to 370 V DC D Optio...

Страница 37: ...tions 1mAOS 4 Channel Analog output 0 1 bidirectional 20mAOS 4 Channel Analog output 4 20mA FOSTS Fiber Optic Output ST terminated FOVPS Fiber Optic Output Versatile Link terminated INP300S IEC 61850 Protocol Ethernet Network Example Shark200 60 10 V2 D INP100S X Shark 200 meter with 60 Hz System 5 A Secondary V 2 V SwitchTM key 18 60 V DC power supply 10 100BaseT Ethernet in Card Slot 1 and no ca...

Страница 38: ...ch key 4 V 4 Multifunction measurement with harmonics 2 MegaBytes for data logging and limit and control functions V Switch key 5 V 5 Multifunction measurement with harmonics 3 MegaBytes for data logging limit and control functions and 64 samples per cycle waveform recorder V Switch key 6 V 6 Multifunction measurement with harmonics 4 MegaBytes for data logging limit and control functions and 512 ...

Страница 39: ...he V SwitchTM Key 1 Open Communicator EXTTM software 2 Power up your meter 3 Connect to the Shark 200 meter through Communicator EXTTM software see Chapter 5 Communication Installation on page 5 1 4 Click Tools Change V Switch from the Title Bar A screen opens requesting the encrypted key 5 Enter the V SwitchTM key provided by EIG 6 Click the Update button The V SwitchTM key is enabled and the met...

Страница 40: ...e table below shows some values are also available in average maximum and minimum Table 1 Measured Values Instantaneous Avg Max Min Voltage L N X X X Voltage L L X X X Current per Phase X X X X Current Neutral X X X X Watt A B C Tot X X X X VAR A B C Tot X X X X VA A B C Tot X X X X PF A B C Tot X X X X Watt Hour A B C Tot X Wh A B C Tot X Wh Net X VARh A B C Tot X VARh A B C Tot X VARh Net A B C ...

Страница 41: ...ervals you define usually 5 15 or 30 minutes Rolling window Demand mode functions like multiple overlapping Block windows You define the subintervals at which an average of Demand is calculated An example of Rolling window Demand mode would be a 15 minute Demand block using 5 minute subintervals thus providing a new Demand reading every 5 minutes based on the last 15 minutes Utility Demand feature...

Страница 42: ...n 6 to 13 VA 4 5 to 10 W depending on the meter s hardware configuration Voltage Inputs For Accuracy specifications see 2 4 Accuracy on page 2 19 Absolute Maximum Range Universal Auto ranging Phase to Reference Va Vb Vc to Vref 20 to 576 V AC Phase to Phase Va to Vb Vb to Vc Vc to Va 0 to 721 V AC Supported hookups 3 Element Wye 2 5 Element Wye 2 Element Delta 4 Wire Delta Input Impedance 1 MOhm P...

Страница 43: ... 19 Class 10 5 A Nominal 10 A Maximum Class 2 1 A Nominal 2 A Maximum Burden 0 005 VA Per Phase Max at 11 A Pickup Current 0 1 of Nominal 0 2 of Nominal if using Current Only mode that is there is no connection to the voltage inputs Connections O Lug or U Lug electrical connec tion Figure 4 1 Pass through wire 0 177 4 5 mm maximum diameter Figure 4 2 Quick connect 0 25 male tab Figure 4 3 Fault Wi...

Страница 44: ... duplex Min input Impedance 96 kΩ Max output current 60 mA Wh Pulse KYZ output contacts and infrared LED light pulses through face plate see 6 4 Per forming Watt Hour Accuracy Testing Verification on page 6 17 for Kh values Pulse Width 90 ms Full Scale Frequency 3 Hz Contact type Solid state SPDT NO C NC Relay type Solid state Peak switching voltage DC 350 V Continuous load current 120 mA Peak loa...

Страница 45: ...mart Grid Solutions Infrared LED Peak Spectral wavelength 940 nm Reset state Off Internal schematic Output timing De energized state NO C NC 90ms 90ms 3600 Watt P pulse Watthour Kh s T º ª LED ON LED ON LED OFF LED OFF LED OFF IR LED Light Pulses Through face plate NO C NC NO C NC NO C NC NO C NC NO C NC KYZ output Contact States Through Backplate P Watt Not a scaled value Kh See Section 6 4 for v...

Страница 46: ...20 to 70 o C Humidity to 95 RH Non condensing Faceplate Rating NEMA 1 mounting gasket included Measurement Methods Voltage current True RMS Power Sampling at over 400 samples per cycle on all channels Update Rate Watts VAR and VA Every 6 cycles e g 100 ms 60 Hz All other parameters Every 60 cycles e g 1 s 60 Hz 1 second for Current Only measure ment if reference voltage is not available Communicat...

Страница 47: ...nated card Protocols Modbus RTU Modbus ASCII DNP 3 0 Com Port Baud Rate RS485 Only 1200 2400 4800 All Com Ports 9600 to 57600 bps Com Port Address 001 247 DNP ONLY 001 65520 Data Format 8 Bit No Parity RS485 also Even or Odd Parity Shark 200T transducer Default Initial communication baud rate 9600 see Chapter 5 Mechanical Parameters Dimensions see Chapter 3 Weight without Option card 2 pounds 0 9 ...

Страница 48: ...toring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions ANSI C62 41 Burst EN61000 6 2 Immunity for Industrial Environments 2005 EN61000 6 4 Emission Standards for Industrial Environments 2007 EN61326 EMC Requirements 2006 KEMA Certified IEC 61850 ...

Страница 49: ... 1 of reading 1 3 0 15 to 5 A Current Neutral calcu lated A 2 of Full Scale 1 0 15 to 5 A 45 to 65 Hz Active Power Total W 0 2 of reading 1 2 0 15 to 5 A 69 to 480 V 0 5 to 1 lag lead PF Active Energy Total Wh 0 2 of reading 1 2 0 15 to 5 A 69 to 480 V 0 5 to 1 lag lead PF Reactive Power Total VAR 0 2 of reading 1 2 0 15 to 5 A 69 to 480 V 0 to 0 8 lag lead PF Reactive Energy Total VARh 0 2 of rea...

Страница 50: ...y For 1 A Class 2 Nominal the input current range for accuracy specification is 20 of the values listed in the table 2 For unbalanced Voltage inputs where at least one crosses the 150 V auto scale threshold for example 120 V 120 V 208 V system degrade the accuracy to 0 4 of reading 3 With reference Voltage applied VA VB or VC Otherwise degrade accuracy to 0 2 See hookup diagrams 8 9 and 10 in 4 8 ...

Страница 51: ...stallations simply use existing DIN or ANSI punches For existing panels pull out old analog meters and replace them with the Shark 200 meter See 3 4 Transducer Installation on page 3 6 for Shark 200T transducer installation See 4 8 Electrical Connection Diagrams on page 4 8 for wir ing diagrams NOTE The drawings shown below and on the next page give you the meter dimen sions in inches and centimet...

Страница 52: ...ch The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Figure 3 2 Shark 200T Dimensions Figure 3 3 Meter Back Dimensions 4 85 12 32 0 91 2 31 0 77 1 95 3 25 8 26 3 56 9 04 3 56 9 04 ...

Страница 53: ...nsions Recommended Tools for Shark 200 Meter Installation 2 Phillips screwdriver Small adjustable wrench Wire cutters The Shark 200 meter is designed to withstand harsh environmental conditions however it is recommended you install it in a dry location free from dirt and corrosive substances see Environmental specifications in 2 2 Specifications on page 2 12 3 2 ANSI Installation Steps 1 Slide met...

Страница 54: ...t washer lock washer and nut on each threaded rod Use a small wrench to tighten Do not overtighten The maximum installation torque is 0 4 Newton Meter Figure 3 5 ANSI Installation 3 3 DIN Installation Steps 1 Slide meter with NEMA 12 Mounting Gasket into panel remove ANSI Studs if in place 2 From back of panel slide 2 DIN Mounting Brackets into grooves in top and bottom of meter housing Snap into ...

Страница 55: ...lutions 3 Secure meter to panel by using a 2 Phillips screwdriver to tighten the screw on each of the two mounting brackets Do not overtighten the maximum installation torque is 0 4 Newton Meter Figure 3 6 DIN Installation DIN mounting bracket Top mounting bracket groove Bottom mounting bracket groove DIN Mounting brackets Remove unscrew ANSI studs for DIN installation DIN Installation 92mm Square...

Страница 56: ...cm 1 Slide top groove of meter onto the DIN Rail 2 Press gently until the meter clicks into place NOTES To remove the meter from the DIN Rail pull down on the Release Clip to detach the unit from the rail see Figure 3 7 If mounting with the DIN Rail provided use the black rubber stoppers also provided see Figure 3 8 NOTE ON DIN RAILS DIN Rails are commonly used as a mounting channel for most termi...

Страница 57: ...tion Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Figure 3 8 DIN Rail Detail Black Rubber Stoppers 2 Release Clip ...

Страница 58: ...anical Installation Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 59: ...urrents Avoid contact with any current carrying surfaces Do not use the meter or any I O Output device for primary protection or in an energy limiting capacity The meter can only be used as secondary protection Do not use the meter for applications where failure of the meter may cause harm or death Do not use the meter for any application where there may be a risk of fire All meter terminals shoul...

Страница 60: ...limentation et de mettre tous les circuits branchés hors tension Ne pas utiliser les compteurs ou sorties d appareil pour une protection pri maire ou capacité de limite d énergie Le compteur peut seulement être util isé comme une protection secondaire Ne pas utiliser le compteur pour application dans laquelle une panne de compteur peut causer la mort ou des blessures graves Ne pas utiliser le comp...

Страница 61: ... device A SWITCH OR CIRCUIT BREAKER SHALL BE INCLUDED IN THE END USE EQUIPMENT OR BUILDING INSTALLA TION THE SWITCH SHALL BE IN CLOSE PROXIMITY TO THE EQUIP MENT AND WITHIN EASY REACH OF THE OPERATOR THE SWITCH SHALL BE MARKED AS THE DISCONNECTING DEVICE FOR THE EQUIPMENT IMPORTANT SI L ÉQUIPEMENT EST UTILISÉ D UNE FAÇON NON SPÉCIFIÉE PAR LE FABRICANT LA PROTECTION FOURNIE PAR L ÉQUIPEMENT PEUT ÊT...

Страница 62: ...t the current gills This connection uses nickel plated brass studs current gills with screws at each end This connection allows the CT wires to be terminated using either an O or a U lug Tighten the screws with a 2 Phillips screwdriver The maximum installation torque is 1 Newton Meter Other current connections are shown in figures 4 2 and 4 3 Voltage and RS485 KYZ connections are shown in Figure 4...

Страница 63: ...s 4 3 CT Leads Pass Through No Meter Termination The second method allows the CT wires to pass through the CT inputs without termi nating at the meter In this case remove the current gills and place the CT wire directly through the CT opening The opening accommodates up to 0 177 4 5mm maximum diameter CT wire Figure 4 2 Pass Through Wire Electrical Connection 5 XJSF QBTTJOH UISPVHI NFUFS VSSFOU HJ...

Страница 64: ...utions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 4 4 Quick Connect Crimp on Terminations For quick termination or for portable applications 0 25 quick connect crimp on connectors can also be used Figure 4 3 Quick Connect Electrical Connection Quick connect crimp on terminations ...

Страница 65: ... 6 Ground Connections The meter s Ground terminals should be connected directly to the installation s protective earth ground Use AWG 12 2 5 mm2 wire for this connection 4 7 Voltage Fuses EIG requires the use of fuses on each of the sense voltages and on the control power Use a 0 1 A fuse on each voltage input Use a 3 A Slow Blow fuse on the power supply EIG offers the EI CP Panel meter protective...

Страница 66: ...wiring The diagrams are presented in the following order 1 Three Phase Four Wire System Wye Delta with Direct Voltage 3 Element a Example of Dual Phase Hookup b Example of Single Phase Hookup 2 Three Phase Four Wire System Wye with Direct Voltage 2 5 Element 3 Three Phase Four Wire Wye Delta with PTs 3 Element 4 Three Phase Four Wire Wye with PTs 2 5 Element 5 Three Phase Three Wire Delta with Dir...

Страница 67: ... The Leader In Power Monitoring and Smart Grid Solutions 1 Service WYE Delta 4 Wire with No PTs 3 CTs Select 3 EL WYE 3 Element Wye from the Shark meter s front panel display see Chapter 6 lc HI LO lb HI LO la HI LO Earth Ground L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT Shorting Block FUSES 3 x 0 1A FUSE 3A C C B B A A N N C B A C B A ...

Страница 68: ...es GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 1a Example of Dual Phase Hookup Select 3 EL WYE 3 Element Wye from the Shark meter s Front Panel Display see Chapter 6 lc HI LO lb HI LO la HI LO Earth Ground x L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT Shorting Block FUSES 2 x 0 1A FUSE 3A C C B B A A N N ...

Страница 69: ...es GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 1b Example of Single Phase Hookup Select 3 EL WYE 3 Element Wye from the Shark meter s Front Panel Display see Chapter 6 lc HI LO lb HI LO la HI LO Earth Ground x L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT Shorting Block x FUSE 0 1A FUSE 3A C C B B A A N N ...

Страница 70: ...he Leader In Power Monitoring and Smart Grid Solutions 2 Service 2 5 Element WYE 4 Wire with No PTs 3 CTs Select 2 5 EL WYE 2 5 Element Wye from the Shark meter s front panel display see Chapter 6 lc HI LO lb HI LO la HI LO Earth Ground L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT Shorting Block FUSES 2 x 0 1A FUSE 3A C C B B A A N N C B A ...

Страница 71: ...eader In Power Monitoring and Smart Grid Solutions 3 Service WYE Delta 4 Wire with 3 PTs 3 CTs Select 3 EL WYE 3 Element Wye from the Shark meter s front panel display see Chapter 6 lc HI LO lb HI LO la HI LO Earth Ground Earth Ground L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT Shorting Block FUSES 3 x 0 1A FUSE 3A C C B B A A N N C B A C B A ...

Страница 72: ...der In Power Monitoring and Smart Grid Solutions 4 Service 2 5 Element WYE 4 Wire with 2 PTs 3 CTs Select 2 5 EL WYE 2 5 Element Wye from the Shark meter s front panel display see Chapter 6 lc HI LO lb HI LO la HI LO Earth Ground Earth Ground L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT Shorting Block FUSES 2 x 0 1A FUSE 3A C C B B A A N N C B A ...

Страница 73: ...eader In Power Monitoring and Smart Grid Solutions 5 Service Delta 3 Wire with No PTs 2 CTs Select 2 CT DEL 2 CT Delta from the Shark meter s front panel display see Chapter 6 lc HI LO lb HI LO la HI LO Earth Ground L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT Shorting Block FUSES 3 x 0 1A FUSE 3A C C B B A A C B A C B A Not connected to meter ...

Страница 74: ...In Power Monitoring and Smart Grid Solutions 6 Service Delta 3 Wire with 2 PTs 2 CTs Select 2 CT DEL 2 CT Delta from the Shark meter s front panel display see Chapter 6 lc HI LO lb HI LO la HI LO Earth Ground Earth Ground L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT Shorting Block FUSES 2 x 0 1A FUSE 3A C C B B A A C B A C B A Not connected to meter ...

Страница 75: ...ons 7 Service Delta 3 Wire with 2 PTs 3 CTs Select 2 CT DEL 2 CT Delta from the Shark meter s front panel display see Chapter 6 NOTE The third CT for hookup is optional and is used only for Current measurement lc HI LO lb HI LO la HI LO Earth Ground Earth Ground L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT Shorting Block FUSES 2 x 0 1A FUSE 3A C C B B A A C B A C B A Not connecte...

Страница 76: ...ns 8 Service Current Only Measurement Three Phase Select 3 EL WYE 3 Element Wye from the Shark meter s front panel display see Chapter 6 NOTE Even if the meter is used only for current measurement an AN reference is recommended for improved accuracy lc HI LO lb HI LO la HI LO Earth Ground L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT Shorting Block FUSE 3A FUSE 0 1A 20VAC Minimum ...

Страница 77: ...tions 9 Service Current Only Measurement Dual Phase Select 3 EL WYE 3 Element Wye from the Shark meter s front panel display see Chapter 6 NOTE Even if the meter is used only for current measurement an AN reference is recommended for improved accuracy lc HI LO lb HI LO la HI LO Earth Ground L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT Shorting Block FUSE 3A FUSE 0 1A 20VAC Minimu...

Страница 78: ...ngle Phase Select 3 EL WYE 3 Element Wye he Shark meter s front panel display see Chapter 6 NOTES Even if the meter is used only for current measurement an AN reference is recom mended for improved accuracy The diagram shows a connection to Phase A but you can also connect to Phase B or Phase C lc HI LO lb HI LO la HI LO Earth Ground L Power Supply Connection N L GND N Vref Va Vb Vc LINE LOAD CT S...

Страница 79: ...rs are ideal for metering systems RTUs PLCs and protective relays They are used specifically to extend the life and increase reliability of critical control apparatus For best protection it is recommended to use two protectors These will protect the instrument on the line inputs and on the reference input to ground The protectors have LED indication to annunciate when the protection has worn out T...

Страница 80: ...trical Installation Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 81: ...ds on page 7 1 and 8 Using the Ethernet Card INP100S on page 8 1 and Appendix E Using the IEC 61850 Protocol Ethernet Net work Card INP300S on page E 1 for more information on these options 5 1 1 IrDA Port Com 1 The Shark 200 meter s Com 1 IrDA port is on the face of the meter The IrDA port allows the unit to be read and programmed without the need of a communication cable Just point at the meter ...

Страница 82: ...ple Shark 200 meters to a PC or other device at either a local or remote site All RS485 connections are viable for up to 4000 feet 1219 20 meters Figure 5 2 Shark 200 Meter Connected to a PC via RS485 bus As shown in Figure 5 2 to connect a Shark 200 meter to a PC you need to use an RS485 to RS232 converter such as EIG s Unicom 2500 See 5 1 2 1 Using the Unicom 2500 on page 5 5 for additional info...

Страница 83: ... Communicator EXTTM 4 0 and MeterManager EXT Software User Manual for instruc tions Protect cables from sources of electrical noise Avoid both Star and Tee connections see Figure 5 5 No more than two cables should be connected at any one point on an RS485 net work whether the connections are for devices converters or terminal strips Include all segments when calculating the total cable length of a...

Страница 84: ...com 2500 Figure 5 4 RS485 Daisy Chain Connection Figure 5 5 Incorrect T and Star Topologies Twisted pair shielded SH cable RT SH RT SH SH SH Slave device 1 Slave device 2 Last Slave device N Master device Earth Connection preferably at single location Twisted pair shielded SH cable Twisted pair shielded SH cable Twisted pair shielded SH cable SH SH SH Slave device 1 Slave device 2 Last Slave devic...

Страница 85: ...lation and Operation Manual for additional information You can order the Unicom 2500 and the recommended communication cable for it from EIG s webstore www electroind com store From the left side of the webpage select Communication Products for the Unicom 2500 and Cables and Accessories for the RS485 4 wire to 2 wire cable Figure 5 6 illustrates the Unicom 2500 connections for RS485 and Fiber Opti...

Страница 86: ... terminal and con nect the RX and TX terminals with a jumper wire to make the terminal See the figure on the right for the Unicom 2500 s settings The Unicom s Baud rate must match the Baud rate of the meter s RS485 port you set the Baud rate by turning the screw to point at the rate you want 5 1 2 2 Using the RS485 to USB Communication Converter EIG offers an RS485 to USB converter to facilitate c...

Страница 87: ...n in the fig ure below 3 Connect the USB connector to your device s USB port 4 Follow the programming instructions in Section 5 2 2 5 2 Shark 200T Transducer Communication and Programming Overview The Shark 200T transducer does not include a display on the front face of the meter there are no buttons or IrDA Port on the face of the meter Programming and communication utilize the RS485 connection o...

Страница 88: ... is useful in debugging or if you do not know the meter s programmed settings and want to find them For 5 seconds after the Shark 200T is powered up you can use the RS485 port with Default Communication mode to poll the Name Register You do this by connecting to the meter with the following default settings see 5 2 2 Connecting to the Meter through Communicator EXTTM Software on page 5 9 Baud Rate...

Страница 89: ...municator EXTTM Software How to Connect 1 Open the Communicator EXTTM software 2 Click the Connect icon in the Icon bar 3 The Connect screen opens showing the Default settings Make sure your settings are the same as shown here Use the pull down menus to make any necessary changes to the settings 4 Click the Connect button If you have a problem connecting you may have to disconnect power to the met...

Страница 90: ...ies GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 5 You will see the Device Status screen confirming connection to your meter Click OK 6 Click the Profile icon in the Menu Bar 7 You will see the Shark 200 meter s Device Profile screen The menu on the left side of the screen lets you navigate between Settings screens see below ...

Страница 91: ... 1 247 for DNP ONLY 1 65520 Protocol Modbus RTU Modbus ASCII or DNP Baud Rate 1200 to 57600 Your meter must have Runtime Firmware version 26 or higher to set Baud rates of 1200 2400 and 4800 Response Delay 0 750 msec Parity Odd Even or None Your meter must have Runtime Firmware version 26 or higher to be able to set Parity DNP Options for Voltage Current and Power these fields allow you to choose ...

Страница 92: ... Solutions See Chapter 8 in the Communicator EXTTM 4 0 and MeterManager EXT Software User Manual for more information 8 When changes are complete click the Update Device button to send a new profile to the meter 9 Click Exit to leave the Device Profile or click other menu items to change other aspects of the Device Profile see 5 2 2 1 Shark 200 Meter Device Profile Set tings on page 5 13 for instr...

Страница 93: ...the Communicator EXTTM 4 0 and MeterManager EXT Software User Manual for detailed instructions on configuring all settings of the meter s Device Profile You can view the manual online by clicking Help Contents from the Communicator EXTTM Main screen CT PT Ratios and System Hookup IMPORTANT You have two options for entering the CT and PT settings You can either enter CT PT Numerator Denominator and...

Страница 94: ...Ratio the ratio to be applied and click Update CT Current Full Scale Display only PT Ratios PT Numerator Primary 1 9999 PT Denominator Secondary 40 600 PT Multiplier Scaling 1 10 100 or 1000 Voltage Full Scale Display only System Wiring 3 Element Wye 2 5 Element Wye 2 CT Delta Example Settings For a CT of 2000 5A set the following CT Ratios in the entry fields CT Numerator Primary 2000 CT Denomina...

Страница 95: ... field The minimum primary voltage based on the percentage you entered is displayed at the bottom of the screen Example CT Settings 200 5 A Set the Ct n value for 200 Ct Multiplier value for 1 800 5 A Set the Ct n value for 800 Ct Multiplier value for 1 2 000 5 A Set the Ct n value for 2000 Ct Multiplier value for 1 10 000 5 A Set the Ct n value for 1000 Ct Multiplier value for 10 Example PT Setti...

Страница 96: ... are as follows Phases Displayed A A and B A B and C This field determines which phases are displayed on the faceplate For example if you select A and B only those two phases will be displayed on the faceplate Auto Scroll Display Yes or No This field enables disables the scrolling of selected readings on the faceplate If enabled the readings scroll every 5 seconds Enable on Face Plate of Display C...

Страница 97: ...ered Flip Power Factor Sign Yes or No Current I Display Autoscale On to apply scaling to the current display or Off No decimal places Display Voltage in Secondary Yes or No NOTE There are two methods available to address power generation applications where the power sign might need to be changed There is the IEEE IEC method and the Shark meter s legacy method They are both readily available by sel...

Страница 98: ...t to use the legacy system shown in the charts on the next page Q1 Lag Q VARh Delivered Q VARh Received P Wh Delivered P Wh Received Q3 Lag Q2 Lead Q4 Lead Q1 Lag Q VARh Received Q VARh Delivered P Wh Received P Wh Delivered Q3 Lag Q2 Lead Q4 Lead IEEE IEC mode View as Load IEEE IEC mode View as Generator Q1 Lag Q VARh Delivered Q VARh Received P Wh Delivered P Wh Received Q3 Lag Q2 Lead Q4 Lead Q...

Страница 99: ...ions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Q1 Lag Q VARh Received Q VARh Delivered P Wh Received P Wh Delivered Q3 Lead Q2 Lag Q4 Lead Q1 Lag Q VARh Received Q VARh Delivered P Wh Delivered P Wh Received Q3 Lead Q2 Lag Q4 Lead Legacy mode View as Load Legacy mode View as Generator ...

Страница 100: ...caling factor for the display See the figure below Enter the scaling factor you want in the Current Scale field This field is multiplied by the CT Multiplier set in the CT PT Ratios and System Hookup screen to arrive at the Primary Full Scale Make sure you set the CT multiplier correctly Enable Fixed Scale for Voltage Display To enter a scaling factor for the Voltage display click the checkbox nex...

Страница 101: ...rgy Power Scaling and Averaging The screen fields and acceptable entries are as follows Energy Settings Energy Digits 5 6 7 8 Energy Decimal Places 0 6 Energy Scale unit kilo K Mega M Example a reading for Digits 8 Decimals 3 Scale K would be formatted as 00123 456 k Power Settings Power Scale Auto unit kilo K Mega M Apparent Power VA Calculation Method Arithmetic Sum Vector Sum Demand Averaging T...

Страница 102: ...t is the product of the values entered in the Sub Interval and Number of Subintervals fields NOTE You will only see the Number of Subintervals and Interval Window fields if you select Rolling Demand System Settings From this screen you can do the following Enable or disable password for Reset reset max min Energy settings Energy accumulators and the individual logs and or Configuration Device prof...

Страница 103: ... You must set up a password before enabling Password protection Click the Change button next to Change Password if you have not already set up a password Change the Password click the Change button You will see the Enter the New Password screen shown below 1 Type in the new password 0 9999 2 Retype the password 3 Click Change The new password is saved and the meter restarts NOTE If Password protec...

Страница 104: ... of limit condition occurs Once they are configured you can view the out of Limits or Alarm conditions in the Limits log or Limits polling screen You can also use Limits to trigger relays See the Communicator EXTTM 4 0 and MeterManager EXT Software User Manual for details The current settings for Limits are shown in the screen You can set and configure up to eight Limits for the Shark 200 meter To...

Страница 105: ...turn Hysteresis the point at which the reading goes back within limit see figure below Examples Above Setpoint 110 Below Setpoint 90 Out of Limit above 132 V Out of Limit below 108 V Above Return Hysteresis 105 Below Return Hysteresis 95 Stay out of Limit until below 126 V Stay out of Limit until above 114 V Primary Fields These fields are display only They show what the setpoint and return hyster...

Страница 106: ... is greater than the Above Setpoint the Above Limit is Disabled if the Below Return Hysteresis is less than the Below Setpoint the Below Limit is Disabled You may want to use this feature to disable either Above or Below Limit conditions for a reading Time Settings Use this setting to enable or disable Daylight Savings Time for the meter to set the beginning and ending times for Daylight Savings T...

Страница 107: ...on Line Sync for clock synchronization Line Sync synchronizes the clock to the AC frequency This a very common syn chronizing method Use these fields to set up NTP clock synchronization 1 Time Zone Zone Descriptor Select the hour and minute of your time zone in relation to Greenwich Mean Time For example if your time zone is Eastern Stan dard time you would select 5 from the pull down Hour menu an...

Страница 108: ...down menu IMPORTANT When you finish making changes to the Device Profile click Update Device to send the new Profile settings to the meter NOTE Refer to Chapter 8 of the Communicator EXTTM 4 0 and MeterManager EXT Software User Manual for additional instructions on configuring the Shark 200 meter settings including Transformer and Line Loss Compensation CT and PT Compensation Option card configura...

Страница 109: ...r Face Elements Figure 6 1 Face Plate with Elements The meter face features the following elements Reading type indicator e g Max Parameter designator e g Volts L N Watt hour test pulse Energy pulse output to test accuracy Scaling factor Kilo or Mega multiplier of displayed readings of Load bar Graphic Display of Amps as of the load see 6 3 Understanding the of Load Bar on page 6 16 for additional...

Страница 110: ...meter face has Menu Enter Down and Right buttons which let you perform the following functions View meter information Enter display modes Configure parameters may be Password protected Perform resets may be Password protected Perform LED Checks Change settings View parameter values Scroll parameter values View Limit states 0 659 0000 A B C MENU ENTER MAX MIN LM1 LM2 THD PRG VOLTS L N VOLTS L L AMP...

Страница 111: ...See Appendix A Shark 200 Meter Navigation Maps on page A 1 for the display s Navigation maps The meter can also be configured using software see Chapter 5 Communication Installation on page 5 1 and the Communicator EXTTM 4 0 and MeterManager EXT Software User Manual for instructions 6 2 1 Understanding Startup and Default Displays Upon powering up the meter displays a sequence of screens Lamp Test...

Страница 112: ... Press the Menu button The Main Menu screen appears The Reset Demand mode rStd appears in the A window Use the Down button to scroll causing the Reset Energy rStE Configuration CFG Operating OPr and Information InFo modes to move to the A window The mode that is currently flashing in the A window is the Active mode which means it is the mode that can be configured For example Press Down Twice CFG ...

Страница 113: ...f you press the Enter button again the Main Menu appears with the next mode in the A window The Down button does not affect this screen If you press the Right button the Reset Demand YES or Reset Energy YES screen appears Press Enter to per form a reset NOTE If Password protection is enabled for reset you must enter the four digit password before you can reset the meter See Chapter 5 Communication...

Страница 114: ...9 for the flashing dash When the correct number appears for that dash use the Right button to move to the next dash Example The left screen below shows four dashes The right screen shows the display after the first two digits of the password have been entered 2 When all 4 digits of the password have been selected press the Enter button If you are in Reset mode and you enter the correct password rS...

Страница 115: ...rameters screen appears 4 Press the Down button to scroll through the configuration parameters Scroll SCrL CT PT Connection Cnct and Port The parameter currently Active i e configurable flashes in the A window 5 Press the Enter button to access the Setting screen for the currently active param eter NOTE You can use the Enter button to scroll through all of the configuration parameters and their Se...

Страница 116: ...n appears See 6 2 4 Entering a Password on page 6 6 for instructions on entering a password 7 Once you have entered the new setting press the Menu button twice 8 The Store ALL YES screen appears You can either Press the Enter button to save the new setting Press the Right button to access the Store ALL no screen then press the Enter button to cancel the Save 9 If you have saved the settings the St...

Страница 117: ...abled by the installed V SwitchTM key see 2 1 3 V SwitchTM Key Tech nology on page 2 8 To enable or disable auto scrolling 1 Press the Enter button when SCrl is in the A window The Scroll YES screen appears 2 Press either the Right or Down button if you want to access the Scroll no screen To return to the Scroll YES screen press either button 3 Press the Enter button on either the Scroll YES scree...

Страница 118: ...tory and cannot be changed a To change the value for the CT numerator From the Ct n screen Use the Down button to select the number value for a digit Use the Right button to move to the next digit b To change the value for CT scaling From the Ct S screen use the Right button or the Down button to choose the scaling you want The Ct S setting can be 1 10 or 100 NOTE If you are prompted to enter a pa...

Страница 119: ...utton when Pt is in the A window The PT n screen appears You can either Change the value for the PT numerator Access one of the other PT screens by pressing the Enter button press Enter once to access the Pt d screen twice to access the Pt S screen a To change the value for the PT numerator or denominator From the Pt n or Pt d screen Use the Down button to select the number value for a digit Use t...

Страница 120: ...ttings 277 277 Volts Pt n value is 277 Pt d value is 277 Pt S value is 1 14 400 120 Volts Pt n value is 1440 Pt d value is 120 Pt S value is 10 138 000 69 Volts Pt n value is 1380 Pt d value is 69 Pt S value is 100 345 000 115 Volts Pt n value is 3450 Pt d value is 115 Pt S value is 100 345 000 69 Volts Pt n value is 345 Pt d value is 69 Pt S value is 1000 NOTE Pt n and Pt S are dictated by primar...

Страница 121: ...r a password refer to Section 6 2 4 for instruc tions on doing so 3 When you have made your selection press the Menu button twice 4 The STOR ALL YES screen appears Press Enter to save the setting Use buttons to select configuration 6 2 5 5 Configuring Communication Port Setting Port configuration consists of Address a three digit number Baud Rate 9600 19200 38400 or 57600 and Protocol DNP 3 0 Modb...

Страница 122: ... enter the address through software settings Refer to Section 5 2 2 b To select the Baud Rate From the bAUd screen use the Right button or the Down button to select the setting you want c To select the Protocol From the Prot screen press the Right button or the Down button to select the setting you want NOTE If you are prompted to enter a password refer to Section 6 2 4 for instruc tions on doing ...

Страница 123: ...de Sheet 2 in Appendix A shows the Operating mode Navigation map NOTE Readings or groups of readings are skipped if not applicable to the meter type or hookup or if they are disabled in the programmable settings OPERATING MODE PARAMETERS POSSIBLE READINGS Voltage L to Neutral Display voltage line to neutral voltage line to neutral max voltage line to neutral min voltage line to neutral THD V3 and ...

Страница 124: ...gments light according to the load as shown in the table below When the load is over 120 of Full Load all segments flash On 1 5 secs and Off 0 5 secs The of Load bar can be programmed through Communicator EXTTM software see Chapter 8 in the Communicator EXTTM 4 0 and MeterManager EXT Software User Manual for instructions Segments Load Full Load none no load 1 1 1 2 15 1 3 30 1 4 45 1 5 60 1 6 72 1...

Страница 125: ...rformance and calibration power providers use field test standards to ensure that the unit s energy measurements are correct Since the Shark 200 meter is a traceable revenue meter it contains a utility grade test pulse that can be used to gate an accuracy standard This is an essential feature required of all billing grade meters Refer to Figure 6 5 for an example of how this process works Refer to...

Страница 126: ... or a Watt hour Engineering Company Three Phase Automated Test System NOTE Watt hour Standards offer pulse inputs that take in the CPU s test pulses The accuracy is computed by ratio metrically comparing the period of the meter s pulse to the period of the Standard s internal pulse You must program the test pulse value Kh into the Standard for the results to be accurate Input Voltage Level Class 1...

Страница 127: ...e by placing the photo detector over the 1 LED 5 Connect the three phase current inputs to the current terminals associated with the test pulse LED being monitored There must be no other current inputs connected 6 Energize the Standard and the Shark 200 meter To assure accuracy both must be on for a minimum of 30 minutes 7 Energize the sources and wait for the outputs to stabilize before starting ...

Страница 128: ... the Shark 200 Meter Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 129: ...O expandability Using the two universal Option Card slots the unit can be easily configured to accept new I O Option cards even after installation without your needing to remove the meter The Shark 200 meter auto detects any installed Option cards Up to 2 cards of any type outlined in this chapter can be used per meter Figure 7 1 Shark 200 Meter Back Showing Option Card Slots and I O Card 10 100 B...

Страница 130: ...m of the Option Card slot covers 2 There is a plastic track on the top and the bottom of the slot The Option card fits into this track Figure 7 2 Detail of Guide Track For safety remove ALL these connections before installing Option cards GND L L Vref Va Vb Vc 3 Slide the card inside the plastic track and insert it into the slot You will hear a click when the card is fully inserted Be careful it i...

Страница 131: ...id Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions For proper card fit and to avoid damaging the unit insert components in the following order a Option card 1 b Option card 2 c Detachable terminal block 1 d Detachable terminal block 2 e Communication connection for Port 2 ...

Страница 132: ... following sections describe the available Option cards 7 4 1mA Output Card 1mAOS The 1mA card transmits a standardized bi directional 0 1mA signal This signal is linearly proportional to real time quantities measured by the Shark 200 meter The outputs are electrically isolated from the main unit 7 4 1 Specifications The technical specifications at 25 C at 5 k load are as follows Number of outputs...

Страница 133: ...mmunity Interference EN61000 4 2 Weight 1 6 oz Dimensions inch W x H x L 0 72 x 2 68 x 3 26 External connection AWG 12 26 0 29 3 31 mm2 5 pin 0 200 pluggable terminal block 7 4 2 Default Configuration The Shark 200 meter automatically recognizes the installed Option card during power up If you have not programmed a configuration for the card the unit defaults to the following outputs Channel 1 Wat...

Страница 134: ...The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 7 4 3 Wiring Diagram Figure 7 3 4 Channel 0 1 mA Output Card 2 C 4 3 1 Channel 0 1 mA Analog Outputs out RL Common C I Outputs 1 2 3 4 ...

Страница 135: ...ts are electrically isolated from the main unit 7 5 1 Specifications The technical specifications at 25 C at 500 load are as follows Number of outputs 4 single ended Power consumption 1 W internal Signal output range 0 to 24 mA Max load impedance 850 24 V DC Hardware resolution 12 bits Effective resolution 14 bits with 2 5 kHz PWM Update rate per channel 100 ms Output accuracy 0 1 of output range ...

Страница 136: ...ions inch W x H x L 0 72 x 2 68 x 3 26 External connection AWG 12 26 0 129 3 31 mm2 5 pin 0 200 pluggable terminal block 7 5 2 Default Configuration The Shark 200 meter automatically recognizes the installed Option card during power up If you have not programmed a configuration for the card the unit defaults to the following outputs Channel 1 Watts 1800 Watts 20 mA Watts 1800 Watts 4 mA 0 Watts 12...

Страница 137: ...Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 7 5 3 Wiring Diagram Figure 7 4 4 Channel 0 20 mA Output Card 2 C 4 3 1 Channel 4 20 mA Analog Outputs V out RL Common C I Loop Outputs 1 2 3 4 ...

Страница 138: ...Specifications The technical specifications at 25 C are as follows Power consumption 0 320 W internal Relay outputs Number of outputs 2 Contact type Changeover SPDT Relay type Mechanically latching Switching voltage AC 250 V DC 30 V Switching power 1250 VA 150 W Switching current 5 A Switching rate max 10 s Mechanical life 5 x 107 switching operations Electrical life 105 switching operations at ra...

Страница 139: ...n Maximum input voltage DC 150 V diode protected against polarity reversal Filtering De bouncing with 50ms delay time Detection scan rate 100 ms Isolation AC 2500 V system to inputs The general specifications are as follows Operating temperature 20 to 70 C Storage temperature 40 to 80 C Relative air humidity Maximum 95 non condensing EMC Immunity Interference EN61000 4 2 Weight 1 5 oz Dimensions i...

Страница 140: ...s Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 7 6 2 Wiring Diagram Figure 7 5 Relay Contact 2 Status Input 2 Card 1 2 T A T NC C NC C I2 I1 S S U NO C NO Status Inputs Relay Outputs NO C NC RELAY CONTACTS Loop Inputs I1 I2 V Common C For wet contacts Inputs I1 I2 Common C For dry contacts ...

Страница 141: ...olated from the inputs and from the main unit 7 7 1 Specifications The technical specifications at 25 C are as follows Power consumption 0 420 W internal Relay outputs Number of outputs 4 Contact type Closing SPST NO Relay type Solid state Peak switching voltage DC 350 V Continuous load current 120 mA Peak load current 350 mA for 10 ms On resistance max 35 Leakage current 1µA 350 V Switching Rate ...

Страница 142: ...s follows Operating Temperature 20 to 70 C Storage Temperature 40 to 80 C Relative air humidity Maximum 95 non condensing EMC Immunity Interference EN61000 4 2 Weight 1 3 oz Dimensions inch W x H x L 0 72 x 2 68 x 3 26 External Connection AWG 12 26 0 129 3 31 mm2 13 pin 3 5 mm pluggable terminal block 7 7 2 Default Configuration The Shark 200 meter automatically recognizes the installed Option car...

Страница 143: ...ower Monitoring and Smart Grid Solutions Pulse Channel 3 1 8 VAR hours per pulse Pulse Channel 4 1 8 VAR hours per pulse 7 7 3 Wiring Diagram Figure 7 6 Pulse Output 4 Status Input 4 Card C C C C I1 I4 I3 C I2 3 4 S T A S NO NO NO 2 1 T U NO Status Inputs Pulse Outputs Loop Inputs I1 I2 V Common C For wet contacts Inputs I1 I2 Common C For dry contacts NO C NC RELAY CONTACTS ...

Страница 144: ...ations The technical specifications at 25 C are as follows Number of Ports 1 Power consumption 0 160 W internal Fiber connection ST FOST or Versatile Link FOVP as per order Optical fiber details Multimode ST FOSTS 50 125 µm 62 5 125 µm 100 140 µm 200 µm Hard Clad Silica HCS Versatile Link FOVPS 200 µm Hard Clad Silica HCS 1 mm Plastic Optical Fiber POF Baud rate Up to 57 6 k b s pre programmed in ...

Страница 145: ...onnector Echo Switch RX TX TX RX ON OFF ECHO Fiber Daisy Chain Fiber Optic Port Versatile Link type connector Echo Switch 2 RX TX RX N 1 TX Meter Meter Meter TX OFF FF ON RX TX ON RX TX OFF FF Host st Meter ON TX RX OFF FF OFF FF RX ON Host st ECH CHO ON ECH CHO For a Daisy Chained Conn onnec ection on set ECH CHO t to ON For a Point to Point Conn onnec ection on set ECH CHO to OFF FF ECH CHO ON E...

Страница 146: ... the Communicator EXTTM 4 0 and MeterManager EXT Software User Manual for instructions on performing Network configuration 7 9 1 Specifications The technical specifications at 25 C are as follows Number of Ports 1 Power consumption 2 1 W internal Baud rate 10 100 Mbit Diagnostic feature Status LEDs for LINK and ACTIVE Number of simultaneous Modbus connections 12 The general specifications are as f...

Страница 147: ...d a configuration for the card the unit defaults to the following IP Address 10 0 0 2 Subnet Mask 255 255 255 0 Default Gateway 0 0 0 0 7 9 3 Wiring Diagram Figure 7 8 10 100BaseT Ethernet Card IMPORTANT The INP100S uses an auto detecting circuit that automatically switches the transmit and receive in order to properly align communication Because of this when you are communicating directly to a me...

Страница 148: ...Protocol Ethernet Network Card INP300S on page E 1 for details and instructions 7 10 1 Specifications The technical specifications at 25 C are as follows Number of Ports 1 Power consumption 2 1 W internal Baud rate 10 100 Mbit Diagnostic feature Status LEDs for LINK and ACTIVE Number of simultaneous Modbus connections 12 Number of simultaneous MMS clients 5 The general specifications are as follow...

Страница 149: ...ion for the card the unit defaults to the following IP Address 10 0 0 2 Subnet Mask 255 255 255 0 Default Gateway 0 0 0 0 7 10 3 Wiring Diagram Figure 7 9 IEC61850 Protocol Ethernet Network Card IMPORTANT The INP300S uses an auto detecting circuit that automatically switches the transmit and receive in order to properly align communication Because of this when you are communicating directly to a m...

Страница 150: ... the I O Option Cards Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 151: ...00 meter you gain the capability of commu nicating over the Ethernet using EIG s Rapid Response technology 8 2 Hardware Connection The INP100S card fits into either of the two Option Card slots in the back of the Shark 200 meter Refer to Chapter 7 for card installation instructions Use a standard RJ45 10 100BaseT cable to connect to the Ethernet card The INP100S card auto detects cable type and wi...

Страница 152: ...zation see 8 4 3 NTP Time Server Synchronization on page 8 24 Alarm and notification emails with meter readings see 8 4 2 3 Email Notification on page 8 14 Data Push of meter readings to a cloud server using the JSON structure see 8 4 2 4 Data Push on page 8 20 Enhanced security with the Exclusive Client feature which lets you Whitelist an IP address or MAC address When that address is used to con...

Страница 153: ... Ethernet by almost all browsers The Shark Series webpages allow you to see the following information for the Shark 200 meter Voltage and current readings Power and Energy readings Power quality information General meter information You can also upgrade the Ethernet Network card s firmware Reset the Ethernet card configure email notification and set up Data Push from the meter s Infor mation webpa...

Страница 154: ...rk Card Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 3 You will see the Shark Series Introduction web page shown below ...

Страница 155: ...geTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 4 To view Voltage and current readings click Volts Amps on the left side of the web page You will see the webpage shown below ...

Страница 156: ...ugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 5 To view power and Energy readings click Power Energy on the left side of the webpage You will see the webpage shown below ...

Страница 157: ...der In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 6 To view power quality information click Power Quality on the left side of the webpage You will see the webpage shown below Graph Icon Phase Angles Icon ...

Страница 158: ...er Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions a To view a graphical representation of the Voltage and current magnitudes click the Graph icon in the corner of the Voltage Current box You will see the webpage shown below ...

Страница 159: ... Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions b To view a graphical representation of the phase angles click the Phase Angles icon in the corner of the Phase Angles box You will see the web page shown below 7 Click Power Quality on the left side of the webpage to return to the previous webpage ...

Страница 160: ...isplayed in the Run Ver field of this webpage determines the default password for Network card upgrading and resetting Any special characters i e any of the following characters used in the meter name or any other designator string in the meter are displayed as _ underscore in the webpage In addition to information about the meter and its firmware this webpage gives you access to the following fun...

Страница 161: ...0 NOTE The Shark 270 meter s Device Profile must be set up before configuring keep alive or email settings in the Network card See Chapter 8 in the Communicator EXTTM 4 0 and MeterManager EXT Software User Manual for instructions 8 4 2 1 Upgrading the Ethernet Card s Firmware From one of the Shark 200 meter s webpages 1 Click Information on the left side of the webpage 2 Click Upgrade Network Card...

Страница 162: ...de file the card will not work 4 Enter the safety code supplied with the Upgrade file and the password the default is n3tUp 0Ad for firmware runtime version 3 35 or higher and eignet2009 for earlier firmware runtime versions See the note on page 8 9 5 Click Submit The upgrade starts immediately it may take several minutes to complete Once the upgrade is complete you will see a confirmation message...

Страница 163: ...f the Shark 200 meter s webpages 1 Click Information on the left side of the webpage 2 Click Reset Network Card bottom box on the right You will see the webpage shown below 3 Enter the Reset password the default is adminR35et for firmware runtime version 3 35 or later and r2d2andc3po for earlier firmware runtime versions See the note on page 8 9 4 Click Reset NOTE As a result of the reset the comm...

Страница 164: ...ith either type of email The Firmware version of the Ethernet card must be 337 or higher for this feature to be available See page 8 9 for information on finding the firmware version From one of the Shark 200 meter s webpages 1 Click Information on the left side of the webpage 2 Click Email Notification on the bottom right of the webpage The first screen you will see is Email Server shown below 3 ...

Страница 165: ... Server port Usually this is 25 but check with your system administra tor in case you are using a different port c If your email server requires authorization click the checkbox next to Yes and enter the Username and Password d Click the Next button 4 The next screen you will see is Watched Events This screen lets you select the conditions that will cause an alarm or notification email to be sent ...

Страница 166: ... button next to the condition The button will turn red Note that when you designate a condition as an alarm an alarm email will be sent out within a minute after the condition occurs and a notification email will also be sent out at the next notification period If you have not set up any notification emails then only the alarm email will be sent There are some conditions which cannot be set as ala...

Страница 167: ...tep 6 a Enter the email address of the person sending the email in the From field b Enter the email subject line in the Subject field the default is Alarm Email c Enter the email address of the person receiving the email in the To field only one email address can be entered d Enter the email address of anyone you want to receive a copy of the email in the CC field only one email address can be ent...

Страница 168: ... a csv file that will be attached to the email g Click the Next button 6 The next screen you will see is Notification Email Data This screen lets you designate to whom the periodic notification email will be sent any data you want sent with the email and the format the data should be in You will also set up the notification period which is the amount of time between peri odic notification emails I...

Страница 169: ...of the email and in a csv file that will be attached to the email g Enter the interval you want between notification emails in minutes in the Notifi cation Period field For example to set up notification emails every 15 minutes enter 15 in this field Any notification conditions that occur in the interval will be saved and sent in the next notification email Valid entries is in this field are betwe...

Страница 170: ...s the customer the ability to access all of their buildings usage data including meter readings in one place JSON is a free open standard format that is widely used in asynchronous browser server communication It uses text to transmit data objects made up of attribute value pairs and array data types The specific meter readings and the frequency of the data push are configured through the card s w...

Страница 171: ...isabled it is in a suspended mode no data is being pushed but settings can still be changed 4 Enter The url of the server this is the address the Lucid client will connect to It can be either a url or an IP address This information will be supplied to the customer by Lucid Note that Lucid Push in the INP100S implements http protocol not https if the supplied address uses https contact Lucid for in...

Страница 172: ...ay webpage enter Enter the Gateway URL of the data service to connect with this will be supplied by the cloud service The Gateway ID Path is the unique identifier for this meter It is supplied by the meter and cannot be changed the field is display only Enter the minute interval for sending the catalog which tells the server which readings will be sent to the server Note that since the catalog is ...

Страница 173: ...y 300 seconds Avoid using very small values for the interval in order to reduce the network traffic For Billing applications set this values between 300 and 900 seconds 5 to 15 min utes 8 Click Next You will see the webpage shown below 9 In the Data Points webpage you select the meter readings you want to be pushed sent to the cloud server You can select up to 15 values The selected data points ha...

Страница 174: ...ible to version 3 After the meter boots up it may take up to 20 seconds for the first time synchronization request to be made 8 4 4 Modbus and DNP over Ethernet The INP100S card enables up to 12 simultaneous sockets of Modbus TCP IP and up to 5 simultaneous sockets of DNP 3 0 over Ethernet This means that multiple users can poll the meter using Modbus and or DNP at the same time For configuration ...

Страница 175: ...Alive setting screen key the following into your web browser s address bar http xx xx xx xx sys setup_keepalive_ssi htm where xx xx xx xx is your INP100S card s IP address You will see the screen shown below You can click on the On button to turn off the keep alive feature for a protocol The button will turn red and say Off For each protocol you can enter a keep alive time and interval in seconds ...

Страница 176: ...bmit to implement your entries click Restore to change back to previous settings click Default to revert to the default system settings IMPORTANT You should not make changes to the settings unless you are sure of what you are doing since even small changes to the values on this screen can render the network connection unstable EIG is not responsible for instability of the network link when values ...

Страница 177: ...locate available system resources between the three logs to increase or decrease the size of the individual historical logs See Chapter 8 Configuring Historical Logs and Allocating Historical Log Sectors sections and Chapter 19 Viewing Historical Logs and Snapshots section of the Communicator EXTTM 4 0 and MeterManager EXT Software User Manual for additional information and instructions Limit Alar...

Страница 178: ...eads Programmable settings changes Critical data repairs A Shark 200 meter equipped with V5 and above has additional memory for data logging V5 gives the meter 3 Megabytes of Flash memory and V6 gives the meter 4 MegaBytes of Flash memory These meters also have waveform recording capabilities and the following additional log Waveform log This event triggered log records a waveform when a user prog...

Страница 179: ...mmed using software see Chapter 5 Communication Installation on page 5 1 and the Communicator EXTTM 4 0 and MeterManager EXT Software User Manual A 2 Navigation Maps Sheets 1 to 4 The Shark 200 meter s Navigation maps begin on the next page The maps show in detail how to move from one screen to another and from one Display mode to another using the buttons on the face of the meter All Display mode...

Страница 180: ...dicates acceptance of the current screen and advances to the next one Navigation and edit buttons No digits or legends are blinking On a menu down advances to the next menu selection right does nothing In a grid of screens down advances to the next row right advances to the next column Rows columns and menus all navigate circularly A digit or legend is blinking to indicate that it is eligible for ...

Страница 181: ...4 Watt Hour Q23 Watt Hour Net RIGHT RIGHT RIGHT VAR Hour Q12 VAR Hour Q34 VAR Hour Net RIGHT RIGHT DOWN2 from any Voltage Line to Line screen DOWN2 from any Power screen DOWN2 from any Apparent Power Frequency screen DOWN2 from any Active Energy screen DOWN2 to Main Menu Watt Hour Total RIGHT VAR Hour Total RIGHT RIGHT Watt Max Q23 VAR Max Q34 PF Max Q23 Watt Min Q23 VAR Min Q34 PF Min Q23 RIGHT R...

Страница 182: ...git blink increment blinking digit from MAIN MENU RSTD selected MENU from any reset mode screen RESET PASSWORD FAIL PASS FAIL Reset Mode Screens no ENTER 2 sec to previous operating mode screen to Main Menu see sheet 2 RESET ENERGY NO RST ENER no blinking is password required RIGHT RIGHT ENTER RESET ENERGY YES RST ENER yes blinking from MAIN MENU RSTE selected no reset all max min values RESET ENE...

Страница 183: ...ration MENU Configuration Mode Screens SAVE CONFIRM STOR ALL DONE 2 sec reboot ENTER ENTER CT MULTIPLIER EDIT CT S 1 or 10 or 100 choice blinking if edit CT NUMERATOR EDIT CT N one blinking if edit ENTER ENTER ENTER ENTER ENTER ENTER ENTER ENTER ENTER ENTER ENTER DOWN RIGHT DOWN RIGHT DOWN or RIGHT DOWN or RIGHT RIGHT DOWN or RIGHT3 ENTER DOWN or RIGHT DOWN or RIGHT RIGHT DOWN or RIGHT ENTER2 ENTE...

Страница 184: ...Doc E149701 A 6 A Shark 200 Meter Navigation Maps Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 185: ...Fixed Data Section Registers 1 47 details the meter s Fixed Information Meter Data Section Registers 1000 12031 details the meter s Readings including Primary Readings Energy Block Demand Block Phase Angle Block Status Block THD Block Minimum and Maximum in Regular and Time Stamp Blocks Option Card Blocks and Accumulators Operating mode readings are described in Section 6 2 6 Commands Section Regi...

Страница 186: ...at The formula to interpret a Floating Point Value is 1sign x 2 exponent 127 x 1 mantissa 0x0C4E11DB9 1sign x 2 137 127 x 1 1000010001110110111001 1 x 210 x 1 75871956 1800 929 Formula Explanation C4E11DB9 hex 11000100 11100001 00011101 10111001 binary Register 0 1 Byte 0 1 0 1 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Meaning s e e e e e e e e m m m m m m m m m m m m m m...

Страница 187: ...ponent the whole number before the decimal point Mantissa the positive fraction after the decimal point B 5 Retrieving Logs Using the Shark 200 Meter s Modbus Map This section describes the log interface system of the Shark 200 meter from a programming point of view It is intended for programmers implementing indepen dent drivers for log retrieval from the meter It describes the meaning of the met...

Страница 188: ...m Event log is used to store events which happen in and to the meter Events include Startup Reset Commands Log Retrievals etc The System Event Log Record takes 20 bytes 14 bytes of which are available when the log is retrieved NOTE The complete Systems Events table is shown in Section B 5 5 step 1 on page B 30 2 Alarm Log 1 The Alarm Log records the states of the 8 Limits programmed in the meter W...

Страница 189: ... 1 for details on programming and interpreting the log 4 Historical Log 2 3 Same as Historical Log 1 5 Historical Log 3 4 Same as Historical Log 1 6 I O Change Log 5 The I O Change Log records changes in the input and out put of Digital I O Type Option Cards Relay and Pulse I O Change Log tables Card Change Flags Byte 0 1 2 3 4 5 6 7 8 9 Value timestamp direction limit Value Bit 0 1 2 3 4 5 6 7 Va...

Страница 190: ...sters involved in retrieving and interpreting a Shark 200 Meter Log Other sections refer to certain values contained in this sec tion See the corresponding value in this section for details NOTES Register is the Modbus Register Address in 0 based Hexadecimal notation To convert it to 1 based decimal notation convert from hex16 to decimal10 and add 1 For example 0x03E7 1000 Size is the number of Mo...

Страница 191: ... is described here All register addresses in this section are given as the Historical Log 1 address 0x7917 Each Historical Log Block is composed of 3 sections The header the list of registers to log and the list of item descriptors Header Registers 0x7917 0x7918 Size 2 registers Registers The number of registers to log in the record The size of the record in memory is 12 Registers x 2 The size dur...

Страница 192: ...rograms that expect a fixed interval Register List Registers 0x7919 0x798D Size 1 register per list item 117 list items The Register List controls what Modbus Registers are recorded in each record of the Historical Log Since many items such as Voltage Energy etc take up more than 1 register multiple registers need to be listed to record those items For example Registers 0x03E7 and 0x03E8 are progr...

Страница 193: ...or byte with a value in the range of 0 14 If this value is 0xFF the descriptor should be ignored 0 ASCII An ASCII string or byte array 1 Bitmap A collection of bit flags 2 Signed Integer A 2 s Complement integer 3 Float An IEEE floating point 4 Energy Special Signed Integer where the value is adjusted by the energy settings in the meter s Programmable Settings 5 Unsigned Integer 6 Signed Integer 0...

Страница 194: ...8 0x1234 Signed Int 2 byte NOTE The sum of all descriptor sizes must equal the number of bytes in the data portion of the Historical Log record Log Status Block The Log Status Block describes the current status of the log in question There is one header block for each of the logs Each log s header has the following base address Log Base Address Alarms 0xC737 System 0xC747 Historical 1 0xC757 Histo...

Страница 195: ... a dummy record filled with all 0xFF s When the log is filled and rolls over this record is overwritten Record Size The number of bytes in this record including the timestamp The data type is an unsigned integer in the range of 14 242 Log Availability A flag indicating if the log is available for retrieval or if it is in use by another port 0 Log Available for retrieval 1 In use by COM1 IrDA 2 In ...

Страница 196: ...e retrieved by one port at a time Only one log at a time can be retrieved First Timestamp Timestamp of the oldest record Last Timestamp Timestamp of the newest record Log Retrieval Block The Log Retrieval Block is the main interface for retrieving logs It is comprised of 2 parts the header and the window The header is used to program the particular data the meter presents when a log window is requ...

Страница 197: ...og to be accessed and other settings concerning the log retrieval Registers 0xC34F 0xC350 Size 2 registers Log Number The log to be retrieved Write this value to set which log is being retrieved 0 System Events 1 Alarms 2 Historical Log 1 3 Historical Log 2 4 Historical Log 3 5 I O Change Log 10 PQ Event Log 11 Waveform Log Bytes Value Type Format Description Bytes 0 1 Log Number Enable Scope UINT...

Страница 198: ...yte timestamp at the beginning then N data bytes for the record data Timestamp 1 The record only contains the 6 byte timestamp This is most useful to determine a range of available data for non interval based logs such as Alarms and System Events Image 2 The full record as it is stored in memory Contains a 2 byte check sum 4 byte sequence number 6 byte timestamp and then N data bytes for the recor...

Страница 199: ...bles auto increment 1 No Repeat count each request will only get 1 window 2 8 2 8 windows returned for each Function Code 0x23 request Log Retrieval Window Block The Log Retrieval Window block is used to program the data you want to retrieve from the log It also provides the interface used to retrieve that data Registers 0xC351 0xC3CD Size 125 registers Window Status The status of the current wind...

Страница 200: ...eve the window repeatedly until all records have been retrieved NOTES When auto increment is enabled this value will automatically increment so that the window will page through the records increasing by RecordsPerWindow each time that the last register in the window is read When auto increment is not enabled this value must be written to manually for each window to be retrieved Log Retrieval Data...

Страница 201: ... Modbus Function Code 0x23 QUERY Field Name Example Hex Slave Address 01 Function 23 Starting Address Hi C3 Starting Address Lo 51 Points Hi 00 Points Lo 7D Repeat Count 04 RESPONSE Field Name Example Hex Slave Address 01 Function 23 Bytes Hi 03 Bytes Lo E0 Data Function Code 0x23 is a user defined Modbus function code which has a format simi lar to Function Code 0x03 except for the inclusion of a...

Страница 202: ...tain the index of that window In the Shark 200 meter repeat counts are limited to 8 times for Modbus RTU and 4 times for Modbus ASCII The response for Function Code 0x23 is the same as for Function Code 0x03 with the data blocks in sequence IMPORTANT Before using function code 0x23 always check to see if the current connection supports it Some relay devices do not support user defined function cod...

Страница 203: ...rite log to engage to Log Number 1 to Enable and the desired mode to Scope default 0 Normal 0xC34F 1 reg This is best done as a single register write This step will latch the first oldest record to index 0 and lock the log so that only this port can retrieve the log until it is disengaged c Verify the log is engaged read the contents of the specific logs status block 0xC737 16 reg again to see if ...

Страница 204: ...ndow returned Space in the window after the last specified record RecordSize x Record PerWindow is padded with 0xFF and can be safely discarded b Verify that the record index incremented by Records Per Window The record index of the retrieved window is the index of the first record in the window This value will increase by Records Per Window each time the window is read so it should be 0 N N x 2 N...

Страница 205: ...Disengage the log write the Log Number of log being disengaged to the Log Index and 0 to the Enable bit 0xC34F 1 reg B 5 4 4 Log Retrieval Example The following example illustrates a log retrieval session The example makes the following assumptions Log Retrieved is Historical Log 1 Log Index 2 Auto Incrementing is used Function Code 0x23 is not used Repeat Count of 1 The Log contains Volts AN Volt...

Страница 206: ... 0000 060717101511 060718101511 0000000000000000 Data Max Records 0x100 256 records maximum Num Records 0x64 100 records currently logged Record Size 0x12 18 bytes per record Log Availability 0x00 0 not in use available for retrieval First Timestamp 0x060717101511 July 23 2006 16 21 17 Last Timestamp 0x060717101511 July 24 2006 16 21 17 NOTE This indicates that Historical Log 1 is available for re...

Страница 207: ...x 0 3 Read 0xC757 16 reg Availability is 0 Send 0103 C757 0010 Command Register Address 0xC757 Registers 16 Receive 010320 00000100 00000064 0012 0002 060717101511 060718101511 0000000000000000 Data Max Records 0x100 256 records maximum Num Records 0x64 100 records currently logged Record Size 0x12 18 bytes per record Log Availability 0x02 2 In use by COM2 RS485 the current port First Timestamp 0x...

Страница 208: ...nd the record is 18 bytes 246 18 13 66 which means that 13 records evenly fit into a single window This is 234 bytes which means later on we only need to read 234 bytes 117 registers of the window to retrieve the records of Repeats 1 We are using auto increment so not 0 but not function code 0x23 Window Status 0 ignore Record Index 0 start at the first record Receive 0110C3500003 command ok NOTES ...

Страница 209: ...FAAD1842FAA9A8 Data Window Status 0x00 the window is ready Index 0x00 0 The window starts with the 0 th record which is the oldest record Record 0 The next 18 bytes is the 0 th record filler Timestamp 0x060717101511 July 23 2006 16 21 17 Data This record is the filler record It is used by the meter so that there is never 0 records It should be ignored It can be identified by the data being all 0xF...

Страница 210: ...ta the timestamp is valid and the index is NOT 0 then the record is legitimate When the filler record is logged its timestamp may not be on the interval The next record taken will be on the next proper interval adjusted to the hour For example if the interval is 1 minute the first real record will be taken on the next minute no seconds If the interval is 15 minutes the next record will be taken at...

Страница 211: ...rrent Index by RecordsPerWindow NOTES This is the step that determines how much more of the log we need to retrieve On the first N passes Records Per Window should be 13 as computed in step 4 and the current index should be a multiple of that 0 13 26 This amount will decrease when we reach the end see step 10 If the current index is greater than or equal to the number of records in this case 100 t...

Страница 212: ...dex is 91 the 8 th window There are now 9 records available 100 91 so make Records per Window equal 9 11 Repeat steps 5 through 10 NOTES Go back to step 5 where a couple of values have changed Pass CurIndex FirstRecIndex RecPerWindow 0 0 0 13 1 13 13 13 2 26 26 13 3 39 39 13 4 52 52 13 5 65 65 13 6 78 78 13 7 91 91 9 8 100 At pass 8 since Current Index is equal to the number of records 100 log ret...

Страница 213: ...rid Solutions 13 Write 0x0000 0xC34F 1 reg disengage the log Send 0106 C34F 0000 Command Register Address 0xC34F Registers 1 Write Single Register Command Data Log Number 0 ignore Enable 0 Disengage log Scope 0 ignore Receive 0106C34F0000 echo NOTES This disengages the log allowing it to be retrieved by other COM ports The log will automatically disengage if no log retrieval action is taken for 5 ...

Страница 214: ... bytes each byte is an enumerated value Group Group of the event Event Event within a group Modifier Additional information about the event such as number of sectors or log number Channel The port of the Shark 200 meter that caused the event 0 Firmware 1 COM 1 IrDA 2 COM 2 RS485 3 COM 3 Option Card 1 4 COM 4 Option Card 2 7 User Face Plate Param 1 4 These are defined for each event see following t...

Страница 215: ... Meter Run Firmware Startup 1 slot 0 class ID card status 0xFF 0xFF Option Card Using Default Settings 1 Log Activity 1 log 1 4 0xFF 0xFF 0xFF 0xFF Reset 2 log 1 4 0xFF 0xFF 0xFF 0xFF Log Retrieval Begin 3 log 0 4 0xFF 0xFF 0xFF 0xFF Log Retrieval End 2 Clock Activity 1 0 1 4 0xFF 0xFF 0xFF 0xFF Clock Changed 2 0 0 0xFF 0xFF 0xFF 0xFF Daylight Time On 3 0 0 0xFF 0xFF 0xFF 0xFF Daylight Time Off 4 ...

Страница 216: ...d 5 Boot Activity 1 0 1 4 FW version Exit to Boot 6 Error Report ing Recovery 4 log 0 0xFF 0xFF 0xFF 0xFF Log Babbling Detected 5 log 0 records discarded time in seconds Babbling Log Periodic Summary 6 log 0 records discarded time in seconds Log Babbling End Detected 7 sector 0 error count stimulus 0xFF Flash Sector Error 8 0 0 0xFF 0xFF 0xFF 0xFF Flash Error Counters Reset 9 0 0 0xFF 0xFF 0xFF 0x...

Страница 217: ...ng when the error occurred 1 acquire sector 2 startup 3 empty sector 4 release sector 5 write data Flash error counters are reset to zero in the unlikely event that both copies in EEPROM are corrupted The flash job queue is flushed and log records are lost in the unlikely event that the queue runs out of space A babbling log is one that is saving records faster than the meter can handle long term ...

Страница 218: ...the Waveform log Logging of diagnostic records may be suppressed via a bit in programmable settings Alarm Record Size 10 bytes 16 bytes image Data The Alarm record data is 4 bytes and specifies which limit the event occurred on and the direction of the event going out of limit or coming back into limit Direction The direction of the alarm event whether this record indicates the limit going out or ...

Страница 219: ...etpoint also has a threshold hysteresis which is the value at which the limit returns into limit after the setpoint has been exceeded This prevents babbling limits which can be caused by the limit value fluttering over the setpoint causing it to go in and out of limit continuously Identifier The first modbus register of the value that is being watched by this limit While any modbus register is val...

Страница 220: ...f the Full Scale above which the limit will return into limit if it is out If this value is below the Below Setpoint this Below limit will be disabled Valid in the range of 200 0 to 200 0 Stored as an integer with 0 1 resolution Multiply by 10 to get the integer divide integer by 10 to get For example 94 9 949 NOTES The Full Scale is the nominal value for each of the different types of readings To...

Страница 221: ...System Events for Power Up events This also means that if a limit is out and it goes back in during the power off condition no into limit record will be recorded The worst value of the into limit record follows the above restrictions it only represents the values since power up Any values before the power up condition are lost Historical Log Record Size 6 2 x N bytes 12 2 x N bytes where N is the ...

Страница 222: ... a Digital Option Card the value will be 0 NOTES An I O Change log record will be taken for each Relay and Digital Input that has been configured in the Programmable Settings to record when its state changes When any one configured Relay or Digital Input changes the values of all Relays and Digital Inputs are recorded even if they are not so configured Byte 0 1 2 3 4 5 6 7 8 9 Value Timestamp Card...

Страница 223: ...he payload NOTE The waveform records must be in sequential order Verify that the record numbers are sequential and if they are not the retrieval of that capture must be restarted PQ Event Record Size 58 bytes Data See the first table in the PQ Event Log Retrieval section for detailed information about the data NOTE The not used section of the PQ Event record byte map is simply 0 Byte 0 1 2 3 4 5 6...

Страница 224: ...0 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 send 01 03 79 57 00 40 recv 01 03 80 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 0...

Страница 225: ... 00 00 00 00 00 00 00 00 00 00 00 00 00 00 03 E8 00 01 00 04 00 00 00 00 00 00 06 08 17 51 0C 00 00 19 00 2F 27 0F 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 03 E8 00 01 00 04 00 00 00 00 00 00 00 00 send 01 03 C3 51 00 40 Read first half of last window recv 01 03 80 00 00 05 19 06 08 18 4E 35 00 00 19 00 2F 27 0F 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 03 E8 0...

Страница 226: ...2 byte Volts C THD Maximum 1F 3F 1F 40 3 4 Float 4 byte Volts A Minimum 1F 41 1F 42 3 4 Float 4 byte Volts B Minimum 1F 43 1F 44 3 4 Float 4 byte Volts C Minimum 06 0B 06 0C 4 4 Energy 4 byte VARhr Negative Phase A 06 0D 06 0E 4 4 Energy 4 byte VARhr Negative Phase B 17 75 6 2 SINT 2 byte Volts A 1st Harmonic Magnitude 17 76 6 2 SINT 2 byte Volts A 2nd Harmonic Magnitude 17 77 6 2 SINT 2 byte Volt...

Страница 227: ...that each capture is composed of 26 waveform records and each record requires 4 windows to retrieve For more informa tion on record retrieval see B 5 4 3 Log Retrieval Procedure on page B 18 The 26 waveform records adhere to the following byte map SIZE CONTENT NOTES OFFSET 6 bytes Timestamp All 26 records have the same time stamp 0 1 byte Capture Number All 26 records have the same capture number ...

Страница 228: ...ock is being presented Breaking the waveform capture down further the specific blocks Header and Channel Blocks are as follows NOTE 1b 1 byte 2b 2 bytes Bytes Block 36 Header 388 Reserved 0xFF 4098 Channel AN Wye or AB Delta 4098 Channel IA 4098 Channel BN Wye or BC Delta 4098 Channel IB 4098 Channel CN Wye or CA Delta 4098 Channel IC Trigger Source 2b SmpRate 1b Flags 1b TriggerType TrigCap Trigg...

Страница 229: ...x and window data repeated 4 times For each block you must check that the window status and window index are correct If the window status is 0xFF then the data is not ready and you should request that record again See B 5 4 4 Log Retrieval Example on page B 21 for an exam ple of this point 3 Once you know you have the right data check the waveform record header to make sure you have received the c...

Страница 230: ...tripping process for all 26 waveform records Once done combine all 26 header stripped records into a single byte array thus creating the waveform capture const uint RECORD_PAYLOAD_SIZE 962 const uint MAX_WAVEFORM_CAPTURE_SIZE 25012 byte waveform_capture new byte MAX_WAVEFORM_CAPTURE_SIZE combine all binary data from waveform records to create waveform cap ture for int i 0 i 26 i waveform_record i ...

Страница 231: ...les earlier in this section to extract the RMS and channel sample data values desired Take note that the waveform capture byte map is in MSB hi byte lo byte form The following is an example snippet in which we first parse the waveform capture header values and then each waveform capture channel block using a predefined function NOTE We assume the channel blocks to be in order in this example e g A...

Страница 232: ...6 new byte 2 waveform_cap ture 24 waveform_capture 25 0 calibration_ia BitConverter ToUInt16 new byte 2 waveform_cap ture 26 waveform_capture 27 0 CHANNEL BLOCK PARSING predefined function public static List int GetChannelSampleData byte waveform_capture int start_byte int temp int begin start_byte 2 skip Channel ID e g AN IA etc and get data start int end start_byte 4098 List int list new List in...

Страница 233: ..._IA 4522 VOLTS_BN 8620 CURRENT_IB 12718 VOLTS_CN 16816 CURRENT_IC 20914 CHANNEL BLOCK PARSING get sample values from capture List int volts_an GetChannelSampleData waveform_capture int Channel_ID VOLTS_AN List int current_ia GetChannelSampleData waveform_capture int Channel_ID CURRENT_IA List int volts_bn GetChannelSampleData waveform_capture int Channel_ID VOLTS_BN List int current_ib GetChannelS...

Страница 234: ... Value is the primary value desired to be acquired Can refer to either RMS values Trigger Cycle RMS Trigger Cycle RMS etc Sample values Volts AN Current IA Volts BN etc Calibration is the sample calibration value for corresponding channel Ratio is either PT Ratio or CT Ratio acquired from Programmable Settings PT Ratio for voltage CT Ratio for current For example if you are looking for the primary...

Страница 235: ... double calibration double ratio return adc_value calibration 1000000 ratio double primary_rms_va GetPrimaryValue rms_va calibration_va pt_ra tio double primary_rms_ia GetPrimaryValue rms_ia calibration_ia ct_ra tio double primary_rms_vb GetPrimaryValue rms_vb calibration_vb pt_ra tio double primary_rms_ib GetPrimaryValue rms_ib calibration_ib ct_ra tio double primary_rms_vc GetPrimaryValue rms_vc...

Страница 236: ...nt_ia ToArray cali bration_ia ct_ratio List double primary_bn GetPrimaryValues volts_bn ToArray cali bration_vb pt_ratio List double primary_ib GetPrimaryValues current_ib ToArray cali bration_ib ct_ratio List double primary_cn GetPrimaryValues volts_cn ToArray cali bration_vc pt_ratio List double primary_ic GetPrimaryValues current_ic ToArray cali bration_ic ct_ratio Additional Waveform Processin...

Страница 237: ...eform_capture 7 0 The trigger source value acquired from the waveform capture header must be parsed to get the specific trigger condition error string for example voltage surge or voltage sag bool deltaHookup hookup flag int trigger_state new int 16 to represent 16 individual bits Array Clear trigger_state 0 trigger_state Length set all bits to 0 set the individual trigger_state bit flags using tr...

Страница 238: ...ing and Smart Grid Solutions if trigger_state i 0 switch i case 0 if deltaHookup triggered_str triggered_str Vab Surge else triggered_str triggered_str Van Surge break case 1 if deltaHookup triggered_str triggered_str Vab Surge else triggered_str triggered_str Van Surge break case 2 if deltaHookup triggered_str triggered_str Vcb Surge else triggered_str triggered_str Vcn Surge break case 3 ...

Страница 239: ...tions triggered_str triggered_str Ia Surge break case 4 triggered_str triggered_str Ib Surge break case 5 triggered_str triggered_str Ic Surge break case 6 if deltaHookup triggered_str triggered_str Vab Sag else triggered_str triggered_str Van Sag break case 7 if deltaHookup triggered_str triggered_str Vbc Sag else triggered_str triggered_str Vbn Sag break case 8 if deltaHookup triggered_str trigg...

Страница 240: ...f what the trigger cycle tag provides the following is a snippet from a CSV generated output of the raw sample values non primary values from a waveform capture The index at which the samples are located within the CSV file is specified in the first column With a trigger cycle tag of 512 and the following table SAMPLES INDEX VOLTS AN CURRENT IA VOLTS BN CURRENT IB VOLTS CN CURRENT IC 27 0 0 0 0 0 ...

Страница 241: ...e locked cycle Note that this means that there are 512 samples every 16 6 ms The sample rate also affects the duration of the capture Since the capture records a fixed number of samples the number of cycles recorded is dynamic based off the sampling rate For example at 512 samples per cycle 4 cycles can be record At 32 samples per cycle 64 cycles can be recorded To calculate the duration of the ca...

Страница 242: ...tate 6 2 bytes Event Channels Bit mapped per trigger events 1 indicates a channel changed state and that the change to the present state caused the event 8 1 byte Capture Number 0 if cycle was not cap tured 1 255 if all or part of the cycle was captured 10 1 byte Flags Always 0 11 2 bytes Event Cycle Tag Tag of the last sample in the event cycle 12 18 bytes Worst Excursion RMS For events ending a ...

Страница 243: ...ent States 2b Event Channels 2b Capture 1b Flags 1b Event Cycle Tag 2b Worst Excursion RMS Va Surge Worst Excursion RMS Vb Surge Worst Excursion RMS Vc Surge Worst Excursion RMS Ia Surge Worst Excursion RMS Ib Surge Worst Excursion RMS Ic Surge Worst Excursion RMS Va Sag Worst Excursion RMS Vb Sag Worst Excursion RMS Vc Sag Sample Calibration Va 2b Sample Calibration Ia 2b Sample Calibration Vb 2b...

Страница 244: ... F3 21 00 00 00 00 00 00 00 00 00 00 00 00 00 00 22 00 00 00 00 00 00 23 From the above content the values would be as follows timestamp 2012 04 30 11 16 36 AM present_states 0000 0001 1100 0000 see table above for bit breakdown Volts C Sag Volts B Sag Volts A Sag event_channels 0000 0001 1100 0000 see table above for bit breakdown Volts C Sag Volts B Sag Volts A Sag 7 Va surge 19 Ib calibration 8...

Страница 245: ...provided under Processing a Wave form Capture on page B 47 PQ events come with numerous PQ records From this numerous set normally there exists a specific pair of PQ records special cases will be discussed later one that is created at the beginning of the PQ event and one created at the end of the PQ event an Out and Return PQ record Using these two records along with all the other PQ records in b...

Страница 246: ...re is the bitmap for both the present states and event channel byte arrays Present State Event Channel Definition 2 bytes bit For example a value of 0x0081 00000000 10000001 in MSB indicates a Surge on Volts A and a sag on Volts B Both the present states and event channels use their bits as a series of TRUE FALSE flags to signify change The present states byte array flags tell whether or not an ou...

Страница 247: ...be trig gered again set to TRUE for that channel The following is a snippet of the present state and event channel byte arrays NOTE x TRUE empty FALSE Present State snippet Event Channel snippet PQ Record Va Surge Vb Surge Vc Surge Timestamp PQ Record Va Surge Vb Surge Vc Surge Timestamp 0 2013 04 01 02 10 13 PM 0 2013 04 01 02 10 13 PM 1 2013 04 01 02 10 14 PM 1 2013 04 01 02 10 14 PM 2 x 2013 04...

Страница 248: ...is simply the timestamp difference between those two records e g 6 seconds The following examples describe error conditions which may occur in the PQ records when PQ trigger conditions are missed For example if a surge comes back into limit while the meter is resetting it may not record the return to normal event Channel Va shows an example of a special case where the surge on PQ record 3 is not r...

Страница 249: ...gisters as 4X registers Many popular SCADA and HMI packages and their Modbus drivers have user interfaces that require users to enter these Registers starting at 40001 So instead of entering two separate values one for register type and one for the actual register they have been combined into one number The Shark 200 meter s Modbus map uses a shorthand version to depict the decimal fields i e not ...

Страница 250: ...ckages that use the 400001 to 465536 method for requesting holding registers take 400000 and add the value of the register Address in the decimal column of the Modbus Map Then enter the number e g 400009 into the UI as the starting register The drivers for these packages strip off the leading four and subtract 1 from the remaining value This final value is used as the starting register or register...

Страница 251: ...P FDSWXUH XS WR VDPSOHV F FOH DQG 0HJ 9 9 SOXV ZDYHIRUP FDSWXUH XS WR VDPSOHV F FOH DQG 0HJ LUPZDUH 9HUVLRQ 6 FKDU QRQH 0DS 9HUVLRQ 8 17 WR QRQH 0HWHU RQILJXUDWLRQ 8 17 ELW PDSSHG ccc ffffff FFF 7 GHQRPLQDWRU RU IIIIII FDOLEUDWLRQ IUHTXHQF RU 6 9HUVLRQ 8 17 QRQH RRW LUPZDUH 9HUVLRQ 6 FKDU QRQH 2SWLRQ 6ORW 8VDJH 8 17 ELW PDSSHG VDPH DV UHJLVWHU 2SWLRQ 6ORW 8VDJH 8 17 ELW PDSSHG VDPH DV UHJLVWHU 0HW...

Страница 252: ... 17 WR 9 V 9 V 3KDVH 8 17 WR 9 V 9 V 3KDVH 8 17 WR 9 V 3RZHU DFWRU 3KDVH 6 17 WR QRQH 3RZHU DFWRU 3KDVH 6 17 WR QRQH 3RZHU DFWRU 3KDVH 6 17 WR QRQH ORFN 6L H UHDG RQO 9ROWV 1 2 7 WR 0 YROWV 9ROWV 1 2 7 WR 0 YROWV 9ROWV 1 2 7 WR 0 YROWV 9ROWV 2 7 WR 0 YROWV 9ROWV 2 7 WR 0 YROWV 9ROWV 2 7 WR 0 YROWV PSV 2 7 WR 0 DPSV PSV 2 7 WR 0 DPSV PSV 2 7 WR 0 DPSV DWWV 3K WRWDO 2 7 0 WR 0 ZDWWV 9 5V 3K WRWDO 2 ...

Страница 253: ...U 3KDVH 2 7 WR QRQH 3RZHU DFWRU 3KDVH 2 7 WR QRQH 3RZHU DFWRU 3KDVH 2 7 WR QRQH 6 PPHWULFDO RPSRQHQW 0DJQLWXGH 6HT 2 7 WR 0 YROWV 6 PPHWULFDO RPSRQHQW 0DJQLWXGH 6HT 2 7 WR 0 YROWV 6 PPHWULFDO RPSRQHQW 0DJQLWXGH 6HT 2 7 WR 0 YROWV 6 PPHWULFDO RPSRQHQW 3KDVH 6HT 6 17 WR GHJUHH 6 PPHWULFDO RPSRQHQW 3KDVH 6HT 6 17 WR GHJUHH 6 PPHWULFDO RPSRQHQW 3KDVH 6HT 6 17 WR GHJUHH 8QEDODQFH VHTXHQFH FRPSRQHQW 8 1...

Страница 254: ... HQHUJ IRUPDW KRXUV 1HW 3KDVH 6 17 WR K SHU HQHUJ IRUPDW KRXUV 7RWDO 3KDVH 6 17 WR K SHU HQHUJ IRUPDW KRXUV 7RWDO 3KDVH 6 17 WR K SHU HQHUJ IRUPDW KRXUV 7RWDO 3KDVH 6 17 WR K SHU HQHUJ IRUPDW 9 5 KRXUV 3RVLWLYH 3KDVH 6 17 WR 9 5K SHU HQHUJ IRUPDW 9 5 KRXUV 3RVLWLYH 3KDVH 6 17 WR 9 5K SHU HQHUJ IRUPDW 9 5 KRXUV 3RVLWLYH 3KDVH 6 17 WR 9 5K SHU HQHUJ IRUPDW 9 5 KRXUV 1HJDWLYH 3KDVH 6 17 WR 9 5K SHU H...

Страница 255: ...LQ WKH QWHUYDO 3RVLWLYH 3KDVH 6 17 WR 9 5K SHU HQHUJ IRUPDW 9 5 KRXUV LQ WKH QWHUYDO 1HJDWLYH 3KDVH 6 17 WR 9 5K SHU HQHUJ IRUPDW 9 5 KRXUV LQ WKH QWHUYDO 1HJDWLYH 3KDVH 6 17 WR 9 5K SHU HQHUJ IRUPDW 9 5 KRXUV LQ WKH QWHUYDO 1HJDWLYH 3KDVH 6 17 WR 9 5K SHU HQHUJ IRUPDW 9 KRXUV LQ WKH QWHUYDO 3KDVH 6 17 WR 9 K SHU HQHUJ IRUPDW 9 KRXUV LQ WKH QWHUYDO 3KDVH 6 17 WR 9 K SHU HQHUJ IRUPDW 9 KRXUV LQ WKH...

Страница 256: ...V 9 V 3KDVH YHUDJH 2 7 0 WR 0 9 V 9 V 3KDVH YHUDJH 2 7 0 WR 0 9 V 9 V 3KDVH YHUDJH 2 7 0 WR 0 9 V 3RVLWLYH 3 3KDVH YHUDJH 2 7 WR QRQH 3RVLWLYH 3 3KDVH YHUDJH 2 7 WR QRQH 3RVLWLYH 3 3KDVH YHUDJH 2 7 WR QRQH 1HJDWLYH 3 3KDVH YHUDJH 2 7 WR QRQH 1HJDWLYH 3 3KDVH YHUDJH 2 7 WR QRQH 1HJDWLYH 3 3KDVH YHUDJH 2 7 WR QRQH ORFN 6L H UHDG RQO DWWV 3K WRWDO 2 7 0 WR 0 ZDWWV 9 5V 3K WRWDO 2 7 0 WR 0 9 5V 9 V 3K...

Страница 257: ... HQHUJ IRUPDW KRXUV 1HW 3KDVH 6 17 WR K SHU HQHUJ IRUPDW KRXUV 7RWDO 3KDVH 6 17 WR K SHU HQHUJ IRUPDW KRXUV 7RWDO 3KDVH 6 17 WR K SHU HQHUJ IRUPDW KRXUV 7RWDO 3KDVH 6 17 WR K SHU HQHUJ IRUPDW 9 5 KRXUV 3RVLWLYH 3KDVH 6 17 WR 9 5K SHU HQHUJ IRUPDW 9 5 KRXUV 3RVLWLYH 3KDVH 6 17 WR 9 5K SHU HQHUJ IRUPDW 9 5 KRXUV 3RVLWLYH 3KDVH 6 17 WR 9 5K SHU HQHUJ IRUPDW 9 5 KRXUV 1HJDWLYH 3KDVH 6 17 WR 9 5K SHU H...

Страница 258: ... KHDGHU IODJ LV LI 2 W 7 37 FRPSHQVDWLRQ VWDWXV LVDEOHG QDEOHG II IODVK VWDWH LQLWLDOL LQJ ORJJLQJ GLVDEOHG E 9VZLWFK ORJJLQJ HH HGLW VWDWH VWDUWXS QRUPDO SULYLOHJHG FRPPDQG VHVVLRQ SURILOH XSGDWH PRGH FFF SRUW HQDEOHG IRU HGLW QRQH 20 20 IURQW SDQHO LPLWV 6WDWXV 8 17 ELW PDSSHG 87654321 87654321 KLJK E WH LV VHWSW LQ RXW ORZ E WH LV VHWSW LQ RXW VHH QRWHV 7LPH 6LQFH 5HVHW 8 17 WR PVHF ZUDSV DURXQ...

Страница 259: ...WV 1 SUHYLRXV HPDQG LQWHUYDO 6KRUW 7HUP 0LQLPXP 2 7 WR 0 YROWV 9ROWV 1 SUHYLRXV HPDQG LQWHUYDO 6KRUW 7HUP 0LQLPXP 2 7 WR 0 YROWV 9ROWV SUHYLRXV HPDQG LQWHUYDO 6KRUW 7HUP 0LQLPXP 2 7 WR 0 YROWV 9ROWV SUHYLRXV HPDQG LQWHUYDO 6KRUW 7HUP 0LQLPXP 2 7 WR 0 YROWV 9ROWV SUHYLRXV HPDQG LQWHUYDO 6KRUW 7HUP 0LQLPXP 2 7 WR 0 YROWV 9ROWV 1 6KRUW 7HUP 0LQLPXP 2 7 WR 0 YROWV 9ROWV 1 6KRUW 7HUP 0LQLPXP 2 7 WR 0 Y...

Страница 260: ...ion h header flag is 1 if OK t CT PT compensation status 0 Disabled 1 Enabled ff flash state 0 initializing 1 logging disabled by Vswitch 3 logging ee edit state 0 startup 1 normal 2 privileged command session 3 profile update mode ccc port enabled for edit 0 none 1 4 COM1 COM4 7 front panel 1 1195 1195 4502 4502 Limits Status UINT16 bit mapped 87654321 87654321 high byte is setpt 1 0 in 1 out low...

Страница 261: ...PPHWULFDO RPSRQHQW 3KDVH 6HT 0LQLPXP 6 17 WR GHJUHH 8QEDODQFH VHTXHQFH 0LQLPXP 8 17 WR 8QEDODQFH VHTXHQFH 0LQLPXP 8 17 WR XUUHQW 8QEDODQFH 0LQLPXP 8 17 WR ORFN 6L H UHDG RQO 9ROWV 1 0LQ 7LPHVWDPS 767 03 DQ HF VHF 9ROWV 1 0LQ 7LPHVWDPS 767 03 DQ HF VHF 9ROWV 1 0LQ 7LPHVWDPS 767 03 DQ HF VHF 9ROWV 0LQ 7LPHVWDPS 767 03 DQ HF VHF 9ROWV 0LQ 7LPHVWDPS 767 03 DQ HF VHF 9ROWV 0LQ 7LPHVWDPS 767 03 DQ HF VH...

Страница 262: ...HF 3RVLWLYH 9 5V 3KDVH 0LQ YJ PG 7LPHVWDPS 767 03 DQ HF VHF 1HJDWLYH DWWV 3KDVH 0LQ YJ PG 7LPHVWDPS 767 03 DQ HF VHF 1HJDWLYH DWWV 3KDVH 0LQ YJ PG 7LPHVWDPS 767 03 DQ HF VHF 1HJDWLYH DWWV 3KDVH 0LQ YJ PG 7LPHVWDPS 767 03 DQ HF VHF 1HJDWLYH 9 5V 3KDVH 0LQ YJ PG 7LPHVWDPS 767 03 DQ HF VHF 1HJDWLYH 9 5V 3KDVH 0LQ YJ PG 7LPHVWDPS 767 03 DQ HF VHF 1HJDWLYH 9 5V 3KDVH 0LQ YJ PG 7LPHVWDPS 767 03 DQ HF VH...

Страница 263: ...VWDPS 767 03 DQ HF VHF 6 PPHWULFDO RPS 3KDVH 6HT 0LQ 7LPHVWDPS 767 03 DQ HF VHF 6 PPHWULFDO RPS 3KDVH 6HT 0LQ 7LPHVWDPS 767 03 DQ HF VHF 8QEDODQFH 6HT 0LQ 7LPHVWDPS 767 03 DQ HF VHF 8QEDODQFH 6HT 0LQ 7LPHVWDPS 767 03 DQ HF VHF XUUHQW 8QEDODQFH 0LQ 7LPHVWDPS 767 03 DQ HF VHF ORFN 6L H UHDG RQO 9ROWV 1 SUHYLRXV HPDQG LQWHUYDO 6KRUW 7HUP 0D LPXP 2 7 WR 0 YROWV 9ROWV 1 SUHYLRXV HPDQG LQWHUYDO 6KRUW 7H...

Страница 264: ... 0D LPXP YJ HPDQG 2 7 WR 0 DPSV 3RVLWLYH DWWV 3KDVH 0D LPXP YJ HPDQG 2 7 0 WR 0 ZDWWV 3RVLWLYH DWWV 3KDVH 0D LPXP YJ HPDQG 2 7 0 WR 0 ZDWWV 3RVLWLYH DWWV 3KDVH 0D LPXP YJ HPDQG 2 7 0 WR 0 ZDWWV 3RVLWLYH 9 5V 3KDVH 0D LPXP YJ HPDQG 2 7 0 WR 0 9 5V 3RVLWLYH 9 5V 3KDVH 0D LPXP YJ HPDQG 2 7 0 WR 0 9 5V 3RVLWLYH 9 5V 3KDVH 0D LPXP YJ HPDQG 2 7 0 WR 0 9 5V 1HJDWLYH DWWV 3KDVH 0D LPXP YJ HPDQG 2 7 0 WR 0...

Страница 265: ...DG RQO 9ROWV 1 0D 7LPHVWDPS 767 03 DQ HF VHF 9ROWV 1 0D 7LPHVWDPS 767 03 DQ HF VHF 9ROWV 1 0D 7LPHVWDPS 767 03 DQ HF VHF 9ROWV 0D 7LPHVWDPS 767 03 DQ HF VHF 9ROWV 0D 7LPHVWDPS 767 03 DQ HF VHF 9ROWV 0D 7LPHVWDPS 767 03 DQ HF VHF PSV 0D YJ PG 7LPHVWDPS 767 03 DQ HF VHF PSV 0D YJ PG 7LPHVWDPS 767 03 DQ HF VHF PSV 0D YJ PG 7LPHVWDPS 767 03 DQ HF VHF 3RVLWLYH DWWV 3K 0D YJ PG 7LPHVWDPS 767 03 DQ HF VH...

Страница 266: ...7 03 DQ HF VHF 3RVLWLYH 3 3KDVH 0D YJ PG 7LPHVWDPS 767 03 DQ HF VHF 3RVLWLYH 3 3KDVH 0D YJ PG 7LPHVWDPS 767 03 DQ HF VHF 3RVLWLYH 3 3KDVH 0D YJ PG 7LPHVWDPS 767 03 DQ HF VHF 1HJDWLYH 3 3KDVH 0D YJ PG 7LPHVWDPS 767 03 DQ HF VHF 1HJDWLYH 3 3KDVH 0D YJ PG 7LPHVWDPS 767 03 DQ HF VHF 1HJDWLYH 3 3KDVH 0D YJ PG 7LPHVWDPS 767 03 DQ HF VHF 9ROWV 1 7 0D 7LPHVWDPS 767 03 DQ HF VHF 9ROWV 1 7 0D 7LPHVWDPS 767 ...

Страница 267: ... ZLWK VSDFHV QWHUSUHWDWLRQ GHSHQGV RQ WKH VSHFLILF FDUG LQ WKH VORW QDORJ XVHV WKH VHFRQG UHJLVWHUV IRU LWV YHUVLRQ 7KH ILUVW UHJLVWHUV DUH HUR 1HWZRUN XVHV WKH ILUVW UHJLVWHUV IRU LWV 581 YHUVLRQ WKH VHFRQG IRU LWV 227 YHUVLRQ 1R RWKHU FDUGV UHSRUW YHUVLRQV ERWK UHJLVWHUV DUH HUR 5HVHUYHG 5HVHUYHG ORFN 6L H 5HDG RQO XUUHQW VSHHG DQG IRUPDW 8 17 ELW PDSSHG abcde fghijklm SV D E F G H 6WRS ELWV I F...

Страница 268: ...N 6L H UHDG RQO H FHSW DV LQGLFDWHG LJLWDO QSXW 6WDWHV 8 17 ELW PDSSHG dddd cccc bbbb aaaa 1LEEOH GGGG IRU LQSXW FFFF IRU LQSXW EEEE IRU LQSXW DQG DDDD IRU LQSXW LWKLQ HDFK ILHOG ULJKWPRVW ELW LV WKH FXUUHQW VWDWH FORVHG RSHQ DQG ELWV DW OHIW DUH WKH ROGHU VWDWHV PV DSDUW KLVWRULFDO VWDWHV DPSOH XUUHQW VWDWH RI LQSXW LV FORVHG EHIRUH WKDW LW ZDV FORVHG WRR EHIRUH WKDW LW ZDV RSHQ DQG WKH ROGHVW VW...

Страница 269: ...XV WFS LS RN 3 6WDWXV LL 3 QRW YDOLG HW 3 IURP S VHWWLQJV 3 IURP 3 XVLQJ ODVW JRRG NQRZQ 3 5HVHUYHG 5HVHUYHG 0 DGGUHVV LQ XVH E WKH QHWZRUN FDUG 8 17 ELW PDSSHG E WHV 7KHVH UHJLVWHUV KROG WKH E WHV RI WKH FDUG V HWKHUQHW 0 DGGUHVV XUUHQW 3 GGUHVV 8 17 7KHVH UHJLVWHUV KROG WKH QXPEHUV QXPEHU HDFK UHJLVWHU WKDW PDNH WKH 3 DGGUHVV XVHG E WKH FDUG XUUHQW 3 0DVN HQJWK 8 17 WR 1XPEHU RI ELWV WKDW DUH VH...

Страница 270: ...YHG LUPZDUH 9HUVLRQV 6 FKDU HDFK QRQH LUPZDUH YHUVLRQV IRU RSWLRQ FDUGV DFK YHUVLRQ LV D FKDUDFWHU VWULQJ OHIW MXVWLILHG DQG SDGGHG ZLWK VSDFHV QWHUSUHWDWLRQ GHSHQGV RQ WKH VSHFLILF FDUG LQ WKH VORW QDORJ XVHV WKH VHFRQG UHJLVWHUV IRU LWV YHUVLRQ 7KH ILUVW UHJLVWHUV DUH HUR 1HWZRUN XVHV WKH ILUVW UHJLVWHUV IRU LWV 581 YHUVLRQ WKH VHFRQG IRU LWV 227 YHUVLRQ 1R RWKHU FDUGV UHSRUW YHUVLRQV ERWK UHJLV...

Страница 271: ...WKHUZLVH VWDWH RI 5HOD LV LQ F WULSSHG UHOHDVHG I E LV WKHQ VWDWH RI 5HOD LV XQNQRZQ RWKHUZLVH VWDWH RI 5HOD LV LQ G WULSSHG UHOHDVHG 7XUQ UHOD RQ 8 17 ELW PDSSHG 21 ULWLQJ D LQ ELW 1 WXUQV UHOD 1 21 WKLV UHJLVWHU LV ZULWHDEOH RQO LQ SULYLOHJHG VHVVLRQ 7XUQ UHOD RII 8 17 ELW PDSSHG 21 ULWLQJ D LQ ELW 1 WXUQV UHOD 1 2 WKLV UHJLVWHU LV ZULWHDEOH RQO LQ SULYLOHJHG VHVVLRQ 7ULS 5HOHDVH GHOD WLPHU IRU ...

Страница 272: ...HDFK RXWSXW XQGHU WHVW QRUPDO 3XOVH 2XWSXW 7HVW 3RZHU 8 17 ELW PDSSHG ddvvvvvv vvvvvvvv 7KLV UHJLVWHU LV ULWHDEOH LQ SULYLOHJHG VHVVLRQ RQO 6LPXODWHV FRQVWDQW 3RZHU IRU WKH 3XOVH 2XWSXW XQGHU WHVW RUPDW LV VDPH DV W VHWWLQJV IRU 3XOVH 2XWSXW 9 LV UDZ YDOXH LQ K SXOVH IURP WR GG GHFLPDO SRLQW SRVLWLRQ 5HVHUYHG 5HVHUYHG QSXW FFXPXODWRU 6FDOHG 8 17 WR QSXW FFXPXODWRU 6FDOHG 8 17 WR QSXW FFXPXODWRU 6F...

Страница 273: ...G 2XWSXW RU 5HOD FFXPXODWRU 8 17 WR QXPEHU RI WUDQVLWLRQV 2SWLRQ DUG 2XWSXW RU 5HOD V FFXPXODWRUV 8 17 WR QXPEHU RI WUDQVLWLRQV 2SWLRQ DUG QSXWV FFXPXODWRUV 8 17 WR QXPEHU RI WUDQVLWLRQV 2SWLRQ DUG 2XWSXWV FFXPXODWRUV 8 17 WR QXPEHU RI WUDQVLWLRQV ORFN 6L H ZULWH RQO 5HVHW 0D 0LQ ORFNV 8 17 SDVVZRUG 1RWH 5HVHW QHUJ FFXPXODWRUV 8 17 SDVVZRUG 1RWH 5HVHW ODUP RJ 1RWH 8 17 SDVVZRUG 1RWH 5HVHW 6 VWHP R...

Страница 274: ...3 DQ HF VHF VDYHG RQO ZKHQ UG UHJLVWHU LV ZULWWHQ 0DQXDOO 7ULJJHU DYHIRUP DSWXUH 8 17 DQ YDOXH DSSOLHV WR 6KDUN RQO UHWXUQV EXV H FHSWLRQ LI EORFNHG E DQRWKHU FDSWXUH LQ SURJUHVV 5HVHUYHG 5HVHUYHG ORVH 3ULYLOHJHG RPPDQG 6HVVLRQ 8 17 DQ YDOXH HQGV DQ RSHQ FRPPDQG VHVVLRQ ORFN 6L H read write 3HUIRUP D 6HFXUH 2SHUDWLRQ 8 17 HQFU SWHG FRPPDQG WR UHDG SDVVZRUG RU FKDQJH PHWHU W SH ORFN 6L H write only...

Страница 275: ...QF PHWKRG 173 LQH DOO RWKHU YDOXHV QR V QF SSSS PHWKRG GHSHQGHQW SDUDPWHU 173 SSSS SRUW SHUIRUPLQJ V QFKURQL DWLRQ 20 20 LQH SSSS H SHFWHG IUHTXHQF 1 5HVHUYHG 5HVHUYHG 1 8VHU 6HWWLQJV 8 17 ELW PDSSHG vfpr cccccccs Y 6HWWLQJ IRU 9LHZ DV HQHUDWRU OLS 9 5 XQIOLS 3 RII Q I IRUFH F FOH HQHUJ SRZHU SURFHVVLQJ HV QR S VXSSUHVV ILOWHULQJ RQ SRZHU UHDGLQJV HV QR U VXSSUHVV ILOWHULQJ RQ FXUUHQW DQG YROWDJH ...

Страница 276: ...V QR Z SRZHU GLUHFWLRQ YLHZ DV ORDG YLHZ DV JHQHUDWRU I IOLS SRZHU IDFWRU VLJQ HV QR D DSSDUHQW SRZHU FRPSXWDWLRQ PHWKRG DULWKPHWLF VXP YHFWRU VXP XOO 6FDOH XUUHQW IRU ORDG EDU JUDSK 8 17 WR QRQH I QRQ HUR DQG XVHU VHWWLQJV ELW J LV VHW WKLV YDOXH UHSODFHV 7 QXPHUDWRU LQ WKH IXOO VFDOH FXUUHQW FDOFXODWLRQ 6HH 1RWH 0HWHU HVLJQDWLRQ 6 FKDU QRQH 20 VHWXS 8 17 ELW PDSSHG dddd 0100110 20 VHWXS 8 17 ELW...

Страница 277: ... I GLVDEOH FRPSHQVDWLRQ IRU ORVVHV GXH WR LURQ HQDEOH FRPSHQVDLRQ IRU ORVVHV GXH WR LURQ Z DGG ZDWW FRPSHQVDWLRQ VXEWUDFW ZDWW FRPSHQVDWLRQ Y DGG YDU FRPSHQVDWLRQ VXEWUDFW YDU FRPSHQVDWLRQ 5HVHUYHG 5HVHUYHG 3URJUDPPDEOH 6HWWLQJV 8SGDWH RXQWHU 8 17 QFUHPHQWV HDFK WLPH SURJUDPPDEOH VHWWLQJV DUH FKDQJHG RFFXUV ZKHQ QHZ FKHFNVXP LV FDOFXODWHG 5HVHUYHG IRU 6RIWZDUH 8VH 5HVHUYHG SKDVH 37 FRPSHQVDWLRQ 9 ...

Страница 278: ...XDOLW RJ 7ULJJHUV 8 17 ELW PDSSHG 8 76543210 DYHIRUP RJ 7ULJJHUV 8 17 ELW PDSSHG 8 76543210 DYHIRUP 34 RJ 6L HV 8 17 ELW PDSSHG pppppppp wwwwwwww LJK E WH LV QXPEHU RI IODVK VHFWRUV IRU 34 ORJ RZ E WH LV QXPEHU RI IODVK VHFWRUV IRU ZDYHIRUP ORJ 5HVHUYHG 5HVHUYHG KDQQHO 9ROWDJH 6XUJH 7KUHVKROG 8 17 WR RI IXOO VFDOH KDQQHO XUUHQW 6XUJH 7KUHVKROG 8 17 WR RI IXOO VFDOH KDQQHO 9ROWDJH 6DJ 7KUHVKROG 8 1...

Страница 279: ... FF 6RXUFH IRU 3XOVH 2XSXW 8 17 HQXPHUDWLRQ ppp vvvv SSS 3KDVH QRQH 3KDVH 3KDVH 3KDVH OO 3KDVHV 3XOVH IURP 2 QG 2I QWHUYDO YYYY 9DOXH QRQH K K K 9DUK 9DUK 9DUK 9 K 5HFHLYHG K HOLYHUHG K QGXFWLYH 9DUK DSDFLWLYH 9DUK W K SXOVH IDFWRU IRU 3XOVH 2XWSXW 8 17 ELW PDSSHG ddVVVVVV VVVVVVVV 9 9 QRW VFDOHG HQHUJ YDOXH SHU SXOVH IURP WR GG GHFLPDO SRLQW SRVLWLRQ 2XWSXW VVLJQPHQW DQG W 8 17 2XWSXW VVLJQPHQW D...

Страница 280: ... FF 6RXUFH IRU 3XOVH 2XSXW 8 17 HQXPHUDWLRQ ppp vvvv SSS 3KDVH QRQH 3KDVH 3KDVH 3KDVH OO 3KDVHV 3XOVH IURP 2 QG 2I QWHUYDO YYYY 9DOXH QRQH K K K 9DUK 9DUK 9DUK 9 K 5HFHLYHG K HOLYHUHG K QGXFWLYH 9DUK DSDFLWLYH 9DUK W K SXOVH IDFWRU IRU 3XOVH 2XWSXW 8 17 ELW PDSSHG ddVVVVVV VVVVVVVV 9 9 QRW VFDOHG HQHUJ YDOXH SHU SXOVH IURP WR GG GHFLPDO SRLQW SRVLWLRQ 2XWSXW VVLJQPHQW DQG W 8 17 2XWSXW VVLJQPHQW D...

Страница 281: ...H 1DPH 6 FKDU QSXW DEHO DQG 6WDWH 1DPHV QSXW DEHO DQG 6WDWH 1DPHV QSXW DEHO DQG 6WDWH 1DPHV 2XWSXW DEHO 6 FKDU 2XWSXW 2SHQ 6WDWH 1DPH 6 FKDU 2XWSXW ORVHG 6WDWH 1DPH 6 FKDU 2XWSXW DEHO DQG 6WDWH 1DPHV 2XWSXW DEHO DQG 6WDWH 1DPHV 2XWSXW DEHO DQG 6WDWH 1DPHV QSXW FFXPXODWRU DEHO 6 FKDU QSXW FFXPXODWRU DEHO 6 FKDU QSXW FFXPXODWRU DEHO 6 FKDU QSXW FFXPXODWRU DEHO 6 FKDU QSXW FFXPXODWRU W 8 17 ELW PDSSH...

Страница 282: ...IRU FXUUHQW RXWSXW Q GLIIHUHQW ZRUGV WKH FXUUHQW OHYHO RXWSXW RI DQDORJ ERDUG ZLOO IROORZ WKH YDOXH RI WKH UHJLVWHU DGGUHVVHG KHUH LJK YDOXH RI VRXUFH UHJLVWHU IRU RXWSXW 9DOXH UHDG IURP WKH VRXUFH UHJLVWHU DW ZKLFK LJK QRPLQDO FXUUHQW ZLOO EH RXWSXW DPSOH IRU WKH P FDUG LI WKLV UHJLVWHU LV SURJUDPPHG ZLWK WKHQ WKH FXUUHQW RXWSXW ZLOO EH P ZKHQ WKH YDOXH UHDG IURP WKH VRXUFH UHJLVWHU LV RZ YDOXH R...

Страница 283: ...VV RI WKH 16 RQ WKH QHWZRUN 7 3 3 3RUW 0RGEXV DWHZD 6HUYLFH 8 17 3RUW IRU WKH DWHZD VHUYLFH PRGEXV WFS LS ZKHQ HQDEOHG I WKLV YDOXH LV 52 WKH GHIDXOW DGGUHVV ZLOO EH XVHG 7 3 3 3RUW HE6HUYLFH 8 17 3RUW IRU WKH HE VHUYLFH KWPO YLHZHU ZKHQ HQDEOHG I WKLV YDOXH LV 52 WKH GHIDXOW DGGUHVV ZLOO EH XVHG 13 UDSSHU 6HUYHU 3RUW 8 17 3RUW QXPEHU ZKHUH WKH 13 6HUYHU ZLOO OLVWHQ IRU FRQQHFWLRQV 13 HYLFH QXPEHU...

Страница 284: ...HWWLQJV IRU 2SWLRQ DUG LUVW 2YHUOD VHH EHORZ 6HWWLQJV IRU 2SWLRQ DUG 6HFRQG 2YHUOD VHH EHORZ ORFN 6L H LUVW 2YHUOD ZULWH RQO LQ 36 XSGDWH PRGH 6ODYH DGGUHVV 8 17 a IRU 0RGEXV a IRU 13 QRQH 6ODYH DGGUHVV RI WKH XQLW 7KH FRPPXQLFDWLRQ FDSDEOH FDUG LV DOZD V D PDVWHU 6HW WR ZKHQ DQ DQDORJ ERDUG LV LQVWDOOHG 6SHHG DQG IRUPDW 8 17 ELW PDSSHG abcde fghijklm SV D E F G H 6WRS ELWV I FOHDUHG VWRS ELW VHW ...

Страница 285: ... ZLWK WKH WULJJHU PRGH FULHWHULD FF 5HOD HOD WR 2SHUDWH 8 17 VHFRQG XQLWV HOD WR RSHUDWH WKH UHOD VLQFH UHTXHVW 5HOD HOD WR 5HOHDVH 8 17 VHFRQG XQLWV HOD WR UHOHDVH WKH UHOD VLQFH UHTXHVW 5HVHUYHG 8 17 6HW WR 5HOD HOD WR 2SHUDWH 8 17 VHFRQG XQLWV HOD WR RSHUDWH WKH UHOD VLQFH UHTXHVW 5HOD HOD WR 5HOHDVH 8 17 VHFRQG XQLWV HOD WR UHOHDVH WKH UHOD VLQFH UHTXHVW 5HVHUYHG 8 17 6HW WR QSXW FFXPXODWRUV 6...

Страница 286: ...6RXUFH IRU 3XOVH 2XSXW 8 17 HQXPHUDWLRQ ppp vvvv SSS 3KDVH QRQH 3KDVH 3KDVH 3KDVH OO 3KDVHV 3XOVH IURP 2 QG 2I QWHUYDO YYYY 9DOXH QRQH K K K 9DUK 9DUK 9DUK 9 K 5HFHLYHG K HOLYHUHG K QGXFWLYH 9DUK DSDFLWLYH 9DUK W K SXOVH IDFWRU IRU 3XOVH 2XWSXW 8 17 ELW PDSSHG ddVVVVVV VVVVVVVV 9 9 QRW VFDOHG HQHUJ YDOXH SHU SXOVH IURP WR GG GHFLPDO SRLQW SRVLWLRQ 2XWSXW VVLJQPHQW DQG W 8 17 2XWSXW VVLJQPHQW DQG W...

Страница 287: ... DEHO DQG 6WDWH 1DPHV QSXW DEHO DQG 6WDWH 1DPHV QSXW DEHO DQG 6WDWH 1DPHV 2XWSXW DEHO 6 FKDU 2XWSXW 2SHQ 6WDWH 1DPH 6 FKDU 2XWSXW ORVHG 6WDWH 1DPH 6 FKDU 2XWSXW DEHO DQG 6WDWH 1DPHV 2XWSXW DEHO DQG 6WDWH 1DPHV 2XWSXW DEHO DQG 6WDWH 1DPHV QSXW FFXPXODWRU DEHO 6 FKDU QSXW FFXPXODWRU DEHO 6 FKDU QSXW FFXPXODWRU DEHO 6 FKDU QSXW FFXPXODWRU DEHO 6 FKDU QSXW FFXPXODWRU W 8 17 ELW PDSSHG ddVVVVVV VVVVVVV...

Страница 288: ...U LV SURJUDPPHG ZLWK WKHQ WKH FXUUHQW RXWSXW ZLOO EH P ZKHQ WKH YDOXH UHDG IURP WKH VRXUFH UHJLVWHU LV RZ YDOXH RI VRXUFH UHJLVWHU IRU RXWSXW 9DOXH UHDG IURP WKH VRXUFH UHJLVWHU DW ZKLFK RZ QRPLQDO FXUUHQW ZLOO EH RXWSXW DPSOH IRU WKH P FDUG LI WKLV UHJLVWHU LV SURJUDPPHG ZLWK WKHQ WKH FXUUHQW RXWSXW ZLOO EH P ZKHQ WKH YDOXH UHDG IURP WKH VRXUFH UHJLVWHU LV QDORJ RXWSXW IRUPDW UHJLVWHU PD PLQ QDOR...

Страница 289: ...R 3Y 7KHVH DUH ZRUGV UHSUHVHQWLQJ WKH QXPEHUV RI DQ 3Y DGGUHVV 7KLV DGGUHVV GHILQHV WKH VWDUW DGGUHVV IRU D UDQJH RI DFFHSWHG DGGUHVV Q FOLHQW WU LQJ WR FRQQHFW IURP DQ DGGUHVV RXWVLGH WKLV UDQJH ZLOO EH UHMHFWHG 7R GLVDEOH WKH VWDUW FKHFNLQJ XVH 13 FFHSWHG 3 GGUHVV QG 8 17 WR 3Y 7KHVH DUH ZRUGV UHSUHVHQWLQJ WKH QXPEHUV RI DQ 3Y DGGUHVV 7KLV DGGUHVV GHILQHV WKH HQG DGGUHVV IRU D UDQJH RI DFFHSWHG ...

Страница 290: ...JLVWHU 9ROWV 8 17 WR YROWV 9ROWV 8 17 WR YROWV 9ROWV 8 17 WR YROWV 7 QXPHUDWRU 8 17 WR QRQH 7 PXOWLSOLHU 8 17 QRQH 7 GHQRPLQDWRU 8 17 RU QRQH 37 QXPHUDWRU 8 17 WR QRQH 37 PXOWLSOLHU 8 17 QRQH 37 GHQRPLQDWRU 8 17 WR QRQH KRXUV 3RVLWLYH 8 17 WR K SHU HQHUJ IRUPDW WR GLJLWV KRXUV 1HJDWLYH 8 17 WR K SHU HQHUJ IRUPDW GHFLPDO SRLQW LPSOLHG SHU HQHUJ IRUPDW 9 5 KRXUV 3RVLWLYH 8 17 WR 9 5K SHU HQHUJ IRUPD...

Страница 291: ... 17 WR 9 5V ZDWWV 9 5V 9 V 9 5V 3KDVH 8 17 WR 9 5V UHJLVWHU 9 V 3KDVH 8 17 WR 9 V 9 V 3KDVH 8 17 WR 9 V 9 V 3KDVH 8 17 WR 9 V 3RZHU DFWRU 3KDVH 8 17 WR QRQH 3RZHU DFWRU 3KDVH 8 17 WR QRQH 3RZHU DFWRU 3KDVH 8 17 WR QRQH 5HVHUYHG 1 1 QRQH 5HVHUYHG 5HVHW QHUJ FFXPXODWRUV 8 17 SDVVZRUG 1RWH ZULWH RQO UHJLVWHU DOZD V UHDGV DV ORFN 6L H UHDG ZULWH H FHSW DV QRWHG RJ 5HWULHYDO 6HVVLRQ XUDWLRQ 8 17 WR PVH...

Страница 292: ...FHSWLRQ LI D ZULWH LV DWWHPSWHG 0HWHU FRPPDQG UHJLVWHUV DOZD V UHDG DV 7KH PD EH ZULWWHQ RQO ZKHQ WKH PHWHU LV LQ D VXLWDEOH PRGH 7KH UHJLVWHUV UHWXUQ DQ LOOHJDO GDWD DGGUHVV H FHSWLRQ LI D ZULWH LV DWWHPSWHG LQ DQ LQFRUUHFW PRGH I WKH SDVVZRUG LV LQFRUUHFW D YDOLG UHVSRQVH LV UHWXUQHG EXW WKH FRPPDQG LV QRW H HFXWHG 8VH IRU WKH SDVVZRUG LI SDVVZRUGV DUH GLVDEOHG LQ WKH SURJUDPPDEOH VHWWLQJV 0 GHQ...

Страница 293: ...HDFK RSWLRQ VORW QWHUSUHWDWLRQ RI WKH UHJLVWHU GDWD GHSHQGV RQ ZKDW FDUG LV LQ WKH VORW 0HDVXUHPHQW VWDWHV 2II RFFXUV GXULQJ SURJUDPPDEOH VHWWLQJV XSGDWHV 5XQ LV WKH QRUPDO PHDVXULQJ VWDWH LPS LQGLFDWHV WKDW DQ HVVHQWDLO QRQ YRODWLOH PHPRU EORFN LV FRUUXSWHG DQG DUPXS RFFXUV EULHIO IUHTXHQF SRZHU IDFWRU SHUFHQWDJH DQJOH SKDVH SRZHU 6 7 QXPHUDWRU 7 PXOWLSOLHU 37 QXPHUDWRU 37 PXOWLSOLHU 6457 IRU GHO...

Страница 294: ...B Modbus Map and Retrieving Logs Doc E149701 MM 44 Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 295: ... always acts as a secondary device slave in DNP communication An important feature allows DNP readings in primary units with user set scaling for current Voltage and power see Chapter 8 in the Communicator EXTTM 4 0 and MeterManager EXT Software User Manual for instructions C 2 Physical Layer DNP uses both Network TCP IP and serial communication DNP3 serial communica tion can be assigned to Port 2...

Страница 296: ...elapses between two consecutive characters within a FT3 frame the frame will be dropped C 4 Application Layer The Shark 200 meter s DNP version supports the Read Write Select Operate Direct Operate and Direct Operate Unconfirmed functions All Application layer requests and responses follow the DNP standard Some sample requests and responses are included in this Appendix see C 8 DNP Message Layouts...

Страница 297: ...within the specified time limit the default is 30 seconds This function uses the same operation rules as a Direct Operate function The Direct Operate function code 05 provides the means for the direct operation of a CROB Object 12 device This function can be used for resetting the Energy and Demand counters minimum and maximum energy registers or controlling relays if there are any installed in th...

Страница 298: ... Output States These data points are mapped to the Digital Relays on any Digital Relay Cards RO1S installed in the Shark meter Data Points 3 through 6 are only available if there is at least one Digital Relay Card RO1S installed in the meter The relays on a card in Slot 1 are mapped to Points 3 and 4 The relays on a card in Slot 2 are mapped to Points 5 and 6 If there is no card installed in a slo...

Страница 299: ... the device s time only Object 60 Class Objects Class 0 requests only are supported Objects are returned in the response in the following order Object 20 all points 0 8 32 bit values Object 30 all points count depends on settings 16 bit values Object 1 all points 0 3 8 bit values Object 10 all points 0 6 8 bit values Object 80 Internal Indicators This request supports the clearing of the Restart b...

Страница 300: ...nitial State and has not been updated since Restart Bit 7 STATE 0 Off 1 On Object Point Var Description Format Range Multiplier Units Comments 1 0 2 Read Digital Input 1 RO1S Status 1 expansion port 1 BYTE Bit Flags N A None Returns the Status and State of the Input in the Flags 1 1 2 Read Digital Input 2 RO1S Status 2 expansion port 1 BYTE Bit Flags N A None Returns the Status and State of the In...

Страница 301: ...tion Format Range Multiplier Units Comments 10 0 2 Reset Energy Counters BYTE Always 1 N A None 10 1 2 Change to Modbus RTU Protocol BYTE Always 1 N A None 10 2 2 Reset Demand Counters Max Min BYTE Always 1 N A None 10 3 2 Read Relay 1 State RO1S Relay 1 expansion port 1 BYTE Bit Flags N A None Returns the Status and State of the Relay in the Flags 10 4 2 Read Relay 2 State RO1S Relay 2 expansion ...

Страница 302: ...trol Code 3 only 12 1 1 Change to Modbus RTU Protocol N A N A N A none Responds to Function 6 Direct Operate No Ack Qualifier Code 17x Control Code 3 Count 0 On 0 msec Off 1 msec ONLY 12 2 1 Reset Demand Counters Max Min N A N A N A none Control Code 3 only 12 3 1 Control Relay 1 RO1S Relay 1 expansion port 1 N A N A N A none See Section C 4 for operation rules and parameters 12 4 1 Control Relay ...

Страница 303: ...6 per energy format scale and d number of decimal places Whr example energy format 7 2K and W hours counter 1234567 n 3 K scale d 2 2 digits after deci mal point mul tiplier 10 3 2 101 10 so energy is 1234567 10 Whrs or 12345 67 KWhrs 20 1 5 W hours Negative UINT32 0 to 99999999 Whr 20 2 5 VAR hours Positive UINT32 0 to 99999999 VARhr 20 3 5 VAR hours Negative UINT32 0 to 99999999 VARhr 20 4 5 VA ...

Страница 304: ...N SINT16 0 to 32767 150 32768 V Values above 150V secondary read 32767 30 2 4 Volts B N SINT16 0 to 32767 150 32768 V 30 3 4 Volts C N SINT16 0 to 32767 150 32768 V 30 4 4 Volts A B SINT16 0 to 32767 300 32768 V Values above 300V secondary read 32767 30 5 4 Volts B C SINT16 0 to 32767 300 32768 V 30 6 4 Volts C A SINT16 0 to 32767 300 32768 V 30 7 4 Amps A SINT16 0 to 32767 10 32768 A Values above...

Страница 305: ...768 VA 30 20 4 Angle Phase A Current SINT16 1800 to 1800 0 1 degree 30 21 4 Angle Phase B Current SINT16 1800 to 1800 0 1 degree 30 22 4 Angle Phase C Current SINT16 1800 to 1800 0 1 degree 30 23 4 Angle Volts A B SINT16 1800 to 1800 0 1 degree 30 24 4 Angle Volts B C SINT16 1800 to 1800 0 1 degree 30 25 4 Angle Volts C A SINT16 1800 to 1800 0 1 degree 30 26 4 CT numerator SINT16 1 to 9999 N A non...

Страница 306: ...INT16 1000 to 1000 0 001 None 30 34 4 Power Factor Phase B SINT16 1000 to 1000 0 001 None 30 35 4 Power Factor Phase C SINT16 1000 to 1000 0 001 None 30 36 4 Watts Phase A SINT16 32768 to 32767 4500 32768 W 30 37 4 Watts Phase B SINT16 32768 to 32767 4500 32768 W 30 38 4 Watts Phase C SINT16 32768 to 32767 4500 32768 W 30 39 4 VARs Phase A SINT16 32768 to 32767 4500 32768 VAR 30 40 4 VARS Phase B ...

Страница 307: ...B N SINT16 0 to 32767 1 10 or 100 V 30 3 4 Volts C N SINT16 0 to 32767 1 10 or 100 V 30 4 4 Volts A B SINT16 0 to 32767 1 10 or 100 V 30 5 4 Volts B C SINT16 0 to 32767 1 10 or 100 V 30 6 4 Volts C A SINT16 0 to 32767 1 10 or 100 V 30 7 4 Amps A SINT16 0 to 32767 1 or 10 A Point value Actual Amps divisor 30 8 4 Amps B SINT16 0 to 32767 1 or 10 A 30 9 4 Amps C SINT16 0 to 32767 1 or 10 A 30 10 4 Wa...

Страница 308: ...NT16 1800 to 1800 0 1 degree 30 23 4 Angle Volts A B SINT16 1800 to 1800 0 1 degree 30 24 4 Angle Volts B C SINT16 1800 to 1800 0 1 degree 30 25 4 Angle Volts C A SINT16 1800 to 1800 0 1 degree 30 26 4 CT numerator SINT16 1 to 9999 N A none CT ratio numerator multiplier denomina tor 30 27 4 CT multiplier SINT16 1 10 or 100 N A none 30 28 4 CT denominator SINT16 1 or 5 N A none 30 29 4 PT numerator...

Страница 309: ... Phase C SINT16 32768 to 32767 4500 32768 W 30 39 4 VARs Phase A SINT16 32768 to 32767 4500 32768 VAR 30 40 4 VARS Phase B SINT16 32768 to 32767 4500 32768 VAR 30 41 4 VARs Phase C SINT16 32768 to 32767 4500 32768 VAR Object Point Var Description Format Range Multiplier Units Comments 80 7 1 Device Restart Bit N A N A N A none Clear via Function 2 Write Qualifier Code 0 dst 16 bit frame destinatio...

Страница 310: ...crc Request 05 64 05 C9 dst src crc Reply 05 64 05 0B src dst crc Request 05 64 0E C4 dst src crc Cx Cy 02 50 01 00 07 07 00 crc Reply 05 64 0A 44 src dst crc Cx Cy 81 int ind crc Request 05 64 0B C 4 dst src crc Cx Cy 01 3 C 01 06 crc Request 05 64 14 C 4 dst src crc alter nate Cx Cy 01 3 C 02 06 3 C 03 06 3C 04 06 3C 01 06 crc Reply 05 64 A1 44 src dst crc same for either request Cx Cy 81 int in...

Страница 311: ... 00 00 00 03 00 00 00 00 00 crc 01 00 00 00 00 crc Reply 05 64 1C 44 src dst crc Cx Cy 81 int ind 0C 01 28 01 00 00 00 03 00 00 00 crc 00 00 01 00 00 00 00 crc Request 05 64 18 C4 dst src crc Cx Cy 06 0C 01 17 01 01 03 00 00 00 00 00 01 00 crc 00 00 00 crc No Reply Request 05 64 18 C4 dst src crc Cx Cy 05 0C 01 17 01 02 03 00 00 00 00 00 01 00 crc 00 00 00 crc Reply 05 64 1A 44 src dst crc Cx Cy 8...

Страница 312: ...ied for the Read function Only objects 10 20 30 and 60 are supported Out of Range Occurs for most other errors in a request such as requesting points that don t exist or direct operate requests in unsupported formats Buffer Overflow Occurs if a read request or a read response is too large for its respective buffer In general if the request overflows there will be no data in the response while if t...

Страница 313: ...om a laptop PC This Appendix contains instructions for installing the USB to IrDA Adapter D 2 Installation Procedures The USB to IrDA Adapter comes packaged with a USB cable and an Installation CD 1 Connect the USB cable to the USB to IrDA Adapter and plug the USB into your PC s USB port Your computer s operating system may find the driver for the adapter automatically If it doesn t continue to st...

Страница 314: ... In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 6 You will see the screen below while the application checks your computer s system 7 When it is finished checking you will see the screen below 8 Click Next ...

Страница 315: ... Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 9 If you want to store the driver files in a folder other than the one shown click Change and select a new location Otherwise click Next 10 Click Install You will see the next screen while the driver is being installed ...

Страница 316: ...der In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 11 When the driver installation is finished you will see the screen below 12 Click Finish to close the screen You will see the following message screen ...

Страница 317: ...llation CD until the entire procedure has completed 14 Position the USB to IrDA Adapter so that it points directly at the IrDA on the front of the Shark meter It should be as close as possible to the meter and not more than 15 inches 38 cm away from it 15 You should see a small message on your PC telling you that a computer is nearby This means that the Infrared Adapter has found the meter You may...

Страница 318: ...ver path you need to open the Device Manager this is dependent on your operating system 17 The USB to IrDA Adapter should appear under both Infrared Devices and Modems click on the sign to display all configured modems NOTE If the Adapter doesn t show up under Modems move it away from the meter for a minute and then position it pointing at the meter s IrDA port again 18 Double click on the Standar...

Страница 319: ...olutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 19 Click the Modem tab The Com Port that the Adapter is using is displayed in the screen 20 Use this Com Port to connect to the meter from your PC using the Communicator EXTTM software 21 Open the software and click the Connect icon ...

Страница 320: ...ut with whatever port your adapter is connected to Refer to Chapter 3 of the Communicator EXTTM 4 0 and MeterManager EXT Software User Manual for detailed connection instructions IMPORTANT You must keep the adapter pointing at the meter s IrDA port If it is moved away from the port you will lose connection to the meter In that case re peat step 21 to re connect to the meter you may need to click t...

Страница 321: ...finitions that provide a stan dardized method of communication and integration to support intelligent electronic devices from any vendor networked together to perform protection monitoring automation metering and control in a substation environment For more information on IEC 61850 go to http iec61850 ucaiug org IEC 61850 was developed to Specify a design methodology for automation system construc...

Страница 322: ...derstanding of the roles of clients and servers and publishers and subscribers is key to the use of IEC 61850 devices A client is the requester sink of information while the server is the responder source of information Information generally flows on a request response basis with the client issuing the request and the server issuing the response However the con cept of servers is extended to provi...

Страница 323: ...er and sub scriber The publisher subscriber relationship differs from the client server in that there is no explicit one to one relationship between the information producer and consumer Publishers issue data without knowledge of which devices will consume the data and whether the data has been received Subscribers use internal means to access the published data From the viewpoint of IEC 61850 the...

Страница 324: ...ther hardware is entered on another level The structure of the IEC 61850 network is composed of different kinds of files each containing information that the system needs in order to function IEC 61850 configu ration uses text based XML files known as the System Configuration Language SCL SCL files use the concept of an XML schema which defines the structure and content of an XML file The schema u...

Страница 325: ...scription of the configured automation system including all devices for example meters breakers and relays and all needed inter device communications for example the measured parameters and the actions to be performed such as turning on a relay when a certain reading is obtained It can also include elements of the SSD file The SCD file is created by a System Configurator which is a software applic...

Страница 326: ...x Data Objects represent real world information possibly grouped by electrical object The IEC 61850 standard has specific semantics for each of the DOs For example the DO named PhV represents the voltage of a point on a three phase power system The DOs are composed of standardized Common Data Classes CDCs which are groups of low level attributes of the objects For example the DO named Hz represent...

Страница 327: ...e IP address subnet mask and IP gateway of the device Datasets the user must decide which information within the IED will be included in reports etc and place this information into datasets The System Configura tor should allow the selection of information using a pick list from information within the ICD file 2 The resulting SCD file is then imported by vendor specific tools into the various devi...

Страница 328: ...ing individual device parameters such as analog deadbands The System Configurator then creates a SCD file with a consistent view of the entire system In step 2 the SCD file is used to configure each device using vendor supplied tools Vendors are free to choose the configuration mechanism but the configuration infor mation MUST be derived from the SCD file NOTE In the Shark 200 meter s IEC 61850 Pr...

Страница 329: ...e Logical Nodes implemented within the Logical Device include the standard LLN0 and LPHD1 with optional standard logical nodes in the M class ex MMXU and T class ex TVTR Each Logical Node contains only standardized objects of standardized types Common Data Class CDC The device is based upon the first edition of the IEC 61850 standards Examples of Logical Nodes within the Shark 200 family include e...

Страница 330: ..._mag_noDC which in turn has the object phsA which again has an attribute named instVal to represent instantaneous values and also the mag attribute which represents the magnitude as an analog magnitude with the attribute f to get the value in 32 bit floating point Thus the voltage of phase A would be referred in this nested structure as Meas nsMMXU1 PhV phsA instVal mag f The node nsMHAI1 groups t...

Страница 331: ...hould be stored in the Shark 200 meter in order to configure the server At power up the server reads the file parses it and configures all the internal settings for proper functionality Storing the CID file in the Shark 200 meter is accomplished through its webpage The webpage allows the user to locate the CID file and submit it to the Shark 200 meter for storage The Shark 200 meter does not need ...

Страница 332: ...202004 20Presentations zip IEC618650 Presentation IEC 61850 û Data Model and Services pdf http www ucaiug org Meetings Austin2011 Shared 20Documents IEC_61850 Tutorial pdf pages 24 32 and 40 161 http brodersensystems com wordpress wp content uploads DTU Master Thesis RTU32 pdf pages 9 36 Additionally there is a good article on the predecessor to IEC 61850 UCA 2 0 at http www elp com index display ...

Страница 333: ...documents TMW 2061850 20Test 20Suite 20Combined pdf Clients and servers for IEC 61850 http www omicron at en products pro communication protocols iedscout test client http kalkitech com products sync 6000 series scl manager iec61850 substa tion design tool SCL editing tool E 2 Using the Shark 200 Meter s IEC 61850 Protocol Ethernet Network Card This section contains instructions for understanding ...

Страница 334: ...able via the CID file XML formatted Embedded Capabilities File ICD downloadable from the unit Supports MMS protocol Supports the following Logical Nodes LLN0 with predefined Sets and Reports LPHD Identifiers MMXU with Phase to N Voltages Phase to Phase Voltages Phase Currents Per Phase VA Total VA Per Phase Var Total Var Per Phase W Total W Per Phase PF Total PF Frequency MHAI with Per Phase THD M...

Страница 335: ...ceptacles Turn on the Shark 200 unit After about 10 seconds the Link LED near the RJ45 Ethernet connector on the IEC 61850 Protocol Ethernet Network card will light which means a link has been established to your network and the Shark 200 meter has correctly identified the IEC 61850 Protocol Ethernet Network card The first time you connect it may take up to one minute for the link to be establishe...

Страница 336: ...ddresses for the NTP Network Time Protocol if not needed you can leave this field blank The IP address of the NTP server on your network or the URL if you configured the DNS in the previous entry field NOTE The network card supports NTP version 4 0 client server mode up to Net work card firmware version 3 44 Starting in version 3 45 the network card works with NTP version 3 0 or 4 0 autodetect in ...

Страница 337: ...s GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 2 Click the Profile icon to open the meter s Device Profile screen The profile is retrieved from the Shark 200 meter ...

Страница 338: ... Network Option card Option Card 1 or Option Card 2 then click Comm Network IP Addresses and DNS 4 Fill in the information on this screen Computer Name the name of the device on the network accessed through the Network card IP Address the IP v4 address for the unit on the network Subnet Mask the IP v4 mask which identifies the sub network to which the unit belongs Default Gateway the IP v4 address...

Страница 339: ...ch is selected and enabled through the Time Settings screen If you enter an NTP server on this screen you still need to enable it in the Time Set tings screen see the instructions in Chapter 5 Communication Installa tion on page 5 1 See 8 4 3 NTP Time Server Synchronization on page 8 24 for additional information on NTP All of these parameters must be properly set up in order to allow the Shark 20...

Страница 340: ... is now configured properly to work on an IEC 61850 network NOTE The INP300S Network card with Network Firmware version 3 43 and higher offers enhanced security with the Exclusive Client feature which lets you Whitelist an IP address or MAC address When that address is used to connect to the meter all other network communication with the meter through the same Network card is suspended This ensure...

Страница 341: ...ork IP address This icd file will be processed with the rest of the system clients other meters switches breakers etc in the network and the resulting file which will be uploaded to the meter to configure it is the Configured IED Description file cid file The IP address for the Shark 200 meter is contained in the Communication section of this cid file See the example Communication section below NO...

Страница 342: ...ld in the ConnectedAp section underlined in the example is the same as the name field defined in the IED section This is how the unit is assigned its name and IP address 1 The Shark 200 meter s icd file can be downloaded directly from the Shark 200 unit To do this use a web browser and enter http aa bb cc dd where aa bb cc dd is the IP address assigned to the IEC 61850 Protocol Ethernet Network ca...

Страница 343: ... icd file Right click the Here right click to Save As link and save a copy of the icd file on your computer An example of a downloaded icd file is shown below xml version 1 0 encoding UTF 8 SCL xmlns http www iec ch 61850 2003 SCL xmlns xsi http www w3 org 2001 XMLSchema instance xsi schemaLocation http www iec ch 61850 2003 SCL SCL xsd xmlns ext http nari relays com Header id Shark 200 ICD nameSt...

Страница 344: ...ype IP xsi type tP_IP 10 0 0 24 P Address ConnectedAP SubNetwork Communication IED name SHARK200IEC desc Electro Industries Shark 200 type S200 manufacturer ElectroIndustries configVersion 1 00 Services DynAssociation 4 Once the System Integrator has processed the Shark 200 meter s icd file and the information of the other devices on the network using either automated tools or manually the final r...

Страница 345: ...0KB Avoid putting too many comments or unnecessary historical information into the file If the file is bigger than 250KB it will be rejected by the IEC 61850 Protocol Ethernet Network card The sAddr fields in each object of the icd file must be preserved when generating the cid file Do not change these because they are used internally by the IEC 61850 server If the cid file has more than one IED d...

Страница 346: ... Protocol Ethernet Network card s main webpage Information webpage has general information on the status of the card e g version healthy serial number and the status of the IEC 61850 server e g ok errors in the uploaded cid file In addition to this information there is a System log which contains events e g errors and warnings from the IEC 61850 protocol layer including problems found when parsing...

Страница 347: ...he Upgrade file Make sure that you select the INP300S option card upgrade file If you upgrade with the INP100S upgrade file the card will work but most IEC 61850 features will be disabled In that case perform the upgrade again using the correct INP300S upgrade file 2 Enter the Safety Code 3 Enter the Upgrade Password the default is n3tUp 0Ad for firmware runtime version 3 35 and later and eignet20...

Страница 348: ... Ethernet Network card you can use the Reset Network Card webpage 1 Click Reset Network Card from the bottom of the Information webpage 2 You will see a screen similar to the one shown above Enter the Reset Password the default is adminR35et for firmware runtime version 3 35 or later and r2d2andc3po for earlier firmware runtime versions See the note on page A 21 3 Click the Reset button The Networ...

Страница 349: ...eature is used by the TCP IP layer for detecting broken connections Once detected the connection is closed in the Network card and the server port is freed This prevents the card from running out of server connections due to invalid links See 8 4 5 Keep Alive Feature on page 8 24 for instructions on configuring this feature E 7 Testing You can use any IEC 61850 certified tool to connect to the Sha...

Страница 350: ...d file is too small it does not contain the min imum necessary description Check to ensure the file is not trimmed Sometimes an ille gal character non ASCII makes the file look smaller Verify that the entire file can be read 16969 TOOBIG The uploaded file is too big it does not fit in the reserved area for the CID file Check to ensure the file is correct Try to delete large com ment sections or hi...

Страница 351: ... Monitoring and Smart Grid Solutions 17985 FAILED The upload failed This can be because of network linkage problems or failed integrity in storage Try to upload the file again DO NOT click the back but ton on the browser if the update is not completed Assure that the network link is stable If the problem persists contact EIG s tech nical support Code Name Description Required Action ...

Страница 352: ...e IEC61850 Network Card Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...