12/30/2020 2
EI916
Specification Tables
Temperature Rise & CFM Chart
Model
SINGLE PHASE MODELS
MB01
MB02
CFM
CFM
Required
Temp
Rise
80° F
39
63
70° F
45
72
60° F
53
84
50° F
63
101
40° F
79
126
30° F
105
168
Specifications
Model
kW
Btu/h
Amps
Internal
CB
Motor
FLA
Motor
HP
Phase
Voltage
CFM
Max Fuse/
HACR
Duct
Connection
Max
Static
EM-MB01-120-1-06 1 3,412 8.3
N/A
0.5 1/18 1-50/60
Hz 120 150 0.03” 15A
6”
EM-MB02-120-1-06 1.6 5,459 13.3
N/A
0.5
1/18 1-50/60
Hz 120 150 0.03” 20A
6”