Product Description
This is a self-contained package with a permanent (washable) air filter, electric heating elements,
modulating element temperature control, powered damper and fan. This product has been designed
specifically for outside air inlet.
All models include WarmFlo electronic outlet temperature sensor and associated control circuitry to
modulate the electric elements for a fixed outlet temperature. This means the electric element is only used
to make-up or heat the outside fresh air to the preset temperature point. There is no overheating or
inefficient use of the electric element.
Heating elements are locked out when this unit’s outlet air temperature is greater than the set point dial
switch.
Diagrams used throughout the installation manual represent general installation requirements. Due to
various model sizes available, actual unit mechanical and wiring requirements will vary dependent upon
specific model.
Handling & Storage
Receiving
It is the receiver’s (person and/or company signing off on the receiving Bill of Lading) responsibility to
inspect for shipping damage. All shipping claims must be made by the receiver.
Storage
Packed or unpacked, the Make-Up Air unit shall not be exposed to rain, snow, or other adverse
environment. This product is designed for in-building storage and installation only.
As much as possible this product must be protected throughout the construction phase to avoid
accumulation of dust and moisture on the components and control box. The installing contractor is
responsible for maintaining the cleanliness and quality of this unit until installation is complete and
approved by the user/end customer.
Placement & Mechanical Information
This product is designed for zero clearance, but use the following mounting and spacing criteria:
1.
Unit can be installed vertically or horizontally. When vertical, inlet must face down.
2.
Make mounting provisions for a 1” air space at the top.
3.
The sides, any location, can be in direct contact with wood framing materials.
4.
No materials shall be in contact with the cabinet housing which has a flame point less than wood,
300°F (150°C).
5.
Product shall be installed in a conditioned space only.
6.
Heating elements are locked out when outlet air temperature is > set point dial switch.