MI
OUTPUTS
(24V
A
C
/ 2A
MAX)
115VAC / 60Hz
CLOCK
CONTROLLER
(1A
MAX)
L1 (BLK)
L2 (RED)
*G (SHIELD)
C (WHT)
99B-MI
"CMI" BOARD
(1 PER CLOCK)
"CMI" BOARD
(1 PER CLOCK)
TO
ADDITIONAL
CLOCKS
LINE (BLK)
NEUTRAL (WHT)
GROUND (G)
*Shield Connects
ONLY at 99B-MI
CLASS II (24VAC)
16 AWG WIRE
RECOMMENDED
SYSTEM CLOCKS : "MI" OPERATION
LOCAL
DISCONNECT
{BY OTHERS}
CLOCK ILLUMINATION
115VAC / 60Hz
LINE (BLK)
NEUTRAL (WHT)
GROUND (G)
PHOTOCELL
OR
LIGHTING CONTROL
{BY OTHERS}
L1 (BLK)
L2 (RED)
*G (SHIELD)
C (WHT)
L1 (BLK)
L2 (RED)
*G (SHIELD)
C (WHT)
CONTROL WIRING
ILLUMINATION WIRING
(IF APPLICABLE)
"HOME RUNS" REQUIRED
ALL "MI" CLOCKS
CONTROL SPECIFICATIONS
1) CONTROLS UP TO (4) "MI" CLOCKS
2) MAX CONTROL WIRE RUN 350'
3) "HOME RUNS" REQUIRED FROM EACH CLOCK
4) DEDICATED 115VAC BRANCH CIRCUIT MUST
BE PROVIDED FOR 99B-MI CONTROLLER
5) CONNNECTIONS FOR 1/2" CONDUIT PROVIDED
06-01-2009
Electric
T
ime Company
, inc. Medfield, MA
02052 USA
Ph: (508) 359-4396 Fax: (508) 359-4482
www
.electrictime.com