2.2 DUO
24+24
Model Indoor Unit
WNG 24+24
Model Outdoor Unit
DUO 24+24 R410A RC
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Capacity
(4)
Btu/hr
22180*2
24230*2
kW
6.55*2
7.10*2
Power input
(4)
kW
4.65
4.81
EER (Cooling) or COP(Heating)
(4)
W/W
2.82 2.95
Energy efficiency class
C
D
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Rated current
A
20.3
21.0
Starting current
A
63 / 63
Circuit breaker rating
A
30
INDOOR
Fan type & quantity
Cross flow*1
Fan speeds
H/M/L
RPM
1300/1200/1100
Air flow
(1)
H/M/L
m3/hr
910/820/740
External static pressure
Min-Max
Pa
N/A
Sound power level
(2)
H/M/L
dB(A)
60/57/55
Sound pressure level
(3)
H/M/L
dB(A)
47/44/42
Moisture removal
l/hr
2.8
Condenstate drain tube I.D
mm
16
Dimensions
WxHxD
mm
1060x295x210
Weight
kg
16
Package dimensions
WxHxD
mm
1125x360x280
Packaged weight
kg
18
Units per pallet
units
16
Stacking height
units
8
OUTDOOR
Refrigerant control
Capillary tube
Compressor type,model
NN27VBAMT
Fan type & quantity
Propeller(direct) x 2
Fan speeds
H/L
RPM
830
Air flow
H/L
m3/hr
4950
Sound power level
H/L
dB(A)
72
Sound pressure level
(3)
H/L
dB(A)
61
Dimensions
WxHxD
mm
950X1270X340
Weight
kg
110
Package dimensions
WxHxD
mm
1110X1425X480
Packaged weight
kg
130
Units per pallet
Units
1
Stacking height
units
1
Refrigerant type
R410A
Refrigerant chargless distance
kg/m
2.15kg/7.5m
Additional charge
4≤L≤10:+0g;10<L≤15:+450g;15<L≤20:+580g
Connections between units
Liquid line
In.(mm)
3/8”(9.53)
Suction line
In.(mm)
5/8”(15.88)
Max.tubing length
m.
20
Max.height difference
m.
15
Operation control type
Remote control
Heating elements
kW
Others
(1)Airflow in ducted units;at nominal external static pressure.
(2)Sound power in ducted units is measured at air discharge.
(3)Sound pressure level measured at 1-meter distance from unit.
(4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
Содержание DUO 18+18 RC
Страница 23: ...12 1 TROUBLESHOOTING Revision Y06 01 Service Manual DUO Series 12 TROUBLESHOOTING...
Страница 24: ...12 2 TROUBLESHOOTING Revision Y06 01 Service Manual DUO Series...
Страница 30: ......
Страница 31: ......