2-1
PRODUCT DATA SHEET
Revision Y06-01
Service Manual - DUO Series
2. PRODUCT
DATA
SHEET
2.1 DUO
18+18
Model Indoor Unit
WNG 18+18
Model Outdoor Unit
DUO 18+18 R410A RC
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Capacity
(4)
Btu/hr
18250*2
18600*2
kW
5.35*2
5.45*2
Power input
(4)
kW
3.32
3.32
EER (Cooling) or COP(Heating)
(4)
W/W
3.22 3.28
Energy efficiency class
A
C
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Rated current
A
14.7
14.7
Starting current
A
32 / 32
Circuit breaker rating
A
30
INDOOR
Fan type & quantity
Cross flow*1
Fan speeds
H/M/L
RPM
1200/1100/1000
Air flow
(1)
H/M/L
m3/hr
890/800/700
External static pressure
Min-Max
Pa
N/A
Sound power level
(2)
H/M/L
dB(A)
57/54/52
Sound pressure level
(3)
H/M/L
dB(A)
44/41/38
Moisture removal
l/hr
2
Condenstate drain tube I.D
mm
16
Dimensions
WxHxD
mm
1060x295x210
Weight
kg
14
Package dimensions
WxHxD
mm
1125x360x280
Packaged weight
kg
17
Units per pallet
units
16
Stacking height
units
8
OUTDOOR
Refrigerant control
Capillary tube
Compressor type,model
Rotary TOSHIBA PA200X2CS-4KU1
Fan type & quantity
Propeller(direct) x 2
Fan speeds
H/L
RPM
780
Air flow
H/L
m3/hr
4500
Sound power level
H/L
dB(A)
70
Sound pressure level
(3)
H/L
dB(A)
60
Dimensions
WxHxD
mm
950X1270X340
Weight
kg
110
Package dimensions
WxHxD
mm
1110X1425X480
Packaged weight
kg
130
Units per pallet
Units
1
Stacking height
units
1
Refrigerant type
R410A
Refrigerant chargless distance
kg/m
1.57kg/7.5m
Additional charge
4≤L≤10:+0g;10<L≤18:+230g;18<L≤25:+430g
Connections between
units
Liquid line
In.(mm)
1/4”(6.35)
Suction line
In.(mm)
1/2”(12.7)
Max.tubing length
m.
25
Max.height difference
m.
15
Operation control type
Remote control
Heating elements
kW
Others
(1)Airflow in ducted units;at nominal external static pressure.
(2)Sound power in ducted units is measured at air discharge.
(3)Sound pressure level measured at 1-meter distance from unit.
(4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).