![Electra DELTA 22 Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/electra/delta-22/delta-22_service-manual_2378837022.webp)
5-8
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02
Service Manual - Delta DCI
5.4.3
Heating Capacity (kW) - Run Mode
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB TEMPERATURE [
o
C]
OD COIL
ENTERING
AIR DB/WB
TEMPERATURE
[
o
C]
DATA
15
20
25
-15/-16
TC
3.37
3.14
2.90
PI
0.93
1.02
1.12
-10/-12
TC
3.76
3.52
3.28
PI
1.12
1.22
1.31
-7/-8
TC
4.04
3.81
3.57
PI
1.26
1.36
1.45
-1/-2
TC
4.18
3.95
3.71
PI
1.34
1.43
1.53
2/1
TC
4.28
4.04
3.81
PI
1.38
1.48
1.57
7/6
TC
5.54
5.30
5.06
PI
1.46
1.55
1.64
10/9
TC
5.84
5.60
5.37
PI
1.54
1.64
1.73
15/12
TC
6.14
5.91
5.67
PI
1.63
1.72
1.82
15-24
TC
85 - 105 % of nominal
(Protection Range)
PI
80 - 120 % of nominal
LEGEND
TC –
Total Heating Capacity, kW
PI
– Power Input, kW
WB –
Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OU –
Outdoor
5.4.4 Capacity
Correction
Factors
Heating Capacity Ratio Vs. Outdoor Temperature
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
-15
-10
-5
0
5
10
15
Outdoor WB Temperature [deg C]
Ca
p
a
c
it
y
R
a
ti
o
n
Содержание DELTA 22
Страница 14: ...4 3 OUTLINE DIMENSIONS Revision Y05 01 Service Manual Delta DCI 4 5 Outdoor Unit DCR 50 DCI...
Страница 43: ...9 2 REFRIGERATION DIAGRAMS Revision Y05 02 Service Manual Delta DCI 9 1 2 Delta 25 35 DCR 25 35 DCI EEV EEV...
Страница 44: ...9 3 REFRIGERATION DIAGRAMS Revision Y05 02 Service Manual Delta DCI 9 1 3 Delta 50 DCR 50 DCI EEV EEV...