5-21
PERFORMANCE DATA
Revision Y05-01
Service Manual - COMPACT
5.1 IOD12/CON12
R22
5.1.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OD Coil(
o
C)
Data
ENTERING AIR WB/DB ID Coil(
o
C)
15/21
17/24
19/27
21/29
23/32
15
(1)
TC
4.06 4.20 4.30 4.40 4.47
SC
2.51 2.61 2.72 2.78 2.84
PI
0.90 0.90 0.90 0.91 0.91
20
(1)
TC
3.93 4.14 4.27 4.37 4.46
SC
2.46 2.59 2.70 2.78 2.83
PI
0.98 0.98 0.98 0.99 0.99
25
TC
3.71 4.01 4.22 4.34 4.45
SC
2.39 2.54 2.68 2.76 2.81
PI
1.06 1.06 1.07 1.08 1.09
30
TC
3.47 3.78 4.09 4.23 4.36
SC
2.32 2.46 2.62 2.70 2.75
PI
1.14 1.16 1.17
1.18 1.19
35
TC
3.22 3.49
3.85
4.04 4.23
SC
2.20 2.36
2.56
2.63 2.69
PI
1.23 1.25
1.27
1.27 1.29
40
TC
2.92 3.18 3.47
3.80 3.99
SC
2.08 2.24 2.42 2.50 2.55
PI
1.33 1.35 1.37 1.39 1.40
46
TC
2.54 2.77 3.05 3.37 3.63
SC
1.91 2.05 2.21 2.29 2.34
PI
1.45 1.47 1.50 1.53 1.54
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible
Capacity,
kW
PI –
Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OD –
Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, an A.S.K Kit is required.
Содержание CON 12
Страница 44: ...9 1 ELECTRICAL CONNECTIONS Revision Y05 01 Service Manual COMPACT 9 ELECTRICAL CONNECTIONS 9 1 COMPACT 7 9 12...
Страница 100: ...14 18 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y05 01 Service Manual COMPACT 14 18 Outdoor Unit CON 12 ST R22 R407C...
Страница 104: ...15 2 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual COMPACT...
Страница 105: ...15 3 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual COMPACT...
Страница 106: ...15 4 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual COMPACT...
Страница 107: ...15 5 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual COMPACT...
Страница 110: ...AIR CONDITIONER SPLIT WALL MOUNTED PROGRAMMING AND OPERATING...
Страница 128: ......
Страница 129: ......