5-17
PERFORMANCE DATA
Revision Y05-01
Service Manual - COMPACT
5.13 IOD9/CON9
R22
5.13.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OD Coil(
o
C)
Data
ENTERING AIR WB/DB ID Coil(
o
C)
15/21
17/24
19/27
21/29
23/32
15
(1)
TC
2.67 2.76 2.83 2.89 2.94
SC
1.70 1.78 1.85 1.89 1.93
PI
0.69 0.69 0.69 0.69 0.70
20
(1)
TC
2.58 2.72 2.81 2.87 2.93
SC
1.67 1.76 1.84 1.89 1.92
PI
0.75 0.75 0.75 0.76 0.76
25
TC
2.44 2.64 2.77 2.85 2.92
SC
1.63 1.73 1.82 1.87 1.91
PI
0.81 0.81 0.82 0.82 0.83
30
TC
2.28 2.49 2.69 2.78 2.86
SC
1.58 1.68 1.78 1.83 1.87
PI
0.87 0.88 0.89
0.90 0.91
35
TC
2.11 2.29
2.53
2.66 2.78
SC
1.50 1.61
1.74
1.79 1.83
PI
0.94 0.95
0.97
0.98 0.98
40
TC
1.92 2.09 2.28
2.50 2.62
SC
1.41 1.52 1.65 1.70 1.73
PI
1.01 1.03 1.05 1.06 1.07
46
TC
1.67 1.82 2.00 2.22 2.39
SC
1.30 1.39 1.50 1.55 1.59
PI
1.11 1.12 1.15 1.16 1.18
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible
Capacity,
kW
PI –
Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OD –
Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, an A.S.K Kit is required.
Содержание CON 12
Страница 44: ...9 1 ELECTRICAL CONNECTIONS Revision Y05 01 Service Manual COMPACT 9 ELECTRICAL CONNECTIONS 9 1 COMPACT 7 9 12...
Страница 100: ...14 18 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y05 01 Service Manual COMPACT 14 18 Outdoor Unit CON 12 ST R22 R407C...
Страница 104: ...15 2 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual COMPACT...
Страница 105: ...15 3 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual COMPACT...
Страница 106: ...15 4 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual COMPACT...
Страница 107: ...15 5 OPTIONAL ACCESSORIES Revision Y05 01 Service Manual COMPACT...
Страница 110: ...AIR CONDITIONER SPLIT WALL MOUNTED PROGRAMMING AND OPERATING...
Страница 128: ......
Страница 129: ......