Controller main operating modes

Heating mode

To start the appliance in this mode, use button 1.
In this mode, the convector heater shall maintain the temperature set. Message in field Operating mode - no 
message. The display shows the current measured and set temperatures, the power indicator scale, the time, 
and date.

Standby

 mode

To start the appliance in this mode, use button 1.
In this mode, when the measured temperature falls below the temperature set, the heater shall not switch on. 
However, when the temperature drops below 7° C, the 

 mode is activated. 

Antifr

ost

 mode

Message in field Operating mode - 

Standby

The current measured temperature, time, and date are shown on the display. 

Delayed Start mode

Message in field Operating mode - 

Standby

When the convector heater is in OFF mode, pressing and holding for 

2

 seconds on the ▲ button allows you to 

enter time when the appliance shall switch on automatically. The time is set in 10 minutes steps. The delayed 
start can be programmed up to 24 hours. At entry in Delayed Start mode setting, the default time is the current 

time, rounded up to 10 minutes, and then pressing the ▲ or ▼ buttons you may increase or decrease the time by steps of 10 minutes. If 
any of the ▲ or ▼ buttons is held for more than 0.7 seconds, the value automatically starts to increase or decrease at 4 units per second. 
When the Delayed Start mode is activated, in the middle of the display is shown the turn-on time. If you want to adjust the preset time, hold 
down the ▲ button again. The Delay Start mode is canceled by pressing the On / Off button. The convector heater shall then switch to 
Heat mode. When the power is turned off while the Delay Start mode is on, the controller shall store the delay time. If the set time shall 
occur before the power is restored, then the controller shall remain in OFF state when the power is restored.

Antifr

ost

 mode

This function shall switch on the convector heater automatically and independently of the selected mode

 (if the checkbox "Antifrost" in 

"System settings" is marked)

 when the room temperature drops below 7°C. For this purpose, the convector heater must be plugged into 

the mains and the 

 must be in the "I" position. When activating this mode, a minimum room temperature of 

c

onvector heater on / off switch

7°C shall be maintained. 
Message in field Operating mode - 

Antifr

ost

When the room temperature raises above 7°C, the Anti-freeze safety mode switches off.

Sleep mode

In this mode the convector heater shall, within 2 hours, automatically and gradually decrease with 3 degrees the temperature set. This 
mode activates by pressing and holding button 2 for more than 2 seconds when the convector is in Heat mode. When this mode is 
activated for five seconds in the display middle field is shown Sleep Mode On, then the display takes the appearance of Heat mode.
Message in field Operating mode - 

Sleep.

The sleep mode is interrupted by pressing button 1 when the convector heater is switched off. The Sleep mode will turn itself off after 6 
hours!

Timer

s

 mode / Program mode

The controller has a built-in weekly programmer that allows you to create seven independently set operating time intervals, and each 
interval can be repeated over the days of the week. The weekly programmer can operate in two modes - Timer and Program. Switching 
from one mode to the other is possible by changing the 

Timer

s

 setting in the sub-menu 

System

 

When the setting is 

On

/Off

, the controller 

is in the Timer

s

 mode, with only start and end of the time intervals and the days of the week for which it is valid.

Message in field Operating mode - 

Timer

s

When the setting 

of Timers in System 

is 

Change

 t

, the controller is in the Program mode, where, in addition to the start and end of the time 

intervals and days of the week for which the program applies, a temperature may be entered. 

Message in field Operating mode - 

Program

Each program or timer set can be activated / deactivated. When introducing a start and an end it must be borne in mind that the controller 
does not allow the end time to be before the start one.
With a weekly programmer set, hold the OK button for more than 2 seconds and all timers set shall be deactivated by displaying the Timer 
Stop message for 5 seconds, then the convector shall switch to Heat mode without a weekly programmer.

17

EN

EN

Содержание RH01F

Страница 1: ...EN ONDERHOUD Dit product is uitsluitend geschikt voor goed ge soleerde plaatsen of voor incidenteel gebruik ELECTRIC CONVECTOR HEATER page 13 TECHNICAL DESCRIPTION INSTALLATION OPERATION AND MAINTENA...

Страница 2: ...W 265 551 RH01F20W S B NL Minimumafstanden tussen de convectieverwarmer en de omliggende objecten mm EN Dimensions and minimum distance between the convector and surrounding objects mm 688 Elektrisch...

Страница 3: ...3 3 8 3 8 3 BG BG...

Страница 4: ...50 1 3 5 2 2 4 BG BG...

Страница 5: ...230 V 5 1 10 1000m RH01F20M W C 4 I 800W II 1200W I II 2000W II 0 4 1 7 max 4 4 4 8 C II 5 BG BG...

Страница 6: ...RH01F20W S B 1 2 3 4 2 2 2 2 2 5 1 1 2 1 2 3 4 1 1 0 1 2 24 4 40 Language 2 OK SW ver yyy HW ver yyy ETP 01 2 1 OK OK OK OK 1 T 6 BG BG...

Страница 7: ...1 1 7 2 10 24 10 10 0 7 4 On Off Antifrost 7 I 7 7 C 2 3 2 2 5 1 6 t 2 5 BG 7...

Страница 8: ...2 3 28 e 7 5 2 3 0 7 4 1 7 1 Smart Smart 15 60 1 Wifi 1 10 30 1 OK 2 8 BG BG...

Страница 9: ...OK 7 4 WiFi WiFi WiFi TS TS WiFi WiFi WiFi WiFi WiFi Eldom Eldom Google Play pp Stor e Android 8 0 Eldom WIFI 3 1 WiFi 2 9 BG BG...

Страница 10: ...WIFI WiFi AP 2 GPS WiFi WiFi ELD Incotex123 WiFi 1 WiFi D 3 Eldom Local Add new device OK OK Syst sett NetworkSettings For connection via the Internet Save WiFi WiFi WiFi Eldom viaInternet e Eldom 10...

Страница 11: ...1 2 2 24 24 BG BG 11...

Страница 12: ...NA NA NA NA 2015 1188 II 3 a RH01F20M W Pnom kW 2 0 Pmin 0 8 kW Pmax c 2 0 kW elmax 2 0 kW elmin 0 8 kW elSB 0 kW NA NA NA NA RH01F20W S RH01F20W B 2 0 2 0 2 0 2 0 0 0 001 www eldominvest com BG BG 12...

Страница 13: ...ge between 3 three and 8 eight years must be allowed only to switch on and off the appliance under condition that it is located or installed within expected position for normal operation and children...

Страница 14: ...recovery and recycling of this product please contact your local city office your household waste disposal service or the shop where you purchasedtheproduct HEATERTECHNICALDESCRIPTION The electric con...

Страница 15: ...tat knob pos E on fig 4 in direction from 1 to 7 on the scale You may decrease temperature by turning the knob in opposite direction When reaching the desired room temperature turn the thermostat knob...

Страница 16: ...ores the last active operating mode for an unlimited period of time before shutting down the device and always starts with the same when switched on again The controller also has the ability to save i...

Страница 17: ...the room temperature drops below 7 C For this purpose the convector heater must be plugged into the mains and the must be in the I position When activating this mode a minimum room temperature of con...

Страница 18: ...e mode to the other is done by changing the setup Open window in sub menu System Settings When the setting is Smart the convector heater shall continue heating as soon as it detects that the window is...

Страница 19: ...ional and is not specifically required for the operation of the convectorheaterasintended Termsusedinthissectionare module theWiFimoduleoftheelectronicthermoregulator electroniccontrol ofyourconvector...

Страница 20: ...account usernameandpassword SERVICEANDMAINTENANCE Nevercleanconvectorwhilepluggedin whenrunningorhot In order to preserve the unit technical characteristics and to prevent overheating is necessary fo...

Страница 21: ...ases whenanonauthorizedpersonhastriedtorepairanykindofadefect Intheabovecasesthedefectwillberepairedagainstrelativepayment Warrantyshallnotapplytonormalwearpartsandcomponentsofthedevice partsthatarebe...

Страница 22: ...ectronic room temperature control plus week timer no Other control options room temperature control with presence detection no room temperature control with open window detection no with distance cont...

Страница 23: ...trueerd door een persoondieverantwoordelijkisvoorhunveiligheid Hetspuitenen ofspoelenmetvloeistoffenisverboden Dekinderenmogennietspleenmethettoestel Kinderenjongerdan3jaarmogenzichnietindebuurtvanhet...

Страница 24: ...tlijn van het Europees Parlement betreffende afgedankte elektrische en elektronische apparatuur AEEA Na uitputting van de levensduur van het toestel dient u ervoor zorgen dat dit toestel volgens de vo...

Страница 25: ...De uitschakeling van bedrijfsmodus gebeurt op dezelfde manier door het ene einde van detoetsmetdemarkering 0 intedrukken LETOP Deschakelaarvoorkeuzevanhetvermogeniseenfunctioneletoets Devolledigeuitsc...

Страница 26: ...e bedrijfsmodus het hoofdscherm met de temperatuur datum tijd en aanvullende informatie weergegeven De regelaar slaat de laatste actieve modus op voordat u het toestel voor onbepaalde tijd uitschakelt...

Страница 27: ...tievakje Antivorst in Systeeminst isaangevinkt alsdekamertemperatuuronder7 Cdaalt Hiervoormoetdeconvectormetstroomwordenverzorgdende mechanischeschakelaarindestand I zijn Bijdeactiveringvandezefunctie...

Страница 28: ...deplaatswasendanineensopeenveelwarmereplaatswordtgeplaatst Functie Openraam Openwindow De regelaar heeft een ingebouwde functie voor het herkennen van een open raam die de verwarming automatisch stopt...

Страница 29: ...llen van het toestel is geactiveerd De klok is niet juist ingesteld De weekprogrammeur werkt niet AANSLUITING VAN ELEKTRISCHE CONVECTOR MET ELEKTRONISCHE AANSTURING EN WIFI MODULEMETINTERNETAFSTANDSBE...

Страница 30: ...ofschakelovernaarmobieledata SelecteerinhetmenuNieuwWiFi netw opderegelaardemodusWiFiaan Door deze stappen uit te voeren wordt uw convector verbonden met het Eldom afstandsbedienings en bewakingssyste...

Страница 31: ...stgebruik elektrischenetspanning verschillendvandenominalewaardenvoorgebruik schadetengevolgevanhetbevriezen natuurrampen calamiteiten rampenofanderegevallenvanovermacht hetnietnalevenvandehandleiding...

Страница 32: ...tijdschakelaa neen Elektronische sturing van de kamertemperatuur plus week tijdschakelaar neen Andere sturingsopties Sturing van de kamertemperatuur met aanwezigheidsdetectie neen Sturing van de kamer...

Отзывы: