6
GB DIP-804/00 /2
(SIMULATION)
FUNCTION PERFORMED
INTERVENTION SIMULATION
(WITH INDICATOR ON
PROTECTIONS ARE ACTIVE)
FUNCTIONS INTERVENTION
(STOP, GENERAL ALARM
AND VISUAL INDICATOR ON)
RECHARGE
ALTERNATOR
(BELT BREAKAGE)
LOW OIL
PRESSURE
OVERHEATING
FUEL RESERVE
AFTER 3 SECONDS
IMMEDIATELY
IMMEDIATELY
AFTER 3 SECONDS
THE RELEVANT INDICATOR
WILL LIGHT UP WITHOUT
STOPPING THE ENGINE
DISCONNECT THE WIRE FROM
TERMINAL [8] OF THE DEVICE AND
CONNECT TERMINAL [8] TO EARTH
DISCONNECT THE WIRE FROM THE
OIL PRESSURE SWITCH TERMINAL
AND CONNECT IT TO EARTH
DISCONNECT THE WIRE FROM THE
THERMOSTAT AND CONNECT IT
TO EARTH
DISCONNECT THE WIRE FROM THE
W TERMINAL OF THE FLOAT AND
CONNECT IT TO EARTH
NOTE
WHEN THE SIMULATION HAS BEEN COMPLETED ENSURE THAT ALL OF THE CONNECTIONS
ARE RETURNED TO THEIR ORIGINAL POSITIONS
DEVICE TEST
Содержание DIP-804/00
Страница 12: ...Remarks 12 GB DIP 804 00 2...