background image

GB DIP-804/00 /2

3

IGNITION KEY

TWIN-FUNCTION INDICATORS

ENGINE PROTECTIONS

- REST
- MANUAL STOP
- RESET PROTECTION

- DEVICE SUPPLY

- START ENGINE

0

AUT.

START

These are on when the key is turned to "AUT".
They switch off when the engine is running and
the oil pressure and battery recharger are
regular.

The engine protections are enabled when the ENGINE PROTECTIONS ACTIVE

indicator is

on (20 seconds after turning the key to "AUT" or, in any case 20 seconds after the end of the start
impulse).
The interventions of the protection probes (mounted on the engine), shown by the relevant visual
indicators, stop the engine and can be divided into two groups:

These are enabled after the PROTECTIONS
ACTIVE indicator

switches on, and they

switch on when the relevant anomaly is
detected.

- OIL AND BATTERY INDICATORS

- ANOMALY INDICATORS

After a 3 second delay for:

Immediately for:

- OIL PRESSURE SWITCH

- OVERHEATING THERMOSTAT

- BATTERY CHARGE ALTERNATOR

(ALTERNATOR BELT BREAKAGE)

MAIN ALARM

This is obtained in three ways:

By turning the ignition key to zero
Because of protections intervention

-
-

The protection device uses two different types of stoppage:
- activating the ELECTROMAGNET which pulled the STOP lever for 20 seconds
- disconnecting the supply to the SOLENOID which closes the gasoline passage.

Enabled when the ignition key is turned to "AUT", without stopping the engine.

This can be obtained by mounting a visual and/or acoustic indicator externally connected to the
relevant output.
This is continuously activated if the protections or fuel reserve alarm intervene.

RESET: This is obtained by turning the ignition key to zero.

(MOUNTED EXTERNALLY)

STOPPING

ALARM

(FUEL RESERVE

)

FUNCTIONING

Содержание DIP-804/00

Страница 1: ...CIENT BATTERY CHARGE ALTERNATOR BELT BREAKAGE LOW OIL PRESSURE OVERHEATING FUEL RESERVE without stopping engine OIL AND BATTERY INDICATORS INTEGRATED INTO THE DEVICE GB DIP 804 00 2 1 DIP 804 00 INSTR...

Страница 2: ...N THE FOLLOWING CONDITIONS Where the environmental temperature is outside the limits indicated in the enclosed technical sheet Where there are high levels or heat from radiation caused by the sun oven...

Страница 3: ...the relevant anomaly is detected OIL AND BATTERY INDICATORS ANOMALY INDICATORS After a 3 second delay for Immediately for OIL PRESSURE SWITCH OVERHEATING THERMOSTAT BATTERY CHARGE ALTERNATOR ALTERNAT...

Страница 4: ...ELLOW G R G B L C R LE 39 40 DIP 804 00 h 1 48 3 4 16 41 40 28 26 27 30 50 30 15 54 50 W 157 3 W MAX BELT BREAKAGE WARNING DO NOT CONNECT THE CHARGE CONTROL BULB INTO THE PLANT SEE TWIN FUNCTION INDIC...

Страница 5: ...TERNATOR REGULATOR 27 ALTERNATOR REGULATOR 28 PRE EXCITATION CHARGE ALTERNATOR 40 STARTER MOTOR 41 BATTERY ON REQUEST ACCESSORIES MOUNTED ON THE ENGINE The system is arranged to command the stopping w...

Страница 6: ...ONDS THE RELEVANT INDICATOR WILL LIGHT UP WITHOUT STOPPING THE ENGINE DISCONNECT THE WIRE FROM TERMINAL 8 OF THE DEVICE AND CONNECT TERMINAL 8 TO EARTH DISCONNECT THE WIRE FROM THE OIL PRESSURE SWITCH...

Страница 7: ...INSUFFI CIENT PRESSURE ENGINE OVERHEATING INSUFFICIENT FUEL NORMALLY THE RELEVANT TERMINAL OF THE BATTERY CHARGE ALTERNATOR IS NEGATIVE WITH THE ENGINE STATIONARY NORMALLY THE TERMINAL OF THE OIL PRE...

Страница 8: ...or lights up The overheating indicator lights up ENGINE STOPS FOR ANOMALY ENGINE DOES NOT STOP UNDER ANY CONDITIONS Stop system electromagnet or solenoid does not function Defective engine probes Defe...

Страница 9: ...y replace the oil pressure switch Test and if necessary replace the thermostat Simulate the functioning of the device see DEVICE TEST on page 5 and if necessary replace it Turn the key to zero to rese...

Страница 10: ...2 SEE PAGE 5 ACCESSORIES DATA FOR ORDERING MOBILE SOCKETS type PMO 134 00 code 40804234 ENGINE PROTECTION DEVICE type code type code DIP 804 00 12 V DIP 804 00 24 V 00030201 00030202 ACCESSORIES AVAI...

Страница 11: ...VDC CIRCUIT LOADING WITH KEY TURNED TO ZERO 8 mA MAXIMUM LOAD ON OUTPUT 5 3 A STOP MAXIMUM LOAD ON OUTPUT 7 3 W GENERAL ALARM TEMPERATURE RANGE 10 60 C TERMINAL BOARD FASTON 6 35 0 8 DEGREE OF PROTECT...

Страница 12: ...Remarks 12 GB DIP 804 00 2...

Отзывы: