 ELCOS SRL 

- Parma - EN - CEM-370 /1

2

 

MOTOR PUMP START UP

 

OFF

 - 

MANUALSTOP

 - 

RESET 

 

 - 

UNIT POWER SUPPLY   

                  

 - 

 GLOW PLUGS CONTROL

 

MOTOR PUMP START UP

BRIEF INSTRUCTIONS

TECHNICAL DATA

Battery voltage supply

12 Vdc   24 Vdc

Voltage supply

8 ÷ 32V

Circuit loading with key at zero

0 mA 

Maximum Consumption

265 mA a 12V 150 mA a 24V 

Tachometer

Max 4000 RPM precision ±  10 RPM 

Timer

1 ÷ 96h

Instruments precision:battery voltmeter, fuel level gauge

2%

Hour-meter

5 digits

Max load of the outputs:

• starting motor (black)

• stopping (yellow)

• preheating  (white/brown)

• headlight (brown)

• general alarm (red/green)

40A 

3A

3A

3A

3A

Degree of protection:

Box front

Rear

Connector

IP54

IP23

IP20

Installation conditions

for external use

Temperature range

-20 ÷ +60°C

Weight

 950   g

Display

Stopping due to low

coolant level.

Press if you want to

set working time

( up to 96 hours).

Stop for end

of work time.

Anomaly A2 

(insufficient

fuel pressure).

Shows the timer

(if set).

General fault A1 

tripped.

Stopping due to high 

engine temperature 

The engine protection are

active.

Stoppage due to low

engine oil pressure.

The battery is

not charging.

Stopping due to lack of

battery charging 

(belt brekage).

Stopping due to low

engine oil pressure.

Press to select the displayed function, 
each time it is pressed, the instrument 
indicated by the display changes.

 

Hold down to silence the general 

alarm (buzzer).

Pump water pressure

is regular.
Pump protection excluded

Pump protection

active.

Stoppage due to low

pressure pump water.

Press until the 2 signs start flashing

to exclude pump protection to 

re-activate.

Protection, press again until they

switch off.

Stoppage due to low

fuel level.

AUT.

START

Содержание CEM-370

Страница 1: ...eakage minimum fuel level available A1 A2 low diesel fuel pressure low coolant level insufficient pump water pressure Complete with display for displaying the following functions pump protection exclu...

Страница 2: ...0 C Weight 950 g Display Stopping due to low coolant level Press if you want to set working time up to 96 hours Stop for end of work time Anomaly A2 insufficient fuel pressure Shows the timer if set G...

Страница 3: ...RE by turning the starter key onto ZERO the engine pump will stop The push button excludes pump protection exclusion is obtained by keeping it pressed for at least 3 consecutive seconds the function i...

Страница 4: ...pressing the push button lights up until the desired value appears on the DISPLAY On releasing the push button the timer automatically starts working continously displaying the remaining work time CAN...

Страница 5: ...W PLUGS 157 GENERAL ALARM LIGHT RED GREEN 3AMAX BATTERY RED PRE EXCITATION CHARGE BATTERY ALTERNATOR WHITE RED GREEN BROWN DO NOT USE 3A MAX 3AMAX BLACK 40A MAX BATTERY ORANGE YELLOW VIOLET WHITE BROW...

Страница 6: ...he engine to idle at constant known speed for example via a portable tachometer LANGUAGE CHOICE The language set up in the factory is ITALIAN the languages that can be selected are ENGLISH FRENCH GERM...

Страница 7: ...G CONDITIONS Where the environmental temperature is outside the limits indicated in the Technical Data Where the air pressure and temperature variations are so rapid as to produce exceptional condensa...

Страница 8: ...PMA 100 00 4 14 bar cod 00500227 PMA 102 00 2 5 bar cod 00500235 PA 100 00 4 14 bar code 00500226 PA 102 00 2 5 bar code 00500231 ORDERING DATA Type CEM 370 cod 00210722 ACCESSORIES KIT Pre wired fem...

Отзывы: