ELCOS SRL
- Parma - EN - CEM-370 /1
2
MOTOR PUMP START UP
-
OFF
-
MANUALSTOP
-
RESET
-
UNIT POWER SUPPLY
-
GLOW PLUGS CONTROL
-
MOTOR PUMP START UP
BRIEF INSTRUCTIONS
TECHNICAL DATA
Battery voltage supply
12 Vdc 24 Vdc
Voltage supply
8 ÷ 32V
Circuit loading with key at zero
0 mA
Maximum Consumption
265 mA a 12V 150 mA a 24V
Tachometer
Max 4000 RPM precision ± 10 RPM
Timer
1 ÷ 96h
Instruments precision:battery voltmeter, fuel level gauge
2%
Hour-meter
5 digits
Max load of the outputs:
• starting motor (black)
• stopping (yellow)
• preheating (white/brown)
• headlight (brown)
• general alarm (red/green)
40A
3A
3A
3A
3A
Degree of protection:
Box front
Rear
Connector
IP54
IP23
IP20
Installation conditions
for external use
Temperature range
-20 ÷ +60°C
Weight
950 g
Display
Stopping due to low
coolant level.
Press if you want to
set working time
( up to 96 hours).
Stop for end
of work time.
Anomaly A2
(insufficient
fuel pressure).
Shows the timer
(if set).
General fault A1
tripped.
Stopping due to high
engine temperature
The engine protection are
active.
Stoppage due to low
engine oil pressure.
The battery is
not charging.
Stopping due to lack of
battery charging
(belt brekage).
Stopping due to low
engine oil pressure.
Press to select the displayed function,
each time it is pressed, the instrument
indicated by the display changes.
Hold down to silence the general
alarm (buzzer).
Pump water pressure
is regular.
Pump protection excluded
Pump protection
active.
Stoppage due to low
pressure pump water.
Press until the 2 signs start flashing
to exclude pump protection to
re-activate.
Protection, press again until they
switch off.
Stoppage due to low
fuel level.
AUT.
START