[*] ASSISTANCE REQUEST

Before replacing the panel, the client should consult our technician.
When he telephones, your electrical technician must have the chart shown on page 6-7 of the manual available
together with the following information:

- The type of equipment installed

- The problem encountered

- The state of the dashboards indicators when the problem arose

- Any previous corrective action taken

DIMENSIONS

TECHNICAL DATA

- BATTERY VOLTAGE SUPPLY

12 VDC (MAX 16 VDC)

Or

24 VDC (MAX 32 VDC)

-

- MAX CURRENT OUTPUT

• YELLOW

3 A

• RED/GREEN (GENERAL ALARM)

3 A

- TEMPERATURE RANGE

-10 ÷ +60 °C

- DEGREE OF PROTECTION

• BOX

IP 23

• CONNECTOR

IP 20

-

FOR EXTERNAL USE

- CONTROL PANEL WEIGHT

1.600 g

• BLACK (STARTER)

40 A

(STOPPING)

• BROWN (AUXILIARY)

3 A

-

HOURMETER

4 DIGITS

- TIMER

1÷ 24h

INSTALLATION CONDITIONS:

- TOTAL WEIGHT (PANEL,

ACCESSORIES AND PACKAGE)

3 100 g

CIRCUIT LOADING WITH KEY AT ZERO

11 mA

GB

CEM-330/00 /1

11

156

198

77

29

50

224

190

210 mm

=

=

6MA

FRONT

REAR

Содержание CEM-330/00

Страница 1: ...ction intervention timer oil and battery lights GB CEM 330 00 1 1 BY SIMPLY STARTING IT AUTOMATICALLY CONTROLS THE MOTOR PUMP ALL THE OTHER FUNCTIONS ARE EASY TO USE WITH JUST TWO PUSH BUTTONS PROTECT...

Страница 2: ...ING CONDITIONS Where the environmental temperature is outside the limits indicated in the Technical Data on page 11 Where there are high levels or heat from radiation caused by the sun ovens or the li...

Страница 3: ...n intervention 6 seconds after the pressure drop detected by the PUMPWATER PRESSURE SWITCH fitted on the water pump stops the engine it is memorised and is indicated by the LOW WATER PUMP PRESSURE lig...

Страница 4: ...METER keeps the hours of work in memory even with the battery disconnected CORRECTINGTHE SETTIME CANCELLING THE TIMER Enabled with the key on AUT it makes it possible if necessary to have the engine p...

Страница 5: ...H THE ENGINE STATIONARY NORMALLY THE TERMINAL OF THE OIL PRESSURE SWITCH IS NEGATIVE WITH THE ENGINE STATIONARY NORMALLY THE TERMINAL OF THE THERMOSTAT IS NEGATIVE WHEN THE ENGINE IS TOO HOT NORMALLY...

Страница 6: ...OIL PRESSURE STOPPAGE DUE TO LOW FUEL LEVEL STOPPAGE DUE TO CLOGGED AIR FILTER STOPPAGE DUE TO LACK OF BATTERY CHARGING BROKEN BELT STOPPAGE DUE TO ENGINE OVER TEMPERATURE STOPPAGE DUE TO LOW COOLANT...

Страница 7: ...PROBE AVAILABLE ON REQUEST ACCESSORIES CHARGE BATTERY ALTERNATOR MOUNTED ON ENGINE 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 11 10 155 3 40 4 150 157 30 BATTERY ORANGE SKY BLUE RED BLACK 40A MAX CONNECTOR CONNECT...

Страница 8: ...E R M I N A L A N D CONNECTITTO EARTH DISCONNECT THE WIRE FROM THE TERMINAL OF THE FLOAT AND CONNECTIT TO EARTH W NOTE STOP GENERAL ALARM AND VISUAL INDICATOR ON WHEN THE SIMULATION HAS BEEN COMPLETE...

Страница 9: ...OF PROBLEM PROBABLE CAUSES REMEDIAL INTERVENTIONS THE STARTER MOTOR DOES NOT FUNCTION Flat battery Starter motor is defective An anomaly indicator is on Defective ignition key Recharge the battery an...

Страница 10: ...ice for the anomaly indicated see PANEL TEST on page 8 and if necessary replace it Check that starter key is in aut engine is running oil pressure switch is disconnected If under these conditions the...

Страница 11: ...previous corrective action taken DIMENSIONS TECHNICAL DATA BATTERY VOLTAGE SUPPLY 12 VDC MAX 16 VDC Or 24 VDC MAX 32 VDC MAX CURRENT OUTPUT YELLOW 3 A RED GREEN GENERAL ALARM 3 A TEMPERATURE RANGE 10...

Страница 12: ...SEE PAGE 7 GB CEM 330 00 1 12 CONFORMITY DECLARATION The company ELCOS s r l assumes full responsability for declaring that the equipment when used in the ways and for the purposes described in the e...

Отзывы: