7 ADDITIONAL SETUP PAGES FOR MODELS STAR3 HARMO and ALM
To access Programming Mode, open the front door and press the PAG and the SEL keys at the same time. Use the SEL
key to select a digit or a setting. Use the SET key to adjust it.
The setup can be protected with a password (see chapter 6)
·Page S10- Pulses with length 100 msec
Enable Pulse mode with pulse length of 100 msec
Press PAG to confirm . Press SET for selection, 20 msec (S11). RLY (S12).
·Page S11 - Pulses with length 20 msec
Enable Pulse mode with pulse length of 20 msec .
Press PAG to confirm. Press SET for the next selection (go to S16)
·Page S12- ALM
The confirmation of this page enable the remote relay control or the alarm mode.
Press PAG to confirm
Press SET to go to the pulse mode (go to S10).
PULSE OUTPUT
·Page S13- Measure corresponding to output 1 .
Pressing the SET key enables to select the measure corresponding to output 1:
kWh tot
kWh tot COG
kVArh tot
kVArh tot COG
kVAh tot
·Page S14 - Measure corresponding to ouput 2.
Pressing the SET key enables to select the measure corresponding to output 2.
The measure available are the same of page S12 for output 1.
·Page S15 - Weight of 1 pulse output 1
Number of kWh corresponding to 1 pulse.
E.g.: 1 pulse = 0.01 kWh
Pressing the SEL key to select the digit to modify.
Pressing the SET key to adjust the selected digit to modify.
Pressing the PAG key enables to go to output 2 pulse weight set-up.
·
Page S16 - Weight of 1 pulse output 2.
Same as S14 for output 2.
This is the last page of the setup. Press PAG to return to the measure pages
RELAYS or ALARM OUTPUT
·Page S17-Measure for Alarm 1
Association of the output 1 with a measures for alarm controlling. Press the SET key to choose one the
following measures The following list is available in 3PH-N mode.
Some of the measures are not carried out in 1PH, 2PH and 3PH mode and therefore can not be found
in the setup of the alarm.
V total ;
VL1;
VL2;
VL3
A total ;
AL1;
AL2;
AL3
kW total ;
kWL1;
kWL2;
kWL3
kVA total ;
kVAL1;
kVAL2;
kVAL3
kVAr total;
kVArL1;
kVArL2;
kVArL3
PF total ;PFL1;
PFL2;
PFL3
THDV tot ;
THDV L1;
THDV L2;
THDV L3
THD A tot ;
THDA L1;
THDA L2;
THDA L3
RLY
= relay 1 controlled remotely, via RS485, instead of locally as an alarm ( go to S18)
Pressing the PAG key enables to go to one of the following pages:
set-up of the upper threshold of output 1 if one of the measures has been selected; ( S19)
set-up of the relay output 2 if the remote mode has been selected for output 1 (S24)
·Page S18-Remote Rs485 relay 1 control
if RLY is confirmed in S17 ( see above) the position of the relay 1 is decided by the Rs485 master device
( PC , PLC, etc) Press PAG to accept the RLY selection and enter the setup of relay 2 ( go to S23) Press
SET to enable the alarm mode ( go to S17).