·Page S5 Reset Averages and Maximum Demands, Power and current averages.

If you select Y with the SET key, all the Averages and maximum demand values will be reset as soon you 

confirm by pressing the PAG. key.

·Page S6 Enable Cogeneration counters.

Select ON or Off to enable the measures and confirm with PAG

To measure properly the cogeneration counters it is strictly necessary to connect the

CTs oriented in the same direction. This is not required if the Cogeneration is OFF

·Page S7 Programming connection type

Select the type of system which you want to measure using the SET key.

·Page S7a

3 PH

Three phases without neutral (i.e. Delta)

·Page S7b

3 PH And n

Three phases with neutral (i.e. Star)

·Page S7c

2 PH 

Two-phases with neutral

·Page S7d

1 PH 

Single phase with neutral

·Page S8 : Rs485 communication parameters setup

Baud Rate: (3 top digits) can have the following values: 2.4, 4.8, 9.6, 19.2 (kbaud)

The Parity (central) value can be : N (none), O (odd), E (even).

The type of communication protocol Modbus (3 bottom digits) can be:

ASCII = Modbus ASCII.  This format is limited to simulate the same data frame of the Vip Energy.

BCD   = Modbus BCD.  It allows the full control of the instrument

IEEE   = Modbus IEEE standard, INTEL format

·Page S9  Rs485 instrument address

The Modbus address of the instrument can be set in this page.

The permitted address field ranges between 1 and 247.

The page S9 is the last one of the basic model STAR3 family.

Other pages will follow only if the STAR3 is equipped with the options HARMO, ALM, 4-20mA

6 - SET-UP PAGE PROTECTION CODE

By default, the access code to set-up pages is not enabled. To enable it, keep the PAG + SEL keys pressed simultaneously

for 30 sec. The display will show the page on which the access code must be entered.

·Page S0 enter setup password

By means of the SEL + SET keys, every digit can be changed and the code can be entered. The initial 

factory code , that must be entered the first time is 000000.

Confirm and exit from this page by pressing the PAG key.

·Page S0a – modify password

Now a second page (with "COD" blinking), identical to the first one, is displayed:

From this page,  the access code can be permanently changed, if wished.

In this case remember or make a safe note of the new code somewhere you can find it later on.

To exit from the second page press the PAG key.

IMPORTANT: After the first access to the password page, the request of the code will become permanent.

From that moment on the code must be always entered to access the set-up page.

Avoid to recall the password page, for test purposes, if the code request is not permanently desired.

SETUP PASSWORD MEMO

STAR3 SERIAL'#

INSTALLED AT

FACTORY PASSWORD
DATE
NEW PASSWORD

DATE
NEW PASSWORD
DATE

NEW PASSWORD

000000

Содержание STAR 3

Страница 1: ...06 Fax 39 051 845544 http www elcontrol energy net e mail Italia vendite elcontrol energy net estero sales elcontrol energy net ST STAR3 AR3 WARNING Elcontrol Energy Net S p a declines all liability for any damage to people or property caused by unsuitable or incorrect use of its products Elcontrol Energy Net reserves the right to change product specifications without prior notice ENGLISH ...

Страница 2: ... L2 VL2 VL3 VL3 L1 V Harmonics A Neutral A1 Avg A2 Avg A3 Avg Peak Current A Harmonics PAG PAG PAG PAG PAG SEL SEL SEL SEL SEL SEL SEL SEL SEL PAG Harmonics model only THD Avg V A TOT V A W THD V L1 L2 L3 PAG PAG PAG PAG PAG SEL SEL SEL SEL SEL SEL SEL 32 PH and N TOT VA PF Hz TOT VA VAr W TOT kVAh kWh TOT kVArh kWh THD A L1 L2 L3 Avg VA VAr W Peak VA VAr W COG lVArh kWh PAG PAG PAG ...

Страница 3: ...TAR3 SET SEL PAG V SEL Three phase energy analyzer STAR3 SET SEL PAG V SEL Three phase energy analyzer STAR3 SET SEL PAG V Pg M1 S1 Phase Phase VL1 L2 SEL Three phase energy analyzer STAR3 SET SEL PAG V Three phase energy analyzer STAR3 SET SEL PAG A Pg M1 S2 Phase Phase VL1 L2 Pg M1 S3 Phase Phase VL1 L2 Pg M1 S4 Voltage Harmonics Pg M2 Phase Currents Pg M2 S1 Neutral Current Pg M2 S2 Phase Curre...

Страница 4: ...T SEL PAG k V SEL Three phase energy analyzer STAR3 SET SEL PAG VA SEL Three phase energy analyzer STAR3 SET SEL PAG VAr SEL Three phase energy analyzer STAR3 SET SEL PAG PF Pg M6 Phase Power factor SEL Three phase energy analyzer STAR3 SET SEL PAG THD r m s A V 3F Pg M7 Averange THD V and A Pg M3 Phase Active Power Pg M4 Phase Apparent Power Pg M7 S1 Phase THD V PgM7 S2 Phase THD A PAG PAG PAG PA...

Страница 5: ...analyzer STAR3 SET SEL PAG V A PF kW 3F SEL Three phase energy analyzer STAR3 SET SEL PAG SEL Three phase energy analyzer STAR3 SET SEL PAG Pg M10 S1 3ø Averange Powers VA VAr W SEL Three phase energy analyzer STAR3 SET SEL PAG kVA A v g kVAr kW 3F Pg M10 S2 Maximum Demand Power VA VAr W Pg M11 3ø Energy Couters VAh VAr W Pg M12 3ø Energy Couters VAh VAr W Pg M12 S1 3ø Cogeneration Couters VArh Wh...

Страница 6: ... SEL PAG Pg S7 Connection type SEL Three phase energy analyzer STAR3 SET SEL PAG Pg S5 Reset Avg and Peak SEL Three phase energy analyzer STAR3 SET SEL PAG Avg M D Pg S4 Reset couters SEL Three phase energy analyzer STAR3 SET SEL PAG Pg S8 Setup Rs485 SEL Three phase energy analyzer STAR3 SET SEL PAG Pg S9 Rs485 address SEL Three phase energy analyzer STAR3 SET SEL PAG Pg S3 Integration period SET...

Страница 7: ...lyzer STAR3 SET SEL PAG k W 3F SEL Three phase energy analyzer STAR3 SET SEL PAG A 3F Pg S12 4 20mA Measure for output 2 selection Pg S11 4 20mA Measure for output 1 selection Pg S13 4 20mA Full scale output 1 Pg S14 4 20mA Full scale output 2 SEL Three phase energy analyzer STAR3 SET SEL PAG A 3F PAG SETUP MENU ADDITIONAL PAGES FOR MODELS 4 20MA PAG PAG PAG ...

Страница 8: ...T SEL PAG 3F kVA SEL Three phase energy analyzer STAR3 SET SEL PAG Pg S11 Pulse mode 20msec width Pg S13 Measure for Pulse 1 Pg S14 Measure for Pulse 2 Pg S16 Units for Pulse 2 Pg S15 Units for Pulse 1 SETUP MENU ADDITIONAL PAGES FOR MODELS ALM AND HARMO PAG PAG PAG SET SET Pg S12 Pg S12 Relay Alarm mode PAG PAG Pg S17 Alarm measure selection Pg S19 Alarm 1 High threshold Pg S18 Remote Rs485 Relay...

Страница 9: ... 3 PH N L3 L2 L1 1 2 3 4 5 6 7 8 9 11 VOLTAGE POWER SUPPLY VL3 VL2 VL1 N A3 A2 A1 COM S1 S2 S2 N S1 CURRENT 90 230 V AC DC 3 PH L3 L2 L1 1 2 3 4 5 6 7 8 9 11 VOLTAGE CURRENT POWER SUPPLY VL3 VL2 VL1 N A3 A2 A1 COM S1 S2 90 230 V AC DC 2 PH AC N AC 1 2 3 4 5 6 7 8 9 11 VOLTAGE CURRENT POWER SUPPLY VL3 VL2 VL1 N A3 A2 A1 COM S1 S1 S2 S2 90 230 V AC DC ...

Страница 10: ...N A3 A2 A1 COM 230V 115V 0 115V 230V 230VAC Fuse 100 mAT 115VAC Fuse 200 mAT 1 2 3 4 5 6 7 8 9 11 VOLTAGE CURRENT POWER SUPPLY VL3 VL2 VL1 N A3 A2 A1 COM STAR3 with switching power supply 90 230 V AC DC 90 230V AC DC 230VAC Fuse 100 mAT 90VDC Fuse 400 mAT 115VAC Fuse 400 mAT L1 L3 L2 1 2 3 4 5 6 7 8 9 11 VOLTAGE POWER SUPPLY VL3 VL2 VL1 N A3 A2 A1 COM CURRENT 3 PH 2PT 90 230 V AC DC NOTE The secon...

Страница 11: ...Average Apparent Power kV verage Apparent Power kVA A COG negative Reactive Energy kvarh COG negative Reactive Energy kvarh Maximum Demand Reactive Power kvar Maximum Demand Reactive Power kvar Positive Imported Active Energy kWh Positive Imported Active Energy kWh COG negative Exp Active Energy kWh COG negative Exp Active Energy kWh Positive Reactive Energy kvarh Positive Reactive Energy kvarh Ap...

Страница 12: ...g damaged in transit 2 CONNECTION OF THE INSTRUMENT 2 1 POWER SUPPLY The power supply connections terminals are located on the rear side and are clearly indicated with the label POWER SUPPLY Use cables having a maximum section of 2 5 mm2 Earth connection is not required Follow the connection diagram at the beginning of the manual 2 2 CONNECTING VOLTAGE MEASUREMENT CABLES These cables having a maxi...

Страница 13: ...AL2peak AL3peak maximum average currents Page M2 S4 Page appearing only in STAR3 HARMO Harmonics Currents AL1h AL2h AL3h Use the key SEL to scroll all the harmonics orders h The maximum order is depending on the fundamental It is the 25th at 50 H Page M3 page not available in 1PH Phase active powers kW PL1 PL2 PL3 3 PH N 3 PH Phase active powers PL1 PL2 2 PH Page M4 page not available in 1PH Phase...

Страница 14: ...active energy counter kVArh Total active energy counter kWh range 0 000 000 00 99 999 999 9 kWh When the upper limit is reached the counter restarts from 00 000 000 0 kWh One decimal disappear definitively after the first roll over Reset the counter to display it again Page M12 S1 Cogeneration counters This page is available only if the COG is enabled into the SETUP Total capacitive reactive energ...

Страница 15: ...dbus address of the instrument can be set in this page The permitted address field ranges between 1 and 247 The page S9 is the last one of the basic model STAR3 family Other pages will follow only if the STAR3 is equipped with the options HARMO ALM 4 20mA 6 SET UP PAGE PROTECTION CODE By default the access code to set up pages is not enabled To enable it keep the PAG SEL keys pressed simultaneousl...

Страница 16: ...t the digit to modify Pressing the SET key to adjust the selected digit to modify Pressing the PAG key enables to go to output 2 pulse weight set up Page S16 Weight of 1 pulse output 2 Same as S14 for output 2 This is the last page of the setup Press PAG to return to the measure pages RELAYS or ALARM OUTPUT Page S17 Measure for Alarm 1 Association of the output 1 with a measures for alarm controll...

Страница 17: ...ressed in seconds The alarm will toggle only if the new alarm condition persist for a time longer than the delay Press the SEL key enables to select the digit to modify Press the SET key enables to modify the selected digit Press the PAG key to go to set up of the output 2 Page S23 Measure for Alarm 2 Similar to S17 for relay 2 Page S24 Remote RS485 relay 2 control Similar to S18 for relay 2 Page ...

Страница 18: ...ables to return to the measurement page 9 ELECTRICAL SPECIFICATIONS OF THE OPTIONAL OUTPUTS SERIAL OUTPUT 485 Standard Rs485 max 32 instruments on each line without repeater up to 247 instruments with repeaters ANALOG OUTPUTS 4 20mA Max load impedance 500 output conversion from 0 20 mA to 0 10 V with 500 output impedance The output signal accuracy is the same as the correlative measure 10 A The ou...

Страница 19: ...AL2 AL3 COM Consumption 1 VA 3 or 2 external curr transf 5A required Measuring range 0 120 In Sensitivity current 20 mA voltage 10 V Over current withstand 50 amps for 1 sec Number of scales 1 voltage scale 2 current scales Measurements True R M S up to25th harmonic 1250Hz with fundamental 50 Hz Sampling frequency 2 5 kHz Accuracy 0 5 for Voltage and current and Power Connection Single phase or th...

Отзывы: