06/2016 - Art. Nr. 4200 1041 1103A
18
Installation
Checking the burner head for natural gas/propane gas
Checking the burner head
• Check the adjustment settings of the
ionisation probe and of the ignition
electrode as per the diagrams.
Recommended setting for
natural gas
On the gas diffusers labelled
A
,
1 outwards-facing slot and 1 inwards-
facing slot should be left open by sliding
shutter/diffuser
E
.
On the gas diffusers labelled
B
,
3 outwards-facing slots and 0 inwards-
facing slots should be left open by
sliding shutter/diffuser
E
.
At the end of the gas diffusers labelled
B
, the opening is 8 mm (adjusted by
sliding the shutter
F
).
Recommended setting for propane
gas
On the gas diffusers labelled
A
,
1 outwards-facing slot and 0 inwards-
facing slot should be left open by sliding
shutter/diffuser
E
.
On the gas diffusers labelled
B
,
0 outwards-facing slots and 1 inwards-
facing slot should be left open by sliding
shutter/diffuser
E
.
At the end of the gas diffusers labelled
B
, the opening is 8 mm (adjusted by
sliding the shutter
F
).
VG 5.950/1200 M/TC
VG 5.950/1200 M/TC