![elco THISION L PLUS Скачать руководство пользователя страница 62](http://html1.mh-extra.com/html/elco/thision-l-plus/thision-l-plus_operating-manual_2377082062.webp)
62
Operation
Parameter listing
Menu
Submenu
Parameter Name
Description
Range
Factory
settings
24. 6
Configurable Inputs-Outputs
24. 6.
0
Multi In Temp 1
0 = None
1 = Common flow sensor
2 = DHW storage tank bottom
3 = DHW circulation sensor
4 = DHW charging sensor
5 = Buffer storage tank top
6 = Buffer storage tank bottom
7 = Flue gas temp sensor
0 - 7
1
24. 6.
1
Multi In Temp 2
0 = None
1 = Common flow sensor
2 = DHW storage tank bottom
3 = DHW circulation sensor
4 = DHW charging sensor
5 = Buffer storage tank top
6 = Buffer storage tank bottom
7 = Flue gas temp sensor
0 - 7
0
24. 6.
2
Multi In Temp 3
0 = None
1 = Common flow sensor
2 = DHW storage tank bottom
3 = DHW circulation sensor
4 = DHW charging sensor
5 = Buffer storage tank top
6 = Buffer storage tank bottom
7 = Flue gas temp sensor
0 - 7
0
24. 6.
3
Multi In Freq
0 = None
1 = Flowmeter
2 = Flow switch
0 - 2
0
24. 6.
4
Multi In AD 1
0 = None
1 = Room thermostat HC1
2 = Room thermostat HC2
3 = Room thermostat HC3
4 = 0-10V input request
5 = External operating mode changeover HCs+DHW
6 = Heat generation lock
7 = Timer CH
8 = Gas Pressure Switch
0 - 8
0