Installation
Connections
Collective flue gas outlet over-pressure
An installation with a collective
flue gas outlet over-pressure in
combination with individually
controlled boilers (e.g. 0-10 V
control), where no bus cable is
connected, is NOT allowed.
Diameter and venting lengths of the
flue gas outlet/air supply:
-
Open system with over-pressure.
NOTE!
1. IPX0D at flue category B
23
and B
33
2. Only with bus cable connected!
3. Adjust parameter 102 to 2
Diameter and venting lengths of the
flue gas outlet/air supply:
-
Closed system with over-pressure.
Please contact ELCO.
d
d
h
d
d
h
=d
=d
d
d
Dimensions cascade flue THISION L PLUS
Open system, overpressure
Output (80/60)
d = minimum diameter Ø in mm
[kW]
h = 2 - 5
h = 6 - 10
h = 11 - 15
h = 16 - 20
114
-
240
150
150
150
150
240
-
360
150
150
180
180
360
-
480
180
180
180
200
480
-
600
200
220
220
220
600
-
660
230
230
250
250
660
-
872
260
260
260
260
872
-
960
280
280
280
300
960
-
1200
280
280
280
300
Dimensions cascade flue THISION L PLUS
Closed system, overpressure, parallel
Output (80/60)
d = minimum diameter Ø in mm
[kW]
h = 2 - 5
h = 6 - 10
h = 11 - 15
h = 16 - 20
114
-
285
150
150
150
150
285
-
524
200
200
200
200
524
-
1440
300
300
300
300