elco Thision EVO WH 250-120 Скачать руководство пользователя страница 20

+

+

+

-

-

+

-

+

Commissioning

20 

GB

Combus  on analysis
Combus  on se   ngs

Combus  on check at full load

Start the boiler in controller stop 
mode and go to 50% load. Now the 
boiler operates at 50% load. Allow 
the boiler to stabilise the combus  on 
for 3 minutes. Then increase the 
boiler load step by step up to 100%. 
Check the gas pressure on the inlet 
of the gas valve while increasing the 
boiler load:
the gas pressure should never go 
below the minimum required value 
-- see technical data. 
When an (op  onal) minimum gas 
pressure switch is connected, this 
must be set to 75% of the required 
gas pressure.
Check the combus  on  se   ngs 
via the test point in the chimney 
connec  on (1). 
If necessary, correct the se   ngs with 
the small adjustment screw at the 
top of the mixer (3).

Combus  on check at minimum load

Switch the boiler to minimum load 
(0%).
Check the combus  on  se   ngs  the 
same way as described for full load. 
If necessary, correct the se   ngs with 
the large adjustment screw at the 
top of the gas valve (2).

Combus  on check at 50% load

An addi  onal reference check of 
combus  on values at 50% load is 
recommended in order to check if 
the gas valve is set in such way, that 
the modula  ng behaviour is normal. 
The CO

2

 value should be in between 

the se     ngs of full load and minumum 
load. 
CO value should be equal to full load 
and minimum load values.
Make sure that the boiler is set to 
automa  c  opera  on and controller 
stop mode is disabled a  er  the 
combus  on test is 

fi

 nished.

Combus  on se   ngs

Adjustments must be made by 
quali

fi

 ed persons only.

If the appliance manufacturer

 supplies checkout and/or service and 
maintenance instruc  ons  carefully 
follow them.
If such instruc  ons are not provided 
then use the procedure outlined 
below.
Adjustment can only be made with a 
special tool.

Remove cap screw with a screw
driver to expose o

 set adjustment

screw.

Check gas supply pressure to the
appliance using a pressure gauge
connected to the inlet pressure
tap.

Start fan and check air 

fl

 ow.

Energize both electric operators in
order to have gas input to burner
and ignite boiler.

Operate boiler on high output.

Adjust CO

2

 % with thro  le

adjustment screw (3) to the
desired value. Turn screw driver
clockwise way to increase CO

2

 %.

Operate boiler on low output

Adjust the CO

2

 % at the desired

value at low output with o

 set

adjustment screw (2). Turn o

 set

adjustment screw clockwise to
increase CO

2

 %.

Replace cap screw and   ghten
pressure tap.

Combus  on se   ngs max. load

 

for natural gas G20 

THISION L EVO

120

CO

2

, max

%

8.4 

-0.2

CO

2

, min

%

8.5 

-0.2

+0

+0

Combus  on se   ngs max. load

 

for natural gas G20 

THISION L EVO

70

CO

2

, max

%

8.4 

 

-0.2

CO

2

, min

%

9.0  

-0.2

+0

+0

TH-L Evo70

TH-L Evo 120

TH-L Evo70

TH-L Evo 120

Combus  on se   ngs max. load

 

for LPG

 G31

THISION L EVO

70-120

CO

2

, max

%

9.6 

 

+0.2

CO

2

, min

%

9.6 

 

+0.2

+0

+0

3

2

2

1

Содержание Thision EVO WH 250-120

Страница 1: ...Operation and Installation manual THISION EVO WH 08 2016 PAG THEWH01...

Страница 2: ......

Страница 3: ...0 21 Gas tightness check 21 Water heater shut down 21 Maintenance Checklist 25 Replacing the electrodes 25 Cleaning the condensate receptacle 26 Cleaning and refilling the syphon 26 Inspection of the...

Страница 4: ......

Страница 5: ...directive 2004 108 EEC EMC directive EN 483 Gas fired central heating boilers Type C boilers of nominal heat input not exceeding 70 kW EN 15420 Gas fired central heating boilers Type C boilers of nom...

Страница 6: ...utory obligations This boiler has been tested and certified to comply with all necessary European directives and is CE marked and complies with 92 42 EEC Efficiency of Hot Water Boilers Directive 90 3...

Страница 7: ...rol ling the speed of the fan As a re sult the venturi mixing system will adapt the gas ra o to the chosen fan speed in order to maintain the best possible combus on figures and therewith the best e c...

Страница 8: ...installed from the system to the unit 1 230Vac electrical supply 2 Mains cold water supply 3 DHWS secondary flow pipework 4 DHWS secondary return pipework 5 Gas supply pipework 6 Condense drain pipewo...

Страница 9: ...NOx level mg kWh 39 39 CO level max min mg kWh 99 11 88 5 Max permissible flue resistance Pa 244 134 Water volume l 6 0 9 0 Water pressure max min boiler module bar 8 1 8 1 Max water temperature High...

Страница 10: ...us output at 60 C 250L storage Continuous operation at 60 C 1st hour continous output at 60 C 500L storage 10 min peak output at 60 C 500L storage L 687 818 L 1622 2413 L 1122 1913 10 Electrical Data...

Страница 11: ...352 1 1 4 1 1 4 1 1 4 1 1 4 3 4 3 4 3 4 3 4 1 1 2 1 1 2 1 1 2 1 1 2 W 100 B1 D H1 H1 mm 1952 1821 1952 1821 11 J K L M N mm mm mm mm mm J K L M N 1100 1000 800 700 600 1100 1000 800 700 600 DHW Flow...

Страница 12: ...ons 1 2 3 4 Condensate connection 5 After filling with water the syphon included in delivery should be installed to the connection 5 at the bottom of the water heater Connect the hose to the draining...

Страница 13: ...nal regulations Construct the flue gas system as short as possible for maximum length see planner documentation Construct horizonal ways with a mini mum angle of 3 Air intake connection 8 The air inta...

Страница 14: ...taining visibility iii Discharges at high level e g into a metal hopper and metal downpipe with the end of the discharge pipe is clearly visible tundish visible or not or onto a roof capable of withst...

Страница 15: ...Sizing of copper discharge pipe D2 for common T P relief valve sizes Schematic discharge pipe arrangement Unvented Applications Worked example of discharge pipe sizing The example below is for a G1 2...

Страница 16: ...16 Cylinder Controls Electrical Connections...

Страница 17: ...been eliminated close the outlet Step 4 Check pipework for leaks Further Commissioning Once the system has been completely filled and vented the unit can be connected to the electrical supply All DHWS...

Страница 18: ...nal posi on Make sure the syphon is filled before star ng the boiler in order to pre vent flue gases discharging through the condensate connec on Flue and air intake connec ons Check whether the flue...

Страница 19: ...s in the display Choose set up confirm with OK button now the boiler load can be changed by rotating the wheel C and confirming the 50 setting with the OK button After checking the combustion values s...

Страница 20: ...to full load and minimum load values Make sure that the boiler is set to automa c opera on and controller stop mode is disabled a er the combus on test is finished Combus on se ngs Adjustments must be...

Страница 21: ...lt in a lockout no 28 The lockout should disappear as soon as the plug is placed back in posi on the boiler will restart Ionisa on electrode 4 Remove electrical connec on from the ionisa on electrode...

Страница 22: ...1 sensor error 65 Room temperature 2 sensor error 70 Buffer storage tank temperature 1 sensor error 71 Buffer storage tank temperature 2 sensor error 72 Buffer storage tank temperature 3 sensor error...

Страница 23: ...g temperature sensor error 324 BX same sensors 325 BX extension module same sensors 326 BX mixing group same sensors 327 Extension module same function 328 Mixing group same finction 329 Extension mod...

Страница 24: ...less header address error 353 Common flow sensor B10 not available 371 Flow temperature 3 heating circuit 3 supervision 372 Limit thermostat heating circuit 3 373 Extension module 3 error collective e...

Страница 25: ...quality of the system water as well as supply water Check the water flow rate through the boiler Check correct the combus on values at full and mimimum load with a combus on analyzer Check the gas pre...

Страница 26: ...fresh water Mount the syphon back in the original posi on Inspec on of combus on chamber For inspec on of the combus on chamber the mixing system and burner must be disassembled Switch o the boiler a...

Страница 27: ...yzer for example Test points Bolt connections Gaskets of mixing system etc Safety devices Check the functionality and the settings of all safety devices connected Consult the chapter commissioning Che...

Страница 28: ...s p m u P Safety devices a W C g n i t t e s t i m i l h g i H ter flow sensor checked d e k c e h c r o s n e s s a g e u l F C g n i t t e s r e t i m i l p m e T Min gas pressure switch setting mba...

Страница 29: ...f T lics Low velocity header Water pboiler kPa Plated heat exchanger Water flow m3 h Bypass boiler Pump setting Other Safety devices High limit setting C Water flow sensor checked Temp limiter settin...

Страница 30: ...Service ELCO UK 3 Juniper West Fenton Way Southfields Business Park Basildon Essex SS15 6SJ Tel 01268 546700...

Отзывы: