18  Commissioning 

  1.

 

If the installation is unvented, before filling the system with water, check the air 

pressure  in  the  potable  water  expansion  vessel  and  adjust  as  necessary  to  a 
nominal 3.5bar.  

  2.  If  the  pressure  regulating  valve  supplied  with  the  unvented  kit  is  an  adjustable 

type, ensure that the setting is limited at a maximum of 3.5bar.  

  3.  Ensure all drain valves are closed  

  4.  Open a tap at the furthest distance from the cylinder.  

  5.  Open the isolation valve in the water supply to the cylinder, allowing the 

cylinder to fill and air to be expelled from the system via the open tap. Continue 
to allow water to flow from the open tap for some minutes until the water flows 

freely without air and dirt particles.  

  6.  Check/operate each tap in turn on the system to ensure that the pipework is fully 

vented of air and dirt/installation debris is flushed from the installation.  

  7.  Visually check all joints for water tightness.  

  8. 

Check the operation of all relief valves 

by manually opening the valves via the 

attached  levers  and  ensuring  that  the  discharged  water  clears  freely  via  the 
tundish and the discharge pipework. Check that the flow ceases completely when 
the levers are released. 

                                                          

Page 

!

 of 

!

21

25

Immersion Heater

 

9.   Turn on the power supply to the immersion heater/s and allow the cylinder to  

 

heat up.  

10.  Check operation of control thermostat.

    11.  Visually check all joints for water tightness.

    12.  Check that no water is/has issued from the thermal and pressure relief valve or    

expansion relief valve.  

Cylinder and Buffer Vessel

 

   13.   Manually open the motorised valve in the primary circuit and fill, flush and vent    
the primary coil observing any instructions from the boiler manufacturer.  

   14.   Turn on the primary heat source (boiler) and allow the cylinder to heat up.  

   15.  Check operation of control thermostat and motorised valve

   16.   Visually check all joints for water tightness.

   17.   Check that no water is/has issued from the thermal and pressure relief valve or    

expansion relief valve.  

Содержание Polywarm-Maxi PWB-1000

Страница 1: ...axi PWC Indirect Hot Water Cylinders and PWB Buffer Vessels Models PWC1 500 800 1000 1500 PWC2 500 800 1000 1500 Models PWB 500 800 1000 1500 2000 2500 3000 Page 1 of 25 Installation and Operating Ins...

Страница 2: ...h Directive 2014 68 EU PED and the Regulations 812 2013 and 814 2013 issued by Directive 2009 125 EC ErP EcoDesign Requirements for Energy Related Products and by Directive 2010 30 EC Energy Labelling...

Страница 3: ...awn to the following documents for best practice Statutory Instruments Water Supply Water Quality England Wales Regulations 2016 as amended The Public Water Supplies Scotland Regulations 2014 as amend...

Страница 4: ...onella in Health Care Premises Code of Practice 2006 General Requirements All connections to the local water main must comply with Water Supply Water Fittings Regulations 1999 as amended Compliance wi...

Страница 5: ...tation 5 Blind inspection flange 6 Primary circuit flow 7 11 4 BSP connection for magnesium anode 8 Connection for immersion heater 10 1 2 BSP tapping for instrumentation 11 Re circulation 13 T P valv...

Страница 6: ...lation Unvented models require necessary safety equipment SRV PRV Safety relief pressure reducing valve including check valve external expansion vessel tundish and a T P Temperature and Pressure relie...

Страница 7: ...ping for instrumentation 4 1 2 BSP tapping for instrumentation 11 Re circulation 5 Blind inspection flange 12 Upper coil flow 6 Primary circuit flow 13 T P valve 7 1 2 BSP tapping for instrumentation...

Страница 8: ...e use of forklift when handling and drain pipe already fitted Note 500 model Hard foam insulation applied to tank All other models Removable soft fleece insulation Unvented models require necessary sa...

Страница 9: ...2 2 3 Performance data Page 9 of 25...

Страница 10: ...g for instrumentation 8 9 1 2 BSP tapping for instrumentation 10 Connection for immersion heater 11 Re circulation 12 T P valve 13 Alternative return from external heat source source 14 Domestic hot w...

Страница 11: ...require necessary safety equipment SRV PRV Safety relief pressure reducing valve including check valve external expansion vessel tundish and a T P Temperature and Pressure relief valve These are supp...

Страница 12: ...2 3 3 Performance data Page 12 of 25 2 3 4 Unvented kits...

Страница 13: ...o filling the system After a few days of operation it is good practice to check the integrity of all joints including the tightness of the inspection flange bolts accessible by removing the cover 5 PW...

Страница 14: ...d kit is nominally sized to accommodate the capacity of the cylinder with which it was supplied plus a nominal system pipework volume of approximately 17 5 of the cylinder capacity If the system pipew...

Страница 15: ...ontrol and load circuits 15 Electrical connections for optional powered anode In areas of the country that have particularly soft water and therefore poor conductivity of the water less than 200 micro...

Страница 16: ...ontactors are suitable for the electrical load and that an earth is connected to the heater refer to Fig 14 Check that the thermostat safety cut out is correctly wired to ensure complete shutdown of t...

Страница 17: ...Page of 17 25 Figure 16 Immersion heater wiring diagrams...

Страница 18: ...axi SSC1 10 Re circulating pump 11 Hot water outlets 12 Temperature pressure relief valve 13 De Stratification pump 14 Primary heating circuit flow 15 Primary heating circuit return 16 Pressure relief...

Страница 19: ...ts 12 Temperature pressure relief valve 13 De Stratification pump 14 Primary heating circuit flow 15 Primary heating circuit return 16 Pressure relief valve 17 Immersion heater 18 Two port motorised v...

Страница 20: ...ting valve 3 Strainer 4 Pressure reducing valve 5 Expansion vessel 6 Non return valve 7 Expansion relief valve 8 Drain valve 9 Inox Maxi SSC1 10 Re circulating pump 11 Hot water outlets 12 Temperature...

Страница 21: ...k all joints for water tightness 8 Check the operation of all relief valves by manually opening the valves via the attached levers and ensuring that the discharged water clears freely via the tundish...

Страница 22: ...ur on initial opening of a hot water tap on a unvented hot water system and does not indicate a fault Page of 22 25 20 Regular Maintenance To ensure safe and continued performance of the water heater...

Страница 23: ...lways be in manual mode and its activation will be at the discretion of the user using the keypad on the control panel Electrical resistance P3 ON OFF In manual mode the user sets the temperature of t...

Страница 24: ...ary Probe 2 Range of operation 50 C 125 C Range of measurement 0 110 C 1 C T3 22 23 Primary Probe 3 Range of operation 50 C 125 C Range of measurement 0 110 C 1 C OUTPUTS P1 3 4 Primary Control 1 230...

Страница 25: ...600 Fax 01268 88250 www elco co uk This publication is issued subject to alteration or withdrawal without notice The illustrations and specifications are not binding in detail All offers and sales are...

Отзывы: