5 6 mm
IGNITION ELECTRODE
The ionization current is checked by inserting a microam-
meter with an end of scale of 1000 µA (d.c.) in series with
the ionization probe. A faulty position of the electrode can
lead to a reduction in the ionization current and cause a
safety cut-out of the burner due to a flame detection failu-
re. In this case, check the position of the electrode, its elec-
tric connection and the earthing of the burner. The ioniza-
tion current is normally > 70 µA.
IONIZATION CURRENT
22 23
LANDIS
LFL 1.622
Fotocellula
min 70
μA
Microamperometro
fondo scala 1000 μA
PHOTORESISTOR
Microamperometer
full scale 1000 µA
REMOVING THE FIRING HEAD
WARNING !