elco ELK22MP Скачать руководство пользователя страница 4

EL.CO. S.R.L.  – ELK22MP

 

INSTRUCTIONS FOR USE 

- Ver.05 - 03/22 - PAG. 4 

 

3.4  –  PROGRAMMING  VIA  ETHERNET  TCP  /  IP  (only  for 
ELK22MPE models) 
 
3.4.1 – DESCRIPTION 

ELK22MPE  devices  are  equipped  with  an  RJ45  Modbus  TCP  /  IP 
communication  interface.  At  rest,  the  module  is  in  receiving 
condition  and  transmits  after  receiving  and  decoding  a  correct 
message addressed to it. 

 

 

The poll rate during programming and in use must not be 

less than 50ms. 
In  case  of  using  a  number  greater  than  8  ELK22MPS  the 
recommended poll speed is greater than or equal to 80ms. 
 
3.4.2 – COMMUNICATION PROTOCOL DESCRIPTION 

The protocol is a subset of the widely used MODBUS RTU protocol. 
This choice guarantees ease of connection to many PLCs and to all 
commercial supervision programs. 
The  connection  between  the  ELK22MPE  centralizer  with  the 
ELK22MPS  slaves  is  via  bus,  which  can  be  purchased  as  an 
accessory. (see Paragraph 10.6) 
 

The default IP address is 10.10.10.50. 
The default SUBNET MASK address is 255.255.255.0 
The default GATEWAY address is 0.0.0.0 
 

For those wishing to develop their own application software, all the 
necessary tips and information are available. 
The  MODBUS  TCP  /  IP  protocol  functions  implemented  in  the 
EKL22MPE instruments are: 
 
 

Function 1 -  output status read 

 

Function 3 -  n word read 

 

Function 6 -  one word write 

 

Function 7 -  allarm status read 

 
These functions (see Paragraph 8) allow the supervision program to 
read  and  modify  any  data  of  the  module.  The  communication  is 
based  on  messages  sent  from  the  centralization  station 
(ELK22MPE)  to  a  slave  station  (ELK22MPS)  and  vice  versa.  The 
slave  station  which  recognizes  its  address  in  the  message, 
analyzes  its  content  and,  if  it  finds  it  formally  and  semantically 
correct, generates a reply message for the master. 
 
The communication process involves four types of messages: 
                  
 From the centralizer to the slave: 

 

Function 1: output status read request 

 

Function 3: n word read request 

 

Function 6: one word write request 

 

Function 7: allarm status read request 

 
From the slave to the centralizer: 

 

Function 1: output status read replay 

 

Function 3: n word read replay 

 

Function 6: one word write replay 

 

Funzione 7: allarm status read replay 

 

Each message contains six fields: 
 

 

header: 2 bytes of unique identification code 

 

control: 2 bytes always at 0 

 

length: length of the packet excluding the first 6 bytes 

 

slave  address:  the  values  between  1  and  255  are  valid; 
address  0  (zero)  is  reserved  by  MODBUS  RTU  for  the 
diffusion of messages, but is not adopted in the ELK22MP 
series  due  to  the  implicit  unreliability  of  this  type  of 
communication; 

 

function code: contains 1 or 3 or 6 or 7 depending on the 
specified function; 

 

information  field:  contains  the  addresses  or  the  value  of 
the words, as required by the function in use; 

 

The functions described for the TCP / IP protocol are found in 
Paragraph 8. 

 

3.4.3 – DATA EXCHANGE 

The  data  exchanged  consists  of  a  16-bit  word.  All  readable  and 
writable  data  appear  as  16-bit  words  allocated  in  the  instrument's 
memory. 
The  operating  and  configuration  parameters  of  the  instrument  can 
be read and written via serial communication. 
 
The configurable parameters are found in Paragraph 6.  

 
 

4 – WARNINGS FOR INSTALLATION AND USE 

 
4.1 – PERMITTED USE 

 

 
The device has been designed as a measurement and 
adjustment  device  in  accordance  with  EN61010-1  for 
operation  at  altitudes  up  to  2000  m.  The  use  of  the 

device  in  applications  not  expressly  provided  for  in  the 
aforementioned  standard  must  include  all  appropriate  protective 
measures.  The  device  CANNOT  be  used  in  hazardous 
(inflammable  or  explosive) environments  without  proper  protection.

 

It  should  be  remembered  that  the  installer  must  ensure  that  the 
electromagnetic  compatibility  rules  are  respected  even  after  the 
device has  been  installed,  possibly  using special  filters.  If a  failure 
or  malfunction  of  the  device  can  create  hazardous  or  dangerous 
situations  for  persons,  animals  or  property,  the  system  must  be 
equipped  with  additional  electromechanical  devices  to  ensure 
safety. 

 
4.2 - MECHANICAL ASSEMBLY 

The  ELK22Mp  module  must  be  installed  on  the  DIM  rail.  Avoid 
placing the inside of the device in places subject to high humidity or 
dirt that  may  cause condensation  or  introduction into  the device of 
parts  or  conductive  substances.  Ensure  that  the  device  has 
adequate  ventilation  and  avoid  installation  in  containers  where 
devices are located that can lead the device to operate outside the 
declared  temperature  limits.  Install  the  device  as  far  as  possible 
from sources that may generate electromagnetic disturbances such 
as motors, contactors, relays, solenoid valves etc. 
Only the frontal panel will be accessible after the installation. 

 

The  programming  device,  in  a  50  x  50  mm  container,  is  designed 
for panel-mounted mounting inside housing.  Then make a 45 x 45 
mm square hole or a 22 mm diameter hole and insert the keypad by 
fastening  it  with  the  supplied  nut.  It  is  recommended  to  mount  the 
special gasket to obtain the degree of frontal protection stated. 
An  installation  not  complying  with  these  instructions  could 
compromise the protection declared.   
 

4.3  

ELECTRICAL CONNECTIONS 

Make  the  connections  by  connecting  only  one  conductor  for  each 
clamp  and  following  the  diagram  shown,  checking  that  the  supply 
voltage  is  that  indicated  on  the  device  and  the  absorption  of  the 
actuators connected to the device is not higher than the maximum 
current  allowed.  The  device,  provided  for  permanent  connection 
within  an  equipment,  does  not  have  either  switch  or  internal 
overcurrent  protection  devices.  It  is  therefore  recommended  to 
provide  for  the  installation  of  an  overcurrent  protection  device 
(500mA fuse for the 230

 

model or 2A fuse for the 24

≂ 

model) and 

a  bipolar  switch/disconnecting  switch,  marked  as  a  disconnecting 
device, which interrupts the power supply of the device. This switch 
must be positioned as close as possible to the device and in a place 
easily accessible by the user. It is also recommended to adequately 
protect  the  supply  of  all  circuits  connected  to  the  device  with 
suitable  items  (i.e.  fuses)  that  are  appropriate  for  circulating 
currents. It is recommended to use insulation cables suitable to the 
voltages, temperatures and operating conditions and to ensure that 

 

Содержание ELK22MP

Страница 1: ...1 For normalized signals 4 20mA 0 10V It is designed for mounting on a din rail The ELK22MP series consists of 4 models 3 of these act as a centralizer and one of them as a slave The models of the ELK...

Страница 2: ...he menu to select a module 5 4 red digits Process value during operation parameter selected during programming 6 4 green digits Setpoint value during operation value of the parameter selected during p...

Страница 3: ...munication speeds adopted range from 1200 to 38400 baudrates and allow very satisfactory performances while remaining well below the limits imposed by the RS485 standard This allows the line to be wir...

Страница 4: ...ters of the instrument can be read and written via serial communication The configurable parameters are found in Paragraph 6 4 WARNINGS FOR INSTALLATION AND USE 4 1 PERMITTED USE The device has been d...

Страница 5: ...and a maximum of 1 to 31 slave devices A devices sequence that have ELK22MPM or ELK22MP as a centralizer must consist of a centralizer device and a maximum of 1 to 15 slave devices Two control units...

Страница 6: ...must be the device to which the line is connected that must have the termination resistor To do this disconnect the resistance from the accessory and continue the line with the cables for RS485 as bel...

Страница 7: ...programming the parameter Cont ON FN the parameter OxF H REG the parameter OyF C REG The adjustment operation operates on outputs depending on the measurement of the setpoint SP1 and hysteresis HPOS...

Страница 8: ...nect one ELK22MP at time and set the ADR parameter before connect the next ELK22MP Example connect and power up the first ELK22MP program the ADR parameter to 0 and power off the system Connect the se...

Страница 9: ...6 LHdo None 0x19 25 AL2 Alarm threshold SSP FSP 0 0x1A 26 HAL2 Hysteresis of alarm remedy 0 100 1 0x1B 27 AL2D Delay of alarm remedy 0 100 0 sec 0 0x1C 28 ADR Module address 1 16 16 0x1D 29 For each m...

Страница 10: ...LSB byte 0 byte1 0x06 byte 2 byte 3 byte 4 byte 5 byte 6 byte 7 7 4 FUNCTION 7 READ ALLARM STATUS The request has the following frame Slave number Function number CRC LSB MSB byte 0 byte1 0x07 byte 6...

Страница 11: ...the following frame Slave number Function number First word address MSB LSB Value to write MSB LSB byte 0 byte1 0x06 byte 2 byte 3 byte 4 byte 5 The normal reply is merely an echo of the request messa...

Страница 12: ...ay outputs and front reinforced between low voltage parts 24 and 240 power supply and relay outputs and low voltage parts static inputs and outputs reinforced between power supply and relay outputs re...

Страница 13: ...ption of the probe Check that the probe is correctly connected to the device and then verify that the probe is working properly 11 2 CLEANING It is recommended to clean the device only with a slightly...

Отзывы: