Burner Functions

Functional Description
Functional Diagram

Starting function

The automatic burner control unit auto-
matically starts the burner when heat is
required by the system.

The motor starts, the ignition is
switched on.

The air damper drive

6a

switches the

air damper

5

to the low-load position (

in ”Basis” design, the air damper is in
the low-load position when the burner
is idle)

Preventilation

The solenoid valve

2

opens nozzle 1

The flame is formed (low load is in
operation).

Switching over to full load

If required by the system, the automatic
burner control unit switches the burner
to full load.

The solenoid valve

3

opens nozzle 2

At the same time, the solenoid valve

7

switches from passage

b–c

to

a–b

The hydraulic air damper drive

6

switches the air damper

5

to full load

(full load is in operation).

The ignition is switched off again
upon activation of full load.

Functional diagram

A Supply oil connection
B Return oil connection
C Combustion air inlet
D

1

Nozzle 1

D

2

Nozzle 2

1

Oil pressure pump with pressure
regulator

2

Solenoid valve for nozzle 1

3

Solenoid valve for nozzle 2

4

Nozzle rod with two nozzles

5

Air damper

6

Hydraulic air damper drive

6a Hydraulic air damper driver for air

cut-off

7

Solenoid valve for air damper drive

8

Combustion air blower

9

Safety solenoid valve (with design
”DIN”)

Safety functions

A

fault shutdown

is effected if:

a flame signal occurs during
preventilation (extraneous light moni-
toring)

no flame occurs within 5
secondsafter starting the burner
(initial oil release)

the flame is extinguished during
operation.

A fault shutdown is indicated by the
flashing lamp in the reset button.
The program timer stops and the
location of the malfunction is indicated
(see Service Instructions, Malfunctions).
After eliminating the malfunction, press
the reset button to start the burner
again.

A

controlled shutdown

is effected if:

the medium temperature or pressure
is reached

the power supply fails.

The burner starts again automatically
as soon as the operating conditions
have returned to normal.

Basis

CEN/ DIN

Содержание EK 4.100 L-ZA

Страница 1: ...09 2005 Art Nr 13 019 533A Operating instructions for authorized experts Light oil burners EK4 L ZA Designs Basis CEN DIN...

Страница 2: ...generators EN 60335 1 Safety of electrical appliances for domestic use Site of installation The burner must not be operated in rooms with aggressive fumes e g hairspray tetrachloroethylene carbon tetr...

Страница 3: ...age 230 400 V 50 60 Hz 230 400 V 50 60 Hz Power consumption 2 5 kW 2 5 kW Weight approx 83 kg 98 kg Burner equipment Electric motor 2800 min 1 2 2 kW 2 2 kW Automatic burner control unit LAL 1 25 LAL...

Страница 4: ...rner tube 10 Flame cup 11 Electric motor 12 Flame monitor 13 Burner housing 14 Air suction box 15 Oil pressure pump 16 Hydraulic air damper drive 17 Inspection glass 18 Ignition transformer Burner typ...

Страница 5: ...onnection B Return oil connection C Combustion air inlet D1 Nozzle 1 D2 Nozzle 2 1 Oil pressure pump with pressure regulator 2 Solenoid valve for nozzle 1 3 Solenoid valve for nozzle 2 4 Nozzle rod wi...

Страница 6: ...terval for flame formation B Burner in operating position B C Burner operation heat generation C Controlled shutdown t1 Pre venting time t2 Safety time t3 Preignition time short t30 Preignition time l...

Страница 7: ...n the scale corre sponds to the zero position in the burner head Adjustment is made by displacing the flame cup after releasing the screw 1 Electrical connection Electric wiring must be carried out by...

Страница 8: ...ump The correct setting is approx 15 20 bar depending on the burner capacity The pressure regulator is actuated by turning the screw 6 Vacuum test suction line The maximum permissible vacuum is 0 4 ba...

Страница 9: ...e Ignition electrodes The ignition electrodes are directed to nozzle 1 Spare ignition electrodes must be bent for replacement at an angle of approx 30 to the nozzle Burner head 1 Oil connection minimu...

Страница 10: ...full load air Tighten the lock nut after adjustment Important Make sure that you do not turn the stops of the hydraulic drive forcefully towards each other i e adjust the stop screws only as long as...

Страница 11: ...een terminals 4 and 5 x Start aborted because the OPEN signal from limit reversing switch A is missing on terminal 8 Terminals 6 7 and 15 remain energized until the fault is eliminated Burner malfunct...

Страница 12: ...a GmbH Aredstr 16 18 2544 Leobersdorf 0810 400010 ELCO Belgium n v s a Pontbeeklaan 53 1731 Zellik 02 4631902 ELCOTHERM AG Sarganserstrasse 100 7324 Vilters 0848 808 808 ELCO GmbH Dreieichstr 10 64546...

Отзывы: