ART. 09/08550-00
PAGINA 5 DI 6
3. Specification:
The instrument shall be re-calibrated at an interval of one year under the
conditions of 18°C-28°C and relative humidity of less than 75%.
3.1 Overview
• The instrument is designed to automatically select measurement functions
and measuring ranges.
• Full range overload protection.
• Allowable max voltage between terminal
to be measured and ground:
600VDC or 600VAC
• Altitude:
max 2000 mt.
• Display unit:
LCD
• Max display value:
6000 numbers
• Polarity indication: automatic indication. "-" indicates negative polarity
• Over range indication:
"0L" or "-0L"
• Sampling rate:
approximately 3 times per second
• Unit display:
to display functions and electric quantity
• Automatic shut-down time:
10 minutes
• Power supply:
1.5V AAA battery ×2
• Battery under-voltage indication:
LCD display symbol
• Temperature coefficient:
less than0.1x accuracy/°C
• Working temperature:
18°C÷28°C
• Storage temperature:
-10°C÷50°C
3.2 Technical parameters
3.2.1 AC current
Measuring range
Resolution
Accuracy
6A
0.001A
±(2.5% R 8 digits)
60A
0.01A
200A
0.1A
-Minimum input current: 0.01A AC current
-Max input current: 200A AC current
-Frequency range: 45÷65Hz
3.2.2 DC voltage
Measuring range
Resolution
Accuracy
600V
0.1V
±(0.5% R 3 digits)
-Minimal input voltage: 0.5V DC
-Maximal input voltage: 600V DC
3.2.3 AC voltage
Measuring range
Resolution
Accuracy
600V
0.1V
±(0.8% R 5 digits)
-Minimal input voltage: 1.0VAC
-Maximal input voltage: 600VAC (valid value)
-Frequency range: 45÷65Hz
3.2.4 Frequency
3.2.4.1 Frequency measurement for the current (A level) through clamp head
Measuring range
Resolution
Accuracy
60.0Hz
0.1Hz
±(1.0% R 5 digits)
1000Hz
1Hz
-Measurement range: 40Hz÷1000Hz
-Input signal range: ≥ 0.2A AC current(valid value)
3.2.4.2 Frequency measurement for the current (V level) through clamp head
Measuring range
Resolution
Accuracy
60.0Hz
0.1Hz
±(1.0% R 5 digits)
1000Hz
1Hz
-Measurement range:40Hz÷1000Hz
-Input signal range:≥ 0.2A AC voltage(valid value)
3.2.5 Electric resistance
Measuring range
Resolution
Accuracy
6KΩ
0.001KΩ
±0.8% R3 digits
-Overload protection: 600VDC or AC (valid value)
3.2.6 Line On/Off test
Measuring range
Resolution
Functions
1W
If the electric resistance of
the line measured is less than
50W, the buzzer inside the
instrument may sound.
-Overload protection: 600VDC or AC (valid value)
4. Operational guidelines
4.1 Reading hold
During the process of measurement, gently touch the key if you want
to hold readings, and monitor’s display value will be locked.
Touch again the key , the readings hold will be removed.
4.2 Backlight
1. In the process of measurement, if the measurement environment is too
dark, press the key for more than 2 seconds to enable backlight
function. Then about 1 minute later, the backlight function will be
automatically disabled.
2. During this process, press the key for 2 sec. to disable backlight.
4.3 Auto shutdown
1. If no operations occur within 10 minutes after the initialization, the
instrument will be in the state of dormancy. Auto shutdown at this moment
can save power consumption. 2 minutes before shutdown, the buzzer will
sound at an interval of 1 minute.
2. Press any key after auto shutdown to wake the instrument into operation.
3. The function of auto shutdown will be disabled if Hz/NCV key is
pressed while the instrument is initialized.
4.4 Preparation for measurement
1. Press the power key for 2 seconds to initialize the instrument. If the battery
voltage is low (approximately ≤2.4V), the monitor will display the symbol
. At this moment, the battery should be replaced. The instrument will
be shut down if the power key is pressed after the initialization.
2. When the instrument is not used for measurement, it will enter the
automatic scan status and display the diagram below.
4.5 Non contact voltage detection (NCV)
1. Press Hz/NVC key for 2 seconds to enable NCV function. Then the
instrument will display
2. Press NCV key and move NCV sensor closer to the lead line to be
measured. The instrument can detect whether the AC voltage of the
measured lead line is >90V. When the instrument detects AC voltage,
the buzzer will sound alarms while backlight flickers.
H
/⁕
H
/⁕
H
/⁕
H
/⁕