Functional Test
The instrument may only be used in properly grounded electrical installations!
If a plug adapter has to be used to test a socket or a lead connection, it is essential to ensure that the
adapter is in a perfect condition and that the protective conductor connection of the adapter is
continuously connected. Using plug adapters without continuous protective conductor leads to faulty test
results.
Prior to usage check that the instrument is in perfect working order, for example at a known voltage
source.
A clear and safe statement concerning the test result can only be given if device is held in hand to ensure
coupling to ground via capacitive electrode.
Prior to using the RCD test function ensure that the connected appliances are switched off.
The test instrument will not detect N/PE reverse.
To test sockets and lead connection wiring, turn on the socket tester by pressing the button.
Then, plug instrument into socket. To carry out measurements properly, socket tester must be held in hand to ensure
coupling to ground via capacitive electrode. A statement regarding the test result is indicated on the LCD.
To switch
ON
backlight briefly press button. To turn
OFF
the instrument apply long press (~1 second) to the
button.
PE-Error recognition
If the symbol „ ” appears, a dangerous contact voltage is present at the PE conductor. In such circumstances the
complete electrical installation must be checked by a qualified electrician.