background image

090070671

 - SCMAS5 - 

TECHNICAL MANUAL

2

FOREWORD

FOR THE INSTALLER:

Please follow carefully the specifications relative to electric and security systems realization further to the manufacturer’s 

prescriptions indicated in the manual provided.

Provide the user the necessary indication for use and system’s limitations, specifying that there exist precise specifications and 

different safety performances levels that should be proportioned to the user needs. Have the user view the directions indicated 
in this document.

FOR THE USER:

Periodically check carefully the system functionality making sure all enabling and disabling operations were made correctly.

Have skilled personnel make the periodic system’s maintenance. Contact the installer to verify correct system operation in case 

its conditions have changed (e.g.: variations in the areas to protect due to extension, change of the access modes, etc…)

-------------------------------

This device has been projected, assembled and tested with the maximum care, adopting control procedures in accordance with 

the laws in force. The full correspondence to the functional characteristics is given exclusively when it is used for the purpose it 
was projected for, which is as follows:

Optical-acoustic device output control module.

Any use other than the one mentioned above has not been forecasted and therefore it is not possible to guarantee the correct 

functioning of the device. Similarly, any other use of this technical manual other than the one it has been compiled for — that is: 

to illustrate the devices technical features and operating mode - is expressly prohibited.

The manufacturing process is carefully controlled in order to prevent defaults and bad functioning. Nevertheless, an extremely low 

percentage of the components used is subjected to faults just as any other electronic or mechanic product. As this item is meant 

to protect both property and people, we invite the user to proportion the level of protection that the system offers to the actual risk 

(also taking into account the possibility that the system was operated in a degraded manner because of faults and the like), as 

well reminding that there are precise laws for the design and assemblage of the systems destinated to these kind of applications.

The system’s operator is hereby advised to see regularly to the periodic maintenance of the system, at least in accordance 

with the provisions of current legislation, as well as to carry out checks on the correct running of said system on as regular 

a basis as the risk involved requires, with particular reference to the control unit, sensors, sounders, dialer(s) and any other 

device connected. The user must let the installer know how well the system seems to be operating, based on the results of 

periodic checks, without delay.

Design, installation and servicing of systems which include this product, should be made by skilled staff with the necessary 

knowledge to operate in safe conditions in order to prevent accidents. These systems’ installation must be made in accordance 

with the laws in force. Some equipment’s inner parts are connected to electric main and therefore electrocution may occur 

if servicing was made before switching off the main and emergency power. Some products incorporate rechargeable or non 

rechargeable batteries as emergency power supply. Their wrong connection may damage the product, properties and the 

operator’s safety (burst and fire).

According to Directive 2012/19/EU on the Waste of Electric and Electronic Equipment 

(WEEE), it is here specified that this Electrical-Electromechanic Device started to be 

commercialized after 13

th

 August 2005, and it shall be disposed of separately from or-

dinary waste products.

DISPOSAL INSTRUCTIONS

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание SCMAS5

Страница 1: ...TECHNICAL MANUAL SCMAS5 Optical acoustic device output control module for AS protocol loop 090070671 www acornfiresecurity com www acornfiresecurity com ...

Страница 2: ... as any other electronic or mechanic product As this item is meant to protect both property and people we invite the user to proportion the level of protection that the system offers to the actual risk also taking into account the possibility that the system was operated in a degraded manner because of faults and the like as well reminding that there are precise laws for the design and assemblage ...

Страница 3: ...ations and serial loop connection LED indicators power supply unit fault LED two colour LED indicator for alarm fault and silencing events Controls rotary dip switches to set ID address 6 pin dip switch to set operating functions Relay contacts carrying capacity 0 5 A 125 VAC 2 A 30 VDC Operating temperature 10 to 55 C 93 r h Weight 58 g Dimensions W 91 6 H 54 7 D 19 mm Distance between centers W ...

Страница 4: ...clip the wires without holding the whole box in your hand the terminal board can be detached To unplug the terminal board Insert the point of a small screwdriver between the green plasic block of the terminal board and the white plastic of the bottom side of the box Gently lever over the whole lenght of the board to make it raise in the arrow s direction pic 2 Pull the board out in the arrow s dir...

Страница 5: ...ic 3 Close the cover and hook the clips again paying attention as not to break them Pic 3 Opening the box and bridge location 4 5 Dip switch setting DIP SWITCH SETTINGS 1 2 and 3 Not used 4 Set to ON if the PSU FAULT clip is free or if it s connected to the fault line of a PSU that sends a 24 V line voltage during fault events no current otherwise Set to OFF if the PSU FAULT is connected to the fa...

Страница 6: ...t Alarm linked devices activated Red double blinking light Alarm linked devices muted by silencing button 7 ANOMALIES An erroneous dip switch setting can cause the module s fault signaling to malfunction The following table describes the effects caused by erroneous settings allowing to find and correct them before the system is actually used EFFECT POSSIBILE REASON The PSU FAULT LED and its remote...

Отзывы: