2

Mounting

The device has degree of protection IP20, and is there-

fore suitable for use in dry interior rooms. The housing is 

made for rail mounting according to EN 60715 in boards 

or cabinets for electrical distribution. The installation is in 

horizontal position, the correct position is when the KNX 

bus terminal is located at the bottom and the terminals  

(    , L, N) for connecting the mains power supply 230 Vac 

are located at the top. For the installation of the device on 

the rail proceed as follows:
•  with the aid of a tool bring the locking device in the fully 

lowered position (1);

•  place  the  upper  edge  of  the  rear  inner  profile  on  the 

upper edge of the rail (2);

•  rotate the device towards the rail (3);

•  push the locking device upward until it stops (4).
Before removing the device, be sure the bus terminals 

have been extracted from their slots. Use a screwdriver 

to slide down the locking device and remove the device 

from the rail.

wer supply 230 Vac to which the device is connected. The 

green LED marked “ON” indicates the device operating.

Reset

The device has a reset pushbutton. After a reset, the bus 

line is not powered for 20 seconds and the bus devices 

connected are restored to their original condition. During 

this interval of time the reset LED (red) is turned perma-

nently on.

1

2

4

3

Configuration and commissioning

Configuration
The device does not require any configuration with ETS

®

 

(Engineering Tool Software) tool. The application software 

APEKAB1TP##.knxprod (## = version) is available in or-

der to add an EK-AB1-TP power supply to an ETS project.
Commissioning
For the commissioning of the device turn on the mains po-

EKINSTGUIDAEKAB1TP

Failure

When the red LED, labeled “I> Imax”, is turned on, this 

means that the KNX output is overloaded or short-circu-

ited. The problem can be solved by removing the cause 

of the short circuit or by reducing the number of KNX de-

vices connected to the line. After the removal of the pro-

blem only the green LED “ON” is turned on, at this time it 

is recommended to reset the line.

bus KNX

EK-AB1-TP

Power supply 640 mA

230 V~
50/60 Hz

I

 ≤ 640 mA

30 V

~

=

1

2

3

L

N

+ 45 °C

ON

I > I

max

L

N

PE

+

-

230Vac

50/60Hz

KNX

bus

DCEKAB1TP

Note. When mounting the device in boards and ca-

binets it shall be provided the necessary ventilation 

so that the temperature can be kept within the ope-

rating range of the device.

Warning! The electrical connection of the device 

can be carried out only by qualified personnel. The 

incorrect installation may result in electric shock or 

fire. Before making the electrical connections, make 

sure the power supply has been turned off.

Warning! In order to supply the KNX bus lines use 

only KNX bus power supplies (e.g. ekinex EK-AB1-

TP or EK-AG1-TP). The use of other power supplies 

can compromise the communication and damage 

the devices connected to the bus.

Electrical connections

Main supply 230 Vac
The connection to the 230 main supply Vac is made with 

screw terminals (    , L, N) located on the upper front of the 

device. Characteristics of the terminal blocks:
•  screw clamping of conductors

•  maximum cross section of conductor 2.5 mm²

•  recommended wire stripping approx. 6 mm

•  torque max 0.8 Nm

KNX bus line
The connection to the KNX bus line is made with the ter-

minal block (black/red) included in delivery and inserted 

into the slot located on the bottom part of the front. Cha-

racteristics of the KNX terminal block:
•  spring clamping of conductors

•  4 seats for conductors for each polarity

•  terminal suitable for KNX bus cable with single-wire 

conductors and diameter between 0.6 and 0.8 mm

•  recommended wire stripping approx. 5 mm

•  color  codification:  red  =  +  (positive)  bus  conductor, 

black = - (negative) bus conductor

!