Configuration and commissioning

Configuration  and  commissioning  of  the  device  require 

the use of the ETS

®

 (Engineering Tool Software) program 

V4 or later releases. These activities must be carried out 

according to the design of the building automation system 

done by a qualified planner.
Configuration
For the configuration of the device parameters the corre-

sponding application program or the whole ekinex

®

 pro-

duct database must be loaded in the ETS program. For 

detailed information on configuration options, refer to the 

application manual of the device available on the website 

www.ekinex.com

Disposal

At the end of its useful life the product 

described in this datasheet is classified 

as waste from electronic equipment in 

accordance with the European Direc-

tive 2002/96/EC (WEEE), and cannot 

be disposed together with the munici-

pal undifferentiated solid waste.

Documentation

This datasheet refers to the release A1.0 of the ekinex

®

 

device EK-FA1-TP, and is available for download at www.

ekinex.com as a PDF (Portable Data Format) file.

File name

Device release

Updating

STEKFA1TP_EN.pdf

A1.0

03 / 2014

Warnings

•  Installation,  electrical  connection,  configuration  and 

commissioning of the device can only be carried out by 

qualified  personnel  in  compliance  with  the  applicable 

technical standards and laws of the respective countri-

es

•  The use of the device in security applications is not al-

lowed.The device may however be used for auxiliary 

Marks

•  KNX

•  CE: the device complies with the Low Voltage Directi-

ve (2006/95/EC) and the Electromagnetic Compatibility 

Directive (2004/108/EC). Tests carried out according 

to EN 50491-2:2010, EN 50491-3:2009, EN 50491-4-

1:2012, EN 50491-5-1:2010, EN 50491-5-2:2010, EN 

50428:2005 +A1:2007 + A2:2009

Maintenance

The device is maintenance-free. To clean use a dry cloth. 

It must be avoided the use of solvents or other aggressive 

substances.

Warning! Incorrect disposal of this product may 

cause serious damage to the environment and hu-

man health. Please be informed about the correct 

disposal procedures for waste collecting and pro-

cessing provided by local authorities.

Warning! Sockets controlled via bus must be cle-

arly identified. Controlling loads with mobile installa-

tion (e.g. household appliances connected to mains 

sockets) must be planned and realized with a care-

ful evaluation of the risks that may arise in the case 

of control without direct visual contact with the load 

(remote  control).  Connecting  loads  different  than 

those planned, remote controlling without direct ve-

rification of the current conditions of the connected 

load or automatic controlling based on scenes or 

time-scheduling can cause serious damage to pe-

ople and objects.

Product 

code

Application

software

(## = release)

Communica-

tion objects

(max nr.)

Group 

adresses

(max nr.)

EK-FA1-TP     APEKFA1TP##.knxprod

76

254

Note. The configuration and commissioning of KNX 

devices require specialized skills. To acquire these 

skills, you should attend the workshops at KNX cer-

tified training centers.

Commissioning
For commissioning the device the following activities are 

required: 
•  make the electrical connections as described above; 

•  turn on the bus power supply; 

Warning! The electrical connection of the device 

can be carried out only by qualified personnel. The 

incorrect installation may result in electric shock or 

fire. Before making the electrical connections, make 

sure the power supply has been turned off. 

72

90

45

70

5

25

20

20

EK-FA1-TP

4xD.O. 10A/230Vac 

~

 50/60 Hz

1

2

3

4

5

6

7

8

0N

0FF

C1

0N

0FF

C2

0N

0FF

C3

0N

0FF

C4

C1

C2

C3

C4

bus KNX

•  recommended wire stripping approx. 6 mm

•  torque max 0.8 Nm

In case of connection of loads powered at SELV voltage, 

it is necessary to leave an output channel unused (cor-

responding to a pair of terminals) between the outputs 

connected to loads with different voltages.

•  switch the device operation to the programming mode 

by pressing the programming pushbutton located on 

the front side of the housing. In this mode of operation, 

the programming LED is turned on; 

•  download into the device the physical address and the 

configuration with the ETS

®

 program. 

At the end of the download the operation of the device 

automatically returns to normal mode; in this mode the 

programming LED is turned off. Now the bus device is 

programmed and ready for use.

Dimensions [mm]

DCEKF

A1TP

L

N

C1

1

2

C2

3

4

C3

5

6

C4

7

8

!

!

!

i