Pag. 2

 

 

 

 

1) 

KNX bus line terminal blocks 

2) 

KNX programming pushbutton 

3) 

KNX programming LED 

4) 

Power supply terminal blocks 

5) 

1-way microswitch A 

6) 

Ethernet port 

7) 

Ethernet port LED 

8) 

Device satus LED 

9) 

DMX communication LED 

10) 

KNX communication LED 

11) 

Device error LED 

12) 

RS485 serial line terminal blocks 

13) 

1-way microswitch B 

 

Command elements 

•  Pushbutton that switches between normal mode 

and KNX physical address programming. 

 
1-way microswitches 

•  A - OFF: normal mode active. ON: Boot mode active 
•  B - OFF: open. ON: RS485 line termination inserted 

(120 

  termination resistance in parallel between 

RT+ and RT-) 

 

Display elements 

The device can run according to two operating modes: 

Normal mode (configuration loaded, Modbus and KNX 

communication running) and Boot mode (no 

configuration or configuration still loading). 
•  Green LED (8) – Device status. Normal mode: Slow 

blinking (~1 Hz). Boot mode: ON= device on; OFF=

 

device off. 

•  Yellow LED (9)  –  DMX communication. Normal 

mode: blinks when a frame is received on the 

RS485 port. Boot mode: if  fast blinking: no 

configuration, if very slow blinking (~0,5 Hz): loading 

configuration. 

•  Yellow LED (10)  –  KNX communication. Normal 

mode: blinks when a frame is received. Boot mode: 

if fast blinking: no configuration, if very slow blinking 

(~0,5 Hz): loading configuration. 

•  Yellow LED (11) – Device error. Normal mode: ON=

 

at least one DMX  request did not get a correct 

answer; OFF=

 

no error. Boot mode: if fast blinking: 

no configuration, if very slow blinking  (~0,5 Hz): 

loading configuration. 

•  Green LED (7) – Ethernet port. Normal mode: ON=

 

Ethernet connector plugged; OFF= Ethernet 

connector unplugged. Boot mode: ON=

 

Ethernet 

connector plugged; OFF= Ethernet connector 

unplugged. 

•  Red  LED  (3)  –  KNX programming. Normal mode: 

ON=

 

physical address programming mode on; 

OFF=

 

physical address programming mode off. Boot 

mode: if fast blinking: no configuration, if very slow 

blinking (~0,5 Hz): loading configuration. 

 

Installation 

The device has IP20 protection degree and is therefore 

suitable for dry indoor environments. The case is 

suitable for mouting on a DIN rail (according to EN 

60715) inside eletrical distribution cabinets. The proper 

installation involves the bus terminal blocks to be in the 

lower side. 

For installation proceed as follows: 

 

•  with the aid of a tool bring the locking device in 

completely lowered position (1); 

•  place the device on the upper edge of the DIN rail 

(2); 

•  rotate the device towards the DIN rail (3); 
•  push the locking device up untili il stops (4). 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To unmount the device, make sure to unplug the 

network connection and the bus terminal from its 

housing.

 

Use a screwdriver to slide down the lock and 

remove the device from the rail. 

 

 

Note. 

It is recommended to install the device so to 

always guarantee full frontal accessibility, in order to 

properly display the status LEDs. 

 

1

 

2

 

5

 

4

 

12

 

6

 

7

 

8

 

9

 

10

 

11

 

13

 

3

 

ON

ON

1 2

8...24 Vac

+V

0V

POWER S.

12...35 Vdc

3 4 5

RS485

ETHERNET

Dev.

Line

Area

KNX

Device state

DMX

EK-BK1-TP

DMX / KNX TP Converter

Failure

RT-

Com

RT+

DC
EKB
K1

TP

 

Ins

er

ire 

cod

ice i

m

m

agi

ne

 