2.   INTRODUCTION

The Ei168 

RadioLINK

Base transmits a Radio Frequency (RF) alarm signal when

the unit attached to it senses fire.  When it receives an RF alarm signal from anoth-
er Ei168 Base, the attached smoke or heat alarm will sound.  It therefore eliminates
the need to run long interconnect wires between all the smoke alarms on different
floors and in different rooms.

It is designed for use with the Easi Fit range of Mains Powered Smoke/Heat
Alarms.  The 

RadioLINK 

Base itself, is also mains powered and has rechargeable

lithium cells for back-up in the event of mains failure.  The 

RadioLINK

Base will

normally be wired to the nearest mains circuit in the ceiling (usually the lighting
circuit, provided unswitched live is available).  The  Smoke/Heat Alarm is then slid
on to the 

RadioLINK

Base rather than to its normal mounting plate.  As many as

12 units can be interconnected in this way.

It is essential to house code the 

RadioLINK

Bases to ensure they will not

accidently signal to nearby systems.  This is easily done as explained in
section 3 below.

(The units will all communicate with each other (provided they are within range) as installed
i.e. without any house coding).

With an Ei410 Remote Control (optional) the system is much more versatile and
user-friendly.  It allows you to remotely test, silence nuisance alarm (Ei161R &
Ei166R only) and even quickly locate which unit is sensing fire.

2

Содержание RadioLINK Ei168

Страница 1: ...al for use with Smoke Heat Alarms Contains vital information on the products operation and installation Read and retain carefully If you are just installing this product the manual MUST be given to th...

Страница 2: ...TINGTHE REPEATER FUNCTION 5 TROUBLESHOOTING RF LINK 6 LIMITATIONSOF RADIO COMMUNICATIONS 7 CHECKING MAINTAININGYOUR SMOKEALARMSYSTEM 8 GETTINGYOUR RadioLINK BASESERVICED 9 FIVEYEARGUARANTEE 10 TECHNIC...

Страница 3: ...he Ei168 RadioLINK Base This will auto matically activate the rechargeable back up cells Repeat this procedure for all alarms in the system see page 5 1 3 To House Code insert a small screwdriver into...

Страница 4: ...se will normally be wired to the nearest mains circuit in the ceiling usually the lighting circuit provided unswitched live is available The Smoke Heat Alarm is then slid on to the RadioLINK Base rath...

Страница 5: ...ying with the advice in the Smoke Heat Alarm instruction leaflet 2 Disconnect the AC mains supply from the circuit that is going to be used 3 Carefully align the RadioLINK Base and screw into place as...

Страница 6: ...surface a position the mounting plate so the cable trunking is as shown in figure 3 b Carefully cut and trim the knockouts in the RadioLINK Base side walls to blend with the contours of the trunking...

Страница 7: ...ill minimize their effect on the radio aerial 7 Replace the wiring cover 8 Remove the required Smoke Heat Alarm from the box discard the mounting plate supplied Carefully line up the smoke heat alarm...

Страница 8: ...perty within 15 minutes before the timeout period expires If any other RadioLINK accessories are to be used they must also be put into the house code mode at this time see their instructions leaflets...

Страница 9: ...arms with nearby systems Finally attach the label provided to the distribution board to identify the alarm circuits Note To clear house codes see section 10 Technical Specification 4 ACTIVATING THE RE...

Страница 10: ...er Note To deactivate the Repeater function see section 10 Technical Specification 5 TROUBLESHOOTING RF LINK If when checking the radio link interconnection some of the alarms do not respond to the bu...

Страница 11: ...ange of existing units even though they may have already been house coded correctly in the system It is important therefore to check that all detectors are communicating in their final installed posit...

Страница 12: ...operating frequencies regardless of the house coding The Ei168 RadioLINK Base has been tested to EN 300 220 1 V1 3 1 200 09 in accordance with the requirements of EN 300 220V1 1 1 2000 09 These tests...

Страница 13: ...on If it is off check circuit breakers fuses and wiring etc Check the red light on the cover flashes every 40 seconds ii Press the test hush button for up to 20 seconds on each unit The horn will soun...

Страница 14: ...ins rechargeable cell back up is checked directly after installation and then at least yearly as follows i Check that the amber light on the side of the RadioLINK Base is not flashing once every 10 se...

Страница 15: ...n installed correctly and is receiving AC power green light on in smoke heat alarms contact Customer Assistance at the nearest address given at the end of this leaflet If it needs to be returned for r...

Страница 16: ...g Your RadioLINK Base Serviced We shall at our discretion repair or replace the faulty unit Do not interfere with the RadioLINK Base or attempt to tamper with it This will invalidate the guarantee but...

Страница 17: ...em A maximum number of 12 Ei168 units can communicate together on one system however the range is likely to be the limiting factor in many cases Communication All units will communicate together as sh...

Страница 18: ...signal range Activating the Repeater Function Press and hold the test button until the alarm sounds and the amber light comes on then immediately while the light is on press and hold the House Code sw...

Страница 19: ...locate RF linked Smoke Heat Alarms Ei428 RadioLINK RELAY MODULE This module is a device that switches a relay upon receipt of an alarm signal from a suitable Ei smoke heat alarm Ei407 RadioLINK MANUAL...

Страница 20: ...ess Park Maesbury Road Oswestry Shropshire SY10 8NN U K Telephone 0870 7584000 www aico co uk Ei Electronics Shannon Industrial Estate Shannon Co Clare Ireland Telephone 353 61 471277 www eielectronic...

Отзывы: