EIPL rm85 Скачать руководство пользователя страница 6

 

 

 

 

Page 6 of 12 

Drawing   : - TPC408 
Issue 

: - 3 

Date 

: - 08/08/14 

 

 

ROUTINE MAINTENANCE 

 
 

 
 
 
 
 
 
 
To  ensure  continued  full  efficiency  of  the  dehumidifier,  maintenance 
procedures should be performed as follows: 
 

 

 

1.  Clean the surface of the evaporator and condenser coils by blowing the 

dirt out from behind the fins with compressed air. Hold the nozzle of the 
air  hose  away  from  the  coil  to  avoid  damaging  the  fins.  Alternatively, 
vacuum clean the coils. 

 

 

 
 
 
 

 

2.  Check that the fan rotates freely.  

The fan motor is sealed for life and 

therefore does not need oiling.

 

 
 

3.  To check the refrigerant charge, run the unit for 15 minutes and observe 

the  evaporator  coil.  It  should  be  evenly  frost  coated  across  its  surface.  
At  temperatures  above  78

°

F,  the  coil  may  be  covered  with  droplets  of 

water  rather  than  frost.    Partial  frosting  accompanied  by  frosting  of  the 
thin capillary tubes, indicates loss of refrigerant gas or low charge.  

 
 

4.  Check all wiring connections. 

 
 

5.  In order to check the defrost operation, the unit needs to be operated in 

an  ambient  temperature  of  less  than  59°F  for  at  least  1  hour.  When 
operated  In  this  condition  the  unit  should  defrost  at  least  once  every 
hour. The  defrost  mode  can  be  monitored  by  observing  the  ice  melting 
on  the  coil  face,  prior  to  defrost  the  face  will  show  a  white  coating  of 
frost, which should clear during defrost 

 

I

F ANY OF THE PRECEDING PROBLEMS OCCUR

,

 CONTACT THE 

E

BAC 

S

ERVICE 

C

ENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO 

PREVENT PERMANENT DAMAGE

.

       

 

WARNING: 

ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN 

DISCONNECTED BEFORE CARRYING OUT ROUTINE 

MAINTNENANCE ON ITEMS 1, 2, 3, 4 & 5 

WARNING:

 

DO NOT STEAM CLEAN REFRIGERATION COILS 

Содержание rm85

Страница 1: ...Page 1 of 12 Drawing TPC408 Issue 3 Date 08 08 14 RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Страница 2: ...2 of 12 Drawing TPC408 Issue 3 Date 08 08 14 RM85 PACKAGE CONTENTS Item Description Quantity 10560RG US Dehumidifier 1 3086144 Quick release hose coupling 1 3944110 PVC Tube 3 8 I D 7 8M TPC408 Manua...

Страница 3: ...air is therefore discharged from the dehumidifier at a slightly higher temperature with a lower absolute humidity than that which entered Continuous circulation of air through the dehumidifier gradua...

Страница 4: ...erants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data labe...

Страница 5: ...l ii If the air temperature is above 78 F frost and or droplets of condensed water should cover the entire evaporator coil F When the unit is operated in ambient of less than 59 F a defrost cycle shou...

Страница 6: ...e covered with droplets of water rather than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiring connections 5...

Страница 7: ...he refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing...

Страница 8: ...as 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass valve 1 Contact the Factory Ser...

Страница 9: ...3 1 6 Filter 2056004 1 7 Capillary 3014254 2 X 2ft 8 Solenoid valve 3020837 1 9 Filter dryer 3020909 1 10 Compressor 3022198 1 11 Defrost Relay 3030269 1 12 Solenoid coil 3030451 1 13 Hour meter 30307...

Страница 10: ...Page 10 of 12 Drawing TPC408 Issue 3 Date 08 08 14...

Страница 11: ...Page 11 of 12 Drawing TPC408 Issue 3 Date 08 08 14...

Страница 12: ...ww eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www eba...

Отзывы: