ROUTINE SERVICE 

 

 
 
 
 
 
 
 
To ensure continued full efficiency of the dehumidifier, service procedures 
should be performed as follows: 
 

 

1. 

Clean the surface of the evaporator and condenser coils by blowing the 
dirt out from behind the fins with compressed air. Hold the nozzle of the 
air hose away from the coil to avoid damaging the fins. Alternatively, 
vacuum clean the coils. 

 
 
 
 
 
2. 

Check that the fan rotates freely.  

The fan motor is sealed for life and 

therefore does not need oiling.

 

 
3. 

To check the refrigerant charge, run the unit for 15 minutes and observe 
the evaporator coil. It should be evenly coated with frost across its 
surface.  At temperatures above 25

°

C, the coil may be covered with 

droplets of water rather than frost.  Partial frosting accompanied by 
frosting of the thin capillary tubes, indicates loss of refrigerant gas or low 
charge.  

 
4. 

Check all wiring connections, including mains cable for damage or loose 
connections. 

 
5. 

In order to check the defrost operation, the unit needs to be operated in 
an ambient temperature of less than 15°C for at least 1 hour. When 
operated In this condition the unit should defrost at least once every 
hour. The defrost mode can be monitored by observing the ice melting 
on the coil face, prior to defrost the face will show a white coating of 
frost, which should clear during defrost 

 
 

I

F ANY OF THE PRECEDING PROBLEMS OCCUR

,

 CONTACT THE 

E

BAC 

S

ERVICE 

C

ENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO 

PREVENT PERMANENT DAMAGE

.

   

 

WARNING: 

ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN 

DISCONNECTED BEFORE CARRYING OUT ROUTINE SERVICE. THE 

SERVICING AND REPAIR OF THIS UNIT SHOULD ONLY BE CARRIED 

OUT BY A SUITABLY QUALIFIED PERSON. 

 

WARNING:

 

DO NOT STEAM CLEAN REFRIGERATION COILS 

Содержание BD75P

Страница 1: ...Page 1 of 12 Drawing TPC476 Issue 2 Date 11 04 19 BD75P INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Страница 2: ...phase plus the additional heat generated by the compressor The air is therefore discharged from the dehumidifier at a slightly higher temperature with a lower absolute humidity than that which entered...

Страница 3: ...al GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the p...

Страница 4: ...e the evaporator coils through the rear grille to confirm frost formation or weeping If the air temperature is below 25 C an even coating of frost should cover the entire evaporator coil If the air te...

Страница 5: ...ng accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiring connections including mains cable for damage or loose connections 5 In order t...

Страница 6: ...he refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing...

Страница 7: ...fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass va...

Страница 8: ...019712 1 5 Capillary 3014251 1 64ft 6 Solenoid valve 3020836 1 7 Filter dryer 3020937 1 8 Solenoid coil 3030452 1 9 On Off switch 3035914 1 10 Fan Motor 3947013 1 11 Fan Blade 3947014 1 12 Castor 3050...

Страница 9: ...to Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407...

Страница 10: ...Page 10 of 12 Drawing TPC476 Issue 2 Date 11 04 19...

Страница 11: ...Page 11 of 12 Drawing TPC476 Issue 2 Date 11 04 19...

Страница 12: ...ww eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www eba...

Отзывы: